Download Print this page

HANYOUNG NUX BK3 Instruction Manual

Digital indicator

Advertisement

Available languages

Available languages

Quick Links

BK3
Digital Indicator
INSTRUCTION MANUAL
Thank you for purchasing
Hanyoung Nux products. Please
read the instruction manual
carefully before using this product,
and use the product correctly. Also,
please keep this instruction manual
where you can see it any time.

▍ Safety information

Please read the safety information carefully before use, and use the product correctly.
The alerts declared in the manual are classified into Danger, Warning and Caution
according to their importance
Indicates an imminently hazardous situation which, if not avoided,
DANGER
will result in death or serious injury
Indicates a potentially hazardous situation which, if not avoided,
WARNING
could result in death or serious injury
Indicates a potentially hazardous situation which, if not avoided,
CAUTION
may result in minor injury or property damage
DANGER
The input/output terminals are subject to electric shock risk. Never let the input/
output terminals come in contact with your body or conductive substances.
WARNING
• If there is a possibility of the product's malfunction or accident, please install the protection circuit outside
• This product does not contain an electric switch or fuse, so the user needs to install a
separate electric switch or fuse externally. (Fuse rating : 250 V 0.5A)
• To prevent defection or malfunction of this product, supply proper power voltage in
accordance with the rating.
• To prevent electric shock or malfunction of product, do not supply the power until the wiring is completed.
• Since this product is not designed with explosion-protective structure, do not use it any place
with flammable or explosive gas.
• Do not decompose, modify, revise or repair this product. This may be a cause of malfunction,
electric shock or fire.
• Reassemble this product while the power is OFF. Otherwise, it may be a cause of malfunction or electric shock.
• If you use the product with methods other than specified by the manufacturer,
there may be bodily injuries or property damages.
• Due to the danger of electric shock, use this product installed onto a panel while an
electric current is applied.
CAUTION
• The contents of this manual may be changed without prior notification.
• Before using the product you purchased, make sure that it is exactly what you ordered.
• Do not use this product at any place with corrosive (especially noxious gas or ammonia)
or flammable gas.
• Do not use this product at any place with direct vibration or impact.
• Do not use this product at any place with liquid, oil, medical substances, dust,
salt or iron contents. (Use at Pollution level 1 or 2)
• Do not polish this product with substances such as alcohol or benzene.
• Do not use this product at any place with a large inductive difficulty or occurring static
electricity or magnetic noise.
• Do not use this product at any place with possible thermal accumulation due to direct
sunlight or heat radiation.
• Install this product at place under 2,000m in altitude.
• When the product gets wet, the inspection is essential because there is a
danger of electric leakage or fire.
• When inputting thermocouple, use the prescribed extension wire.
(using normal wire causes temperature errors)
• When inputting termoresistance, use low lead resistance and null 3-wire resistance difference
(when the 3-wire lead resistance is different it can cause differences in temperature).
• For input signal lines, please avoid power line, power supply line and load line in order
to avoid the influence of induction noise.
• Separate the input signal line and output signal line, and if it cannot separate from
each other, please use shield line for input signal line.
• Please use non-grounded sensor for thermocouple (When using grounded sensor,
it can cause the device's malfunction due to short circuit)
• If there is excessive noise from the power supply, using insulating transformer or
noise filter is recommended. The noise filter must be attached to a panel which is
already connected to a ground and the wire between the filter output and power supply
terminal must be as short as possible.
• When you exchange the sensor, please turn off the power
• After checking the polarity of terminal, connect wires at the correct position.
• When this product is connected to a panel, use a circuit breaker or switch approved with
IEC947-1 or IEC947-3.
• Write down on a panell that if the circuit breaker or switch is operating then the power
will be disconnected since the circuit breaker or switch is installed.
• The warranty period for this product including parts is one year.
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Michuhol-gu,
Incheon, Korea TEL : +82-32-876-4697
http://www.hynux.com
PT.NUX INDONESIA
Kawasan Industri Lippo Cikarang
JI.Cempaka Blok F16,No.02 Delta Silikon II
Cicau Cikarang Pusat,Bekasi Indonesia 17550
TEL : +62-21-4000-2032
MA0902KE181210
▍ Suffix code
Model Code
BK3-
Digital Temperature Indicator 96(W) X 48(H) mm
K
K thermocouple
(refer to the range and input code chart)
K1
J
J thermocouple
R
R thermocouple
P1 Resistance Temperature Detector(RTD)
Input
P2
Pt100 Ω (refer to the range and input code chart)
type
G
0 - 5 V DC
V
1 - 5 V DC
F
0 - 10 V DC
C
4 - 20 mA DC
▍ Specification
Thermocouple
K, J, R
Input sensor
RTD : Pt100 Ω(IEC)
DC voltage
0 - 5 V DC, 1 - 5 V DC, 0 - 10 V DC
DC current
4 - 20 ㎃ DC
Input sampling time
500 ㎳
Input display resolution
Usually less than indication value 1 ℃ (0.1 ℃)
Input impedance
1 ㏁ (thermocouple and DC voltage)
Allowable signal source resistance Thermocouple (100 Ω max), DC voltage (2 KΩ max)
Allowable wiring resistance RTD (10 Ω max) but resistances among 3 wires should be same
Allowable input voltage
Within ±10 V DC (thermocouple, RTD, DC voltage)
±0.5 % of FS ±1 Digit
Display accuracy
(but, if less than 599 ℃ with R input, warranty not applied)
Insulation resistance
20 MΩ min (500 V DC)
Dielectric strength
2,000 V AC 50/60 ㎐, for 1 min, (between the different recharging part)
Power Supply Voltage
110/220 V AC 50/60 ㎐ (Dual usage)
Voltage fluctuation
±10 % of power supply voltage
Power consumption
4 VA max
Ambient temperature
0 ~ 50 ℃
Storage temperature
-25 ~ 65 ℃
Vibration resistance
10 - 50 ㎐, Peak amplitude for 2 hrs each in X, Y and Z direction
Shock resistance
300 ㎨ each in X, Y and Z direction for 3 times
Weight
350 g
▍ Range and input code chart
Classification
Code
K
K1
Thermocouple
J
R
P1
RTD
P2
G
DC voltage
V
F
DC current
C

▍ Dimensions and panel cutout

■ Dimensions

▍ Connection diagrams

Information
Input
Range(℃)
0 ~ 1,300 ℃
K Thermocouple
0.0 ~ 200.0
J Thermocouple
0 ~ 400
R Thermocouple
599 ~ 1,699
-199 ~ 600 ℃
Pt100 Ω
-199.9 ~ 199.9 ℃
0 - 5 V DC
1 - 5 V DC
0 ~ 100
0 - 10 V DC