Concorde BC-8000 Field Calibration Procedure

Hide thumbs Also See for BC-8000:

Advertisement

Quick Links

BC-8000 Field Calibration Procedure 55 AMP
CF1_FIELDCAL_BC8000 Revised 9/8/2012
Charger section can be used on a BC-9000 Version 1.00
INTRODUCTION:
The BC-8000 Battery Capacity Analyzer and Charger will perform capacity
testing of 12 and 24 volt lead-acid batteries and charge the batteries.
Capacity testing amperage setting resolution is 0.1A for tests in the range
of 0.5A to 15A and resolution of 1A for tests from 15A to 55A. The micro
processor controlled unit uses quartz crystal timing and will accurately
measure the capacity of a fully charged battery with a rating between 0.5
and 55 amp-hours. Amperage selection resolution is 0.1A for a load of
0.5 to 14.9 amps and 1A resolution for 15 to 55 amps. The BC-8000
saves the date, time, test parameters, and test results. It is equipped with
a USB interface. With the BC Report software the user can retrieve data
from the BC-8000 to create a printable report that includes test settings,
test results, time and date of test, and a battery discharge voltage graph.
The BC-8000 is line powered and easy to operate. The recommended
calibration interval is 1 year.
Battery charging amperage resolution is 0.01 amp from 0.050 to 2.50
amps and 0.1 amp from 2.6 to 25 amps. The battery charger voltage
range is 3.0V to 36.2V. When operating at 3.0V the maximum amperage
is 2 amps. The AC power input is universal 100V to 240V. The charger
can charge in 1 or 2 steps, maximum run time limit on each step, and
operate in constant voltage or constant current mode.
SCOPE:
This document provides instructions on how to perform the annual
calibration for the BC-8000. The calibration is broken down into the
following categories:
Verify timing accuracy
Calibrate Cutoff at 10.00 Volts
Calibrate Cutoff at 20.00 Volts
Calibrate 0.5A, 2.0A, 8.5A, 15A, and 55A calibration points
Calibrate the Seiko clock chip (This is optional. The clock is calibrated
at the factory and requires adjustment if the time keeping accuracy is
unacceptable. The date and time are set to the current PC time by the
BC-8000 report utility every time test results are transferred from the
BC-8000 to the report utility)
Calibrate the charger voltages and currents.
Page 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the BC-8000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Concorde BC-8000

  • Page 1 0.5 and 55 amp-hours. Amperage selection resolution is 0.1A for a load of 0.5 to 14.9 amps and 1A resolution for 15 to 55 amps. The BC-8000 saves the date, time, test parameters, and test results. It is equipped with a USB interface.
  • Page 2 BLACK lead to the negative terminal of the 24V power source. 5. Verify unit is OFF. Connect the BC-8000 to the VOLTAGE OUTPUT CONNECTOR on the CF1 test device. It is the connector that has two #16 AWG smaller wires.
  • Page 3 The crystal oscillator should provide an accurate time base for the entire life of the BC-8000. If the unit fails this test, it is an indication that the crystal time base may have been damaged.
  • Page 4 4. Connect 5 ½ digit DMM plus + to the AMP plus + test point on the CF1 test device. 5. Verify the BC-8000 is OFF. 6. Connect the BC-8000 to the HIGH AMPERAGE CONNECTOR on the CF1 test device. It is the connector wired with two #6 heavy duty wires.
  • Page 5 30. Write the mV reading into the calibration work sheet. (55 Amp calibration) 31. Press NEXT to save the calibration data into memory. Wait for the word “SAVED” to appear then disappear. 32. Turn OFF the BC-8000 power. Page 5...
  • Page 6 24V battery that can accept a 25A charge, a CF1 current shunt, and a DMM. All Voltage OUT and DISP menu items require the output of BC-8000 connected to a DMM and can never be connected to a battery as the unit being calibrated will output various voltages.
  • Page 7 10. Press UP to select OUT 17.0V. Press NEXT to start. Wait for the relays to sequence. Press UP or DOWN button to get as close as possible to 17.0V on the DMM. Press NEXT to save the calibration. 11. Press UP to select DISP 17.0V. Press NEXT to start. Wait for the relays to sequence.
  • Page 8 Press UP or DOWN button to get as close as possible to 25.0A on the LCD display. Press NEXT to save the calibration. Charger menu item and associated BC-8000 output connector hook up. These are the charger menu items and what you should do at each menu item.
  • Page 9 CALIBRATE SEIKO CLOCK CHIP (OPTIONAL): 1. Turn OFF the BC-8000. 2. Connect the USB cable to the PC computer. Start the BC-8000 report utility. Press the “Set Date and Time” button. The software will search for the BC-8000 and establish a connection. Enter “invalid report” into the battery serial number rectangular box.
  • Page 10 8. Sign and date the calibration work sheet. 9. Install the lid and attach it with the 8 screws. Figure 1 (BC-8000 will not have the IC chip U2 shown on the left) Page 10...
  • Page 11 CALIBRATION WORK SHEET RECORDS - BC-8000 S/N___________________ Item name Measured Specification Pass Fail value 450 Hz 449.8 - 450.2 Hz 10.00 Volt cutoff 9.90 - 10.10 Volts 20.00 Volt cutoff 19.80 - 20.20 Volts 0.5 Amp calibration 0.497 to 0.503 mV 2.0 Amp calibration...