Page 1
Kotron ® Tip Sensitive RF Level Sensor Instruction Manual and Parts List Level Sensor...
Page 2
Magnetrol/STI will repair or replace the control at no cost a component’s mechanical integrity. Cautions are also to the purchaser (or owner) other than transportation.
Electrostatic Discharge (ESD) Handling Procedure Magnetrol’s electronic instruments are manufactured to the highest quality standards. These instruments use electronic components that may be damaged by static electricity present in most work environments.
Preliminary Operational Check After unpacking and before installation, perform the following operational check on the unit in a non-hazardous area. 1. Fill a suitable grounded container with water. 2. In a non-hazardous area, power the unit with proper voltage. 3. Dip the probe in the water. The relay should activate. 4.
Probe Length If the geometry of your application requires a probe shorter than 14" (356 mm), refer to the Probe Length vs. chart below. Dielectric Constant TOTAL PROBE LENGTH (Inches) A minimum probe length of 4" (102 mm) is permissible in a conductive liquid (dielectric of 24 or greater).
1.6.2 Vertical Mounting As medium rises on the probe, unit will signal at a point determined by the calibration of the unit and the dielectric constant of the medium. In conductive media, the actua- tion point will be at the tip of the probe over a wide range of zero calibrations.
NOTE: This unit is factory supplied with the jumper wire connecting LL and CM. Caution: In hazardous areas, do not power the unit until the conduit is sealed and enclosure cover is screwed down securely. 9. Installation is complete. Replace housing cover. 1.8.1 Operating Mode Selection Low Level (LL) means tank material below the...
Calibration Caution: For Hazardous Locations – Extra precautions must be taken during instrument calibration. Before housing cover is removed, power MUST be turned off. 1. Turn on power to the instrument. 2. Remove housing cover. 3. Set point locations: Conductive media — The set point is located at the tip of the probe.
5. Replace housing cover. 6. Bring material to alarm condition and check for relay con- tact change. Reference Information This section presents an overview of the operation of the Kotron Tip Sensitive RF Level Sensor, information on troubleshooting common problems, listings of agency approvals, a list of replacement parts and electrical and dimensional data.
2.3.2 Switch Chatter 1. Check for low voltage. 2. Check ground system. 3. Check for turbulence. Relocate probe or isolate from turbulence. 2.3.3 Relay Will Not Reset Check probe for buildup or fouling. Clean and recalibrate. 50-606 Kotron Tip Sensitive RF Level Sensor...
Agency Approvals AGENCY MODEL APPROVED APPROVAL CATEGORY APPROVAL CLASSES 80-8032-3X2 Explosion Proof Class I, Groups A, B, C & D Class II, Groups E, F & G Class III, NEMA 4X 80-8032-3X2 Explosion Proof Class I, Groups C & D Class II, Groups E, F &...