NOJA-7343-03 User Manual Ground Mounted Kiosk GMK-1000 Series www.nojapower.com.au...
Page 2
NOJA Power Switchgear product. It contains information that is the intellectual property of NOJA Power Switchgear and the document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear.
NOJA-7343-03 NTRODUCTION The NOJA Power Ground Mounted Kiosk (GMK) is designed for the connection and protection of underground cables for voltages up to 27kV. The kiosk houses an OSM Automatic Circuit Recloser and an RC-10 Controller. This document provides the following information for the GMK: ...
- 40° C to + 55° C - 40° C to + 55° C Input AC Voltage 110/220Vac 110/220Vac Note 1: Subject to the rating of the Dead Break Elbow connectors installed (not supplied). User Manual Ground Mount Kiosk (GMK-1000 Series)
IP65 for the controller compartment IP54 for the customer equipment compartment IP65 for the OSM310-GMK IP54 for the OSM + Cable Compartment. IMENSIONS AND EIGHT Dimensions 1225 x 1341 x 1160 mm Weight 480kg User Manual Ground Mount Kiosk (GMK-1000 Series)
NOJA-7343-03 RAWINGS Note: The GMK is supplied with a blank radio equipment tray. Suitable mounting holes have to be drilled prior to use. User Manual Ground Mount Kiosk (GMK-1000 Series)
Page 8
NOJA-7343-03 Note: The manual trip ring is located in the customer equipment compartment, next to the open/close indicator window. LV supply is through the gland plate on the partition wall. User Manual Ground Mount Kiosk (GMK-1000 Series)
A cable pit must be built for the GMK. A concrete base is recommended. OUNTING ETAILS The GMK has 4 x 14mm diameter mounting holes which can be used for bolting the GMK to the ground. User Manual Ground Mount Kiosk (GMK-1000 Series)
Fork entry holes, 140 x 50mm are available at the bottom of the unit as shown. Where no forklift is available, the GMK can be lifted through the lifting points welded on the enclosure body using slings and a crane. User Manual Ground Mount Kiosk (GMK-1000 Series)
Page 11
NOJA-7343-03 User Manual Ground Mount Kiosk (GMK-1000 Series)
NOJA-7343-03 ABLE NTRIES The GMK is supplied with blank aluminium gland plates for HV, LV and Earth cable entries. Holes must be drilled to suit the compression glands of incoming cables. User Manual Ground Mount Kiosk (GMK-1000 Series)
The Earth Saddles are used to support earth conductors with a stand-off Type C interface when elbow connections are removed from the poles during maintenance. The interface can be earthed through the studs below the saddles. User Manual Ground Mount Kiosk (GMK-1000 Series)
A cable entry has to be prepared on the HV gland plate to suit the incoming main earth cable which will be then connected to the earth bar. The earth bar comes with M12 nut and bolt that can be used in connecting the main earth cable. User Manual Ground Mount Kiosk (GMK-1000 Series)