Switch Description; Ratings - FEDERAL PACIFIC PSI Series General Description Manual

Pad-mount switchgear 15kv, 25kv; 35kv
Table of Contents

Advertisement

Switch Description

The Auto-jet
switch provides a unique method of load inter-
®
ruption, producing a laminated jet of air which extinguishes the
arc.
Auto-jet
switches have a heavy gauge steel, all welded base
®
frame that assures proper alignment and eliminates any prob-
lem of switch-to-enclosure alignment. A quick-make, quick-
break stored energy mechanism with heavy duty, long life die
springs provides high speed opening and closing independent
of the operating handle speed. This durable mechanism as-
sures safe load make, 3-time fault closing capability, and load
interruption with the Auto-jet
15 kV and 25 kV Switches

RATINGS

kV
Interrupting
Max.
Nom.
BIL Cont.
Des.
Load Cap. Mag.
15
17
95
600
600
15
17
95
1200 1200 100
25
27
125
600
600
34.5
38
150
600
600
*The three-time duty-cycle fault-closing rating means that the
switch can be closed three times into rated fault amperes and re-
main operable and able to carry and interrupt its rated load current.
601 Old Airport Road • Bristol, VA 24201 Phone (276) 669-4084 • FAX (276) 669-1869 • www.federalpacific.com • ISO9001:2015
interrupter.
®
Amperes RMS
Fault-
Mom. &
Close
Fault-Close
(ASYM KA)
Cycle*
100
21
40
21
40
100
21
40
27
21
40
Duty
3
3
3
3
Figure 11. Connector/Termination Detail
INSTALLATION & OPERATION INSTRUCTIONS
PAD-MOUNTED SWITCHGEAR TYPE PSI
REV. 1.6 - NOVEMBER 2017
34.5 kV Switches
SECTION IB-1G-500
PAGE 5