This product is design with a probe style sensor to reach into ducted flows in building, process, datacenter and HVAC applications. An instrumentation class sensor is used to eliminate trouble alarms and provide best accuracy across wide temperature ranges. The Rooster Sensor100 comes calibrated with NIST certificate, from 0.15 –...
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 Soft Buttons and Home Screen Layout Startup Delay Indicator Night Setback/Mute Indicator Time of Day Asset Tag Status Color (Green, Yellow or Red) Air Velocity (touch to toggle units) Air Temperature Alert Banner (touch to toggle units)
Page 5
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 Toggle Temperature Type Instantly toggle displayed temperature units from Fahrenheit to Celsius or vice versa by pressing on the displayed temperature reading on the home screen. >Home Password-Protected Access Tiers: Certifier & EH&S Password protected access tiers enable advanced configuration options and features.
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 Rear Panel Layout for Advanced Connections Rear Panel View of Rooster Sensor100 Connection Description Connector Type Mating Connector 2-Pin, polarized, Phoenix Power Entry Included and attached to AC/DC power supply Contact Sensor Connection RJ-11 Included as part of sensor assembly Not included.
After configuring your wires, the Rooster Sensor100 is mountable to a cabinet or physical wall panel by first securing the back plate, and, once this is complete, the Rooster will snap right onto the backplate. Two backplate versions are available.
Using the backplate label as a reference, the next step is to prepare the wiring harness for the Rooster Sensor100. Once the wire harnesses are pulled through the opening and attached to the Rooster, then the front touch panel assembly can be snapped into place.
Night Setback Input The Rooster Sensor100 allows the user to connect to the digital input (0V, dry contact), on Input Connector, positions 5 & 6. The purpose of the Night Setback input is to allow the user the ability to send a remote signal to all Rooster Sensor100’s, simultaneously, which changes their behavior during low flow conditions.
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 Set Minimum Alarm Volume Threshold EH&S, Certifier Set Time / Clock Format EH&S, Certifier Toggle between Fahrenheit or Centigrade Temperature Units on Home Screen None Toggle between Metric or Imperial Air Velocity Units on Home Screen...
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 Alarm Troubleshooting Is your alarm failing to sound or clear how you intended? You may need to verify that you have entered valid threshold values. For both normal and NSB modes of operation, the “Alarm Trip” or “NSB Trip” point must be a lower value than the “Alarm Clear”...
Switching the latch state to “OFF” disables this feature entirely. Home> Settings>System>Alarms/Sound>Alarm Controls>Latch Alarm Alarm Delay To account for hysteresis, users can define the amount of time that the Rooster Sensor100 has to achieve continuous safe velocity readings before the alarm state is cleared and continuous unsafe velocity readings before an alarm is triggered.
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 Startup Delay The startup delay prevents an alarm from triggering until the workstation and ventilation systems have fully powered up and are operational. Refer to chart on next page for further definitions. Alarm Delay Definition Alarm is paused for 30 seconds on power up.
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 I/O Polarity For advanced users, it may be helpful to toggle relay and input nodes from N/C to N/O. Consult diagram below for further information. Home>Settings>System>Advanced>I/O Polarity DAC Output The Rooster Sensor100 has DAC Output enabled, with correspondence to air velocity.
Rooster powers up to enter the firmware update sequence) 4. After ~3 seconds, release Home button. After 10 seconds, the LED on the front of the Rooster will light and the unit will boot up with new Firmware.
Rooster™ Sensor100 USER MANUAL 62320MN000-A02 GUI Map WARRANTY The Rooster Sensor100 is warranted to be free from defects in workmanship and materials for a period of one (1) year from receipt. Degree Controls will at its option replace or repair defective parts within the warranty period.