Contents The Eden Power Tray 6. REVISION HISTORY 7. DISCLAIMER 8. CONTACT DETAILS 9. APPENDICES Cycle Time function (Times menu (Ti13) Defrost Cycle (Fans Off) Defrost Cycle (Fans On) Integral Compressor Action Remote Display 9.5.1 Panel Cut-out 9.5.2 Remote Display 9.5.3 Retaining Clips 9.5.4 Remote Display Module 10.
All high current outputs are protected by re-settable MCB’s. Connector configurations where possible remain identical to previous RCS cabinet control panels to safeguard easy replacement of legacy units. The assisted defrost variants also provide an external connection for defrost heater klixons to provide further safety features.
Part Codes The Eden Power Tray 1.1.1 Variants / Part Codes for Ordering This installation and set-up guide covers the complete Eden Power Tray range. The following part codes should be used at the ordering stage:- Variant Inlet Valve Type Communication Type Part No Off-Cycle defrost...
Connection Details - Hot Gas Defrost The Eden Power Tray 2.5 EP3119, EP3129 (LSV) & EP31110, EP31210 (EEV) (Hot Gas Defrost & KTUC09 Hot Gas Defrost Legacy replacement) - Connectivity Details STV1 Pin Number Function Rating/Designation Earth Not Used Not Used LSV/EEV Live 2A Internal MCB (CB 8) LSV/EEV Neutral...
Hot Gas Defrost Circuit Diagram The Eden Power Tray 2.6 EP3119, EP3129 (LSV) & EP31110, EP31210 (EEV) (Hot Gas Defrost & KTUC09 Hot Gas Defrost Legacy replacement) - Circuit Diagram Installation Guide | Issue 2.0 | The Eden Power Tray Page 12...
Connection Details - External Defrost Contactor The Eden Power Tray 2.7 EP3117, EP3127 (LSV) & EP3118, EP3128 (EEV) (External Defrost Contactor & KTUC09 “Tray” Legacy replacement) - Connectivity Details STV1 Pin Number Function Rating/Designation Earth Not Used Not Used LSV/EEV Live 2A Internal MCB (CB 8) LSV/EEV Neutral Fans Live...
Minor Assisted Defrost Circuit Diagram The Eden Power Tray 2.10 EP3111 (Minor Assisted Defrost Legacy replacement) – Circuit Diagram Installation Guide | Issue 2.0 | The Eden Power Tray Page 16...
Connection Details – Sensors & Comms. The Eden Power Tray 2.13 All Variants – Sensor / communication network connections 12 Way BLZ Pin Number Function Rating/Designation Air On – Signal Air On – Ground Air Off Sensor – Signal Air Off Sensor – Ground Evaporator In Sensor –...
HT and LT variants. If the user wishes to confirm / modify parameters using the RCS system manager then the Eden controllers will need to be logged onto the system to achieve this, please complete the Setup and Address sections as identified on pages 8-11 before proceeding to use the system manager.
Page 22
Setting up the controller The Eden Power Tray Alarm Critical alarm present, see Alarms Menu – Page 10 Service See Parameter Ti9 – Page 18 HACCP See Parameter Su9 – Page 9 Valve Illuminated when Relay 1 is on – Pages 28-29 Fans Illuminated when Relay 2 is on - Pages 28-29 Lights...
Setting up the controller The Eden Power Tray 3.2 Using the front panel display and function keys To enter setup press the FUNCTION and UP buttons simultaneously for greater than 3 seconds until the message appears. Pressing the ENTER key again at this point will allow access to the first item in the setup menu (Su1).
Setting up the controller The Eden Power Tray 3.2.1 Set Up Menu Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, at this point press the ENTER button again and the display will indicate Su1. This is the first item in the set up menu.
Page 25
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information Digital Input 1 0 = Case Clean Case - Case - Default for cabinet type 3 and Function 1 = Door Open Clean - Clean 4 is case clean. If unit type 1 2 = C1 Fault or 2 selected (su1) then default value becomes 2 –...
Setting up the controller The Eden Power Tray 3.2.2 Controller address and communications menu Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the DOWN key once - the display will indicate Addr at this point press the ENTER button and the display will indicate 485A.
Page 27
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information 0 – 255 Sn -2 Sub-Net Address Byte Allows the user to set the second byte of the controllers sub net mask. Note- If DHCP is set to yes this value is not editable.
Setting up the controller The Eden Power Tray 3.2.3 Controllers Refrigeration related parameter menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the DOWN key 2 times - the display will indicate rEF, at this point press the ENTER button and the display will indicate rF1.
Page 29
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information Superheat Setpoint 0.0 - 9.0 °C 6.0°C 6.0°C The controller will attempt to maintain this superheat setpoint N/A will be displayed if LSV version. 0 – 100% EEV Injection Sets the value of the EEV when percentage...
Setting up the controller The Eden Power Tray 3.2.4 Controllers DEFROST menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the DOWN key 3 times - the display will indicate dEF, at this point press the ENTER button and the display will indicate dF1.
Page 31
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information Defrost termination -40.0°C - +35.0°C °C 8.0°C 8.0°C Scheduled defrost will terminate Temperature when the defrost termination sensor reaches this temperature. Note – If the defrost termination sensor is not fitted (or faulty) then defrost termination will occur when the Evap.
Setting up the controller The Eden Power Tray 3.2.5 Controllers Fan related parameter menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the DOWN key 4 times - the display will indicate FAns, at this point press the ENTER button and the display will indicate Fn1.
Page 33
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information Fans On setpoint -10.0°C - +30.0°C °C 50.0°C 5.0°C Cold store Only. (HT) (HT) Defrost termination sensor temperature or Air On -1.0°C -1.0°C temperature which when (LT) (LT) achieved will allow fans to be...
Setting up the controller The Eden Power Tray 3.2.6 Controllers time related parameter menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the DOWN key 5 times - the display will indicate Ti, at this point press the ENTER button and the display will indicate Ti1.
Page 35
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information 0 – 120 ti11 Air Off Alarm Delay Delay for the Air Off OT alarm 00:00 – ti12 Log Probe Alarm hh:mm 00:20 00:20 Delay for the log probe alarm NOTE –...
Setting up the controller The Eden Power Tray 3.2.7 Controllers current status menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the UP key 6 times - the display will indicate StA, at this point press the ENTER button and the display will indicate St1.
Page 37
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information St12 Digital Input 2 Open Displays the current state of controllers Closed digital input 2. Function dependant upon selection made in SETUP menu – Su8 St13 Case Clean Displays if the controller is currently in case clean mode.
Setting up the controller The Eden Power Tray 3.2.8 Controllers current alarms menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the UP key 4 times - the display will indicate ALAr, at this point press the ENTER button and the display will indicate AL1.
Page 39
Setting up the controller The Eden Power Tray Parameter Range Units Deflt Deflt Information Logging Sensor Indicates if the controller Failure currently has a faulty Log temperature sensor. AL10 Door Open Indicates if the controller (Cold store Only) currently has a Door Open alarm Note N/A will be displayed if not type 4 or 5...
Setting up the controller The Eden Power Tray 3.2.9 Controllers lights related parameter menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the UP key 3 times - the display will indicate LtS, at this point press the ENTER button and the display will indicate Li1.
Setting up the controller The Eden Power Tray 3.2.10 Controller sleep mode menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SLP, Press the UP key 2 times - the display will indicate SLP, at this point press the ENTER button and the display will indicate SP1.
Setting up the controller The Eden Power Tray 3.2.11 Controller self test menu. Accessed by pressing and holding the FUNCTION and UP keys simultaneously for greater than 3 seconds. The display will indicate SEt, Press the UP key once - the display will indicate SELF, at this point press the ENTER button and the display will indicate SF1.
Cleaning The Eden Power Tray 4. Cleaning Only use a soft lint-free cloth. Abrasive cloths, towels, paper towels and similar items may damage the Eden controller. Keep any liquids away from the controller; don’t use aerosol sprays, solvents or abrasives. Installation Guide | Issue 2.0 | The Eden Power Tray Page 43...
Specification The Eden Power Tray 5. Specification 5.1 Power requirements: 220 – 240 Vac ±10% Supply Voltage Range: 50 – 60 Hz Supply Frequency: Maximum supply current: 32 Amps Typical supply current: Loading Dependant Operating temperature range: +5C to +50C Operating Humidity: 80% maximum Storage temperature range:...
Revision History The Eden Power Tray 6. Revision History Revision Date Author Amendments Comments 06/08/14 First Draft Issued for internal review 06/02/15 Various Amendments Circuit Diagrams updated. Part Codes Updated. General Text Corrections. Installation Guide | Issue 2.0 | The Eden Power Tray Page 45...
To allow for design and specification improvements, the information contained within this document is subject to change at any time without prior notice. RCS Energy Management shall not be liable for any errors or omissions, for incidental or consequential damages either directly or indirectly resulting from the misuse of this product or associated document.
Contact Details The Eden Power Tray 8. Contact Details RCS Energy Management Limited RMS House Kennet Side Newbury Berkshire RG14 5PX UNITED KINGDOM Tel: +44 (0) 1635 231600 Fax: +44 (0) 1635 231699 Email: sales@rcsenergymanagement.co.uk Website: www.rcsenergymanagement.co.uk Installation Guide | Issue 2.0 | The Eden Power Tray...
Appendices The Eden Power Tray 9. Appendices Appendix 1 9.1 Cycle Time function (Times menu (Ti13) Minimum value 0 Minutes Default Value 60 Minutes Maximum value = 120 Minutes This energy saving feature applies to HT cases with liquid solenoid valve control only, and operates within the standard LSV control loop.
Appendices The Eden Power Tray Appendix 5 9.5 Remote Display The Eden Power Tray range is available in configurations to support remote display requirements. The Eden Compact remote display unit maintains exactly the same fascia dimensions as the compact controller. 9.5.1 Panel Cut-out: 71mm 29mm...
Appendices The Eden Power Tray 9.5.2 Remote Display The remote display unit is robustly held in position by the use of sprung clips at either end of the enclosure. These have been designed to allow the fitment of the module through a panel cut-out from the front. 9.5.3 Retaining Clips: The remote display unit maintains exactly the same functionality as the integral display variant of the Eden Compact with menu access, parameter management and setup the same as previously described within this...
Declaration of Conformity The Eden Power Tray 10. European Declaration of Conformity We of RCS Energy Management Limited RMS House, Kennet Side, Bone Lane, Newbury, Berkshire, RG14 5PX In accordance with the following directive(s): EN 60730-1 (Fourth Edition) 2010 Automatic electrical controls for household and similar use.