12. SENDING ARBITRARY DATA TO AN AJ71 PB96
(INFORMATION REPROT: RECEIVER)
F.
12. SENDING ARBITRARY DATA
To AN
AJ7lCB96 (INFORMATION
REPORT:
RECEIVER)
To send self station variable values to the AJ71 PB96 spontaneously, issue
"Unsolicited Status".
The AJ71 PB96 will set the received data in the buffer memory. (See the
User's Manual for details on the buffer memory.)
[Parameters required for the requester]
0
Priority
Set the order of priority in accordance with which the Unsolicited Status
is to be sent.
Priority
scription
Low
issued with a low order of priority.
High
issued with a
#gbo&r
of priority.
0
Access Specificaion
The variables to be sent can
be
specified by Index or by Name.
Index
I
Index
of the
variable to
be
read
Variable
Name
I
Name of the
variable
to
be read
Subindex
Used to designate which element of an Array Object is sent.
If no Subindex is designated, all elements will be sent.
Data
Set
the
data to be sent.
[Respense from the receiver (AJ71PB96)I
None
i""
(1)
The AJ71PB96 cannot receive this service under the following cir-
cumstances:
0
When the connection type is MSAC or MSCY and the AJ71 PB96
When the connection type is BRCT or MULT and the AJ71 PB96
is operating as a master station.
is operating as a requester.
(2) The Priority parameter set for the requester is not set in the
AJ71 PB96 buffer memory.
(3)
If the AJ71 pB96 receives this service using
one
of the following
communication types, the AJ71PB96
will
not interpret the received
in accordance with the
OD
of
the
communicating station (remote
OD):
MMACIO, MSACIO, MSAC-SIlO,MSCY/O, MSCY-SI10
BRCT, MULT
12-