it is possible for the scrolls to seal, preventing pressure equalization through the compressor. This
may leave the low side shell and suction line tubing pressurized. If a brazing torch is then applied to
the low side while the low side shell and suction line contain pressure, the pressurized refrigerant
and oil mixture could ignite when it escapes and contacts the brazing flame. To prevent this
occurrence, it is important to check both the high and low sides with manifold gauges before
unbrazing. Instructions should be provided in appropriate product literature and assembly (line repair)
areas. If compressor removal is required, the compressor should be cut out of system rather than
unbrazed.
7
Dismantling & disposal
Removing oil and refrigerant:
Do not disperse in the environment.
Use the correct equipment and method of removal.
Dispose of oil and refrigerant properly.
Dispose of compressor properly.

DISCLAIMER

1. The contents of this publication are presented for informational purposes only and are not to be
construed as warranties or guarantees, express or implied, regarding the products or services
described herein or their use or applicability.
2. Emerson Climate Technologies GmbH and/or its affiliates (collectively "Emerson"), as
applicable, reserve the right to modify the design or specifications of such products at any time
without notice.
3. Emerson does not assume responsibility for the selection, use or maintenance of any
Responsibility for proper selection, use and maintenance of any Emerson product remains solely
with the purchaser or end user.
4. Emerson does not assume responsibility for possible typographic errors contained in this
publication.
C6.2.7/1007-0619/E
product.
23

Advertisement

Table of Contents
loading

Table of Contents