Daikin McQuay ED 15117 Protocol Information

Bacnet networks (ms/tp, ip, ethernet); lonworks networks
Table of Contents

Advertisement

Quick Links

Magnitude
Protocol Information
®
BACnet
Networks (MS/TP, IP, Ethernet)
®
L
W
Networks
ON
ORKS
Daikin McQuay Magnitude
Compressor Model WME
© 2010 McQuay International
Engineering Data
TM
Chiller Unit Controller
Magnetic Bearing Centrifugal Chiller, Single-
ED 15117
Group: Controls
Part Number: ED 15117
Date: April 2010
Supersedes: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ED 15117 and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin McQuay ED 15117

  • Page 1: Bacnet ® Networks (Ms/Tp, Ip, Ethernet) Lon Works ® Networks

    Engineering Data ED 15117 Group: Controls Part Number: ED 15117 Date: April 2010 Supersedes: New Magnitude Chiller Unit Controller Protocol Information ® BACnet Networks (MS/TP, IP, Ethernet) ® Networks ORKS ™ Daikin McQuay Magnitude Magnetic Bearing Centrifugal Chiller, Single- Compressor Model WME...
  • Page 2: Table Of Contents

    IMIT ETPOINT ETWORK URRENT ........50 .........31 EFAULT ALUES HILLER NABLE ......31 VAPORATOR NTERING ATER HILLER NABLE UTPUT ......32 ..........50 HILLER NABLE ETPOINT EMPERATURE .......32 ..50 HILLER APACITY IMITED VAPORATOR WITCH TATUS ......34 HILLER OCAL ETWORK ED 15117...
  • Page 3 Alarms-BACnet........63 VAPORATOR EAVING ATER ..........51 .......... 63 EMPERATURE LARM LASSES ....52 ....... 63 VAPORATOR OURS LARM ANDLING Clearing Alarms-BACnet ......65 ......52 VAPORATOR TATUS ....53 ....... 65 VAPORATOR ATER LARM ESSAGES Alarms-L ........67 ......53 ORKS IRECTORY DDRESS ......... 67 ECOVERY NTERING ATER URRENT LARM...
  • Page 4: Revision History

    American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Echelon, , and LonTalk from Echelon Corporation, Windows from Microsoft ORKS Corporation, and McQuay, Daikin McQuay, and Magnitude from McQuay International. Limited Warranty Consult your local McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your local McQuay Representative, go to www.mcquay.com.
  • Page 5: Introduction

    Introduction This document contains the necessary information you need to incorporate a Daikin McQuay ® Magnitude™ Chiller Unit Controller into a building automation system (BAS). It lists all BACnet ® properties, L variables, and corresponding Magnitude Chiller Unit Controller data points. It ORKS also contains the BACnet Protocol Implementation Conformance Statement (PICS).
  • Page 6: Basic Protocol Information

    Some object types occur more than once in the Magnitude Chiller Unit Controller; each occurrence or instance has different properties and controls different unit variables or data points. Each instance is designated with a unique instance index. Some properties can be adjusted ED 15117...
  • Page 7 (read/write properties, e.g., setpoints) from the network and others can only be interrogated (read-only properties, e.g., status information). Each data point accessible from a BACnet network is described with a table that gives the Object Identifier, Property Identifier, Full BACnet Reference or path, and the Name enumeration of the property.
  • Page 8: Magnitude Chiller Unit Controller Device Object

    BACnet communication module’s initialization phase. The BACnet communication module continues to poll the device object name parameter during run-time. If the device object name is changed at the controller during runtime, the update will be automatically applied to the BACnet ED 15117...
  • Page 9 communication module as soon as the change is received. The allowable range of characters for the device object name will be 1 to 31 characters. If an empty string is read from the controller, the following default name will be used: Default device object name: MTE Chiller UCA - address* *Address = the MAC Address For example:...
  • Page 10 While the Magnitude Chiller Unit Controller supports all shown object types, not all object types are used. See the Object List for details. The device properties will be read-only. The controller values are writable from BACnet via the BACnet TimeSynchronization services. ED 15117...
  • Page 11: Network Considerations

    Network Considerations Access to Properties Object properties are accessible from the network by specifying the device object identifier, object identifier, and the property identifier. To access a property, you must specify the object identifier including the device object identifier or the object name including the device object name and the property identifier.
  • Page 12 BBMD address. If the new value is non-zero, a Register-Foreign-Device message is sent to the BBMD address. Changing the BBMD address may affect the operation of other BACnet devices on the network. This parameter can only be accessed and configured via the unit controller OITS panel. ED 15117...
  • Page 13: Bac Net D Evice M Anagement

    Foreign Device Time-To-Live The Foreign Device Time-To-Live (FDTTL) value is read from the Magnitude Chiller Unit Controller during the BACnet communication module’s initialization phase. The BACnet communication module continues to poll the FDTTL parameter during run-time. If the FDTTL is changed at the unit controller during run-time, the update is automatically applied to the BACnet communication module as soon as the change is received.
  • Page 14 (cold start or warm start). The functionality of a cold and warm start are the same simply reboot BACnet Communication module. The chiller controller can never be reset via the BACnet network. Reinitialize Device is implemented with a non-changeable password of 1234. ED 15117...
  • Page 15: Bac Net Device Management Configuring The Unit Controller

    Configuring the Unit Controller The Magnitude Chiller Unit Controller can operate with the default values of the various parameters. However, certain communication parameters must be configured appropriately (see the appropriate Magnitude Communication Module Installation Manual for details). Default values may be changed using the unit controller OITS panel or via the BACnet network (see the Magnitude Chiller Unit Controller Operation &...
  • Page 16 ORKS Transceiver User’s Guide. Free topology networks may take on the following topologies:  Bus  Ring  Star  Mixed - Any combination of Bus, Ring, and Star Limitations to wire lengths apply and must be observed. ED 15117...
  • Page 17 Figure 1. Singly Terminated Free Topology Ring Topology Star Topology Singly Terminated Bus Topology Stub Termination Termination Termination Mixed Topology Termination A network segment is any part of the free topology network in which each conductor is electrically continuous. Each of the four diagrams in is a illustration of a network segment. Some applications may require two or more segments.
  • Page 18 L network. A network configuration tool maps device Neuron IDs to the ORKS domain/subnet/node logical addressing scheme when it creates the network image, the logical network addresses and connection information for all devices (nodes) on the network. ED 15117...
  • Page 19 External Interface File (XIF) guidelines specify exact documentation rules so that proprietary configuration tools are not required to commission and configure L devices. The L Chiller Communication ORKS ORKS Module is self-documenting so that any network management tool can obtain all the information needed over the network to connect it into the system and to configure and manage it.
  • Page 20: Typical Application: Minimum Integration

    See Protocol Point Summary section (Tables 4-7) for a complete list of all L ORKS variables or BACnet points available to the network. For a detailed description of all available data points, see the Detailed Data Point Information section. ED 15117...
  • Page 21: Alarms

    Alarms Alarms in a Magnitude Chiller Unit Controller are divided into three classes: Faults, Problems, and Warnings.  Fault Alarms have the highest priority.  Problem Alarms have medium priority.  Warning Alarms have the lowest priority. Notification BACnet Magnitude Chiller Unit Controllers may have their alarms monitored by one of two methods: 1) a BACnet Binary Output indicating whether any alarms exist, or 2) Alarm value using three BACnet Analog Value objects.
  • Page 22: Protocol Point Summary - Bacnet

    50 -15.16 to 104°F (-26.2 to 40°C) Temperature Condenser Water Flow Rate 147 0 to 10,001.55 GPM (0 to 631 L/s) Condenser Pump #1 Status 11 0=Pump Off Request, 1=Pump On Request Condenser Pump #2 Status 12 0=Pump Off Request, 1=Pump On Request ED 15117...
  • Page 23 Network Control Property Description *Cool Setpoint - Network 35 – 80°F (1.7°C to 26.7°C); Default=44°F -40 to 257°F (-40 to 125°C) *Evaporator Entering Water Temperature Evaporator Flow Switch Status 0=No Flow, 1=Flow *Evaporator Leaving Water Temperature -40 to 257°F (-40 to 125°C) Evaporator Pump #1 Run Hours 112 0 –999,999 Evaporator Pump #2 Run Hours...
  • Page 24 10=ChillerSoftwareProbWarn Clear Alarm Network 0= Normal (Default), 1=Clear Alarm *Boldface denotes data points for typical minimum integration. This column refers to whether or not the Present Value property of the object is Read Only (R) or read/write (W). ED 15117...
  • Page 25: Protocol Point Summary - L

    Protocol Point Summary - L ORKS The following section defines the comprehensive list of L variables available from the unit ORKS controller to the network. The properties are displayed as Network Output Variables, Network Input Variables, and Network Configuration Parameters (see Tables 5-7 below). The shaded data points with numbers are the data points listed in Table 3.
  • Page 26: N Etwork I Nput V Ariables

    0 to 100%; Default=100% Setpoint *Chiller Enable nviChillerEnable 32 SNVT_switch 0=Disable, 1=Enable Setpoint Chiller Mode Setpoint nviMode 36 SNVT_hvac_mode 108 1=HVAC_HEAT, 3=HVAC_COOL, 11=HVAC_ICE; Default=Cool Compressor Select nviCompSelect 43 SNVT_count 1=Comp 1/Circuit 1, 2=Comp 2/Circuit 2, 3=Comp 3, 4=Comp4 ED 15117...
  • Page 27: Network Configuration

    Network Control Variable Name SNVT Reference Description Property 49 SNVT_temp_p *Cool Setpoint nviCoolSetpt 105 35 – 80°F (1.7°C to 26.7°C); Default=6.6°C Heat Setpoint nviHeatSetpt 54 SNVT_temp_p 105 100 to 150°F (37.8 to 65.6°C); Default=57.2°C Ice Setpoint nviIceSpt 55 SNVT_temp_p 14.9 to 35.06°F (-9.5 to 1.7°C); Default=- 3.9°C *Clear Alarm nviClearAlarm...
  • Page 28: Detailed Data Point Information

    Usable Range Default Value Percent of chiller BACnet: Real 0–100% capacity : Fixed-Point Scalar ORKS signed long BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Value Present Value Object Name ChillerCapacity ED 15117...
  • Page 29: Alarm Digital Output

    ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoActCapacity Chiller lev_percent two bytes Alarm Digital Output This read only network variable indicates whether an alarm condition has occurred. This variable must be polled for alarm notification. Measurement Units Data Type Usable Range Default Value...
  • Page 30: Active Capacity Limit Output

    Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Value Present Value Object Name NetworkCapacityLimitPct LonWorks Name Profile SNVT Type SNVT SNVT Size SCPT_Reference SCPT ORKS Index Index nviCapacityLim (input) Chiller lev_percent 81 two bytes ED 15117...
  • Page 31: Chiller Enable

    Chiller Enable This mandatory L configuration variable sets the default power-up and restart mode of the ORKS chiller, unless the configuration parameter nciDefaults = 1 (See Default Values). If nciDefaults = 1, the default values are the values specified during manufacturing. Refer to the appropriate Operating Manual for suitable variable values.
  • Page 32: Chiller Enable Setpoint

    0 = Not Limited (Inactive) 1 = Limited (Active) ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoChillerStat.Limited Chiller chlr_status 3 bytes Property Values (Limited) 0 = Not Limited (Inactive) 1 = Limited (Active) Structure typedef struct { chiller_t chlr_run_mode; ED 15117...
  • Page 33 hvac_t chlr_op_mode; struct{ unsigned in_alarm :1; // offset 0 unsigned run_enabled :1; // offset 1 unsigned local :1; // offset 2 unsigned limited :1; // offset 3 unsigned chw_flow :1; // offset 4 unsigned condw_flow :1; // offset 5 /* The last two bits (offset 6) are not defined */ } chlr_state;...
  • Page 34: Chiller Local/Network

    } SNVT_chlr_status; Chiller Location This optional configuration network parameter provides a description of the location. Measurement Units Data Type Usable Range Default Value Structure Any NUL terminated ASCII string ASCII string of zeros + up to 31 bytes. ED 15117...
  • Page 35: Chiller Mode

    BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Device Variable Location Object Name Location ORKS Name Profile SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index ORKS nciLocation Chiller str_asc 31 bytes SCPT_location Chiller Mode Chiller Mode Setpoint –...
  • Page 36: Chiller Mode Setpoint - N

    This network variable indicates the current state of the chiller. The OFF state is represented by state = FALSE and value = 0. The other discrete states are represented by state = TRUE and value > 0. Measurement Units Data Type Valid Range Default Value Chiller State BACnet: Enumerated See Below : structure ORKS ED 15117...
  • Page 37: Chiller Status

    BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Binary Input Present Value Object Name UnitOFF Property Values 0 = Off 1 = Run Allowed ORKS The L equivalent of this data point is part of the Chiller Status network variable output. ORKS Name Profile...
  • Page 38: Clear Alarm Network

     High Motor Gap Temperature  Mechanical High Pressure Measurement Units Data Type Usable Range Default Value Integer Enumerated 0=Normal BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Binary Value Present Value Object Name ClearAlarm ED 15117...
  • Page 39 Property Values 0 = Normal 1 = Clear Alarm ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nviClearAlarm McQuayChiller SNVT_switch two bytes Valid Range State Value Clear Alarm unused No Alarm unused Clear Alarm ED15117...
  • Page 40: Compressor Average Current

    There is a separate output for each compressor. L uses the Compressor Select ORKS variable. Measurement Units Data Type Usable Range Default Value Pressure (gauge) psi / kPa BACnet: Real 0-410.0217 PSI : Fixed-Point Scalar ORKS signed long ED 15117...
  • Page 41: Compressor Discharge Refrigerant Temperature

    BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Input Present Value Object Name C1Comp1DischRefPressure ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoCmpDisRefPres McQuayChiller SNVT_press two bytes *Note: The units for SNVT_press#US is inches of water column. To display units in psi the format must be changed to SNVT_press#US_psi. Compressor Discharge Refrigerant Temperature This read only network variable indicates the current refrigerant temperature discharged from the compressor.
  • Page 42: Compressor Percent Rla

    BACnet uses a separate variable for each compressor. L uses the Compressor ORKS Select variable. Measurement Units Data Type Usable Range Default Value Event Count Hours BACnet: Real 0 –999,999 : Float Type unsigned ORKS long ED 15117...
  • Page 43: Compressor Select

    BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Value Present Value Object Name C1Comp1Hours ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoCompHrs McQuayChiller SNVT_count_f two bytes Compressor Select This L -only network variable selects the compressor/circuit (number 1, 2) that is ORKS interrogated.
  • Page 44: Compressor Suction Saturated Refrigerant Temperature

    C1Comp1SuctionPressure ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoSuctRefPress McQuayChiller SNVT_press two bytes *Note: The units for SNVT_press#US is inches of water column. To display units in psi the format must be changed to SNVT_press#US_psi. ED 15117...
  • Page 45: Compressor Suction R Temperature

    Compressor Suction Refrigerant Temperature This read only network variable indicates the current refrigerant temperature entering the compressor. There is a separate output for each compressor. L uses the Compressor Select variable. ORKS Measurement Units Data Type Usable Default Value Range Temperature °F/°C BACnet: Real...
  • Page 46: Condenser Leaving Water Temperature

    Data Type Usable Range Default Value Event Count BACnet: Real 0 –999,999 : Fixed-Point Scalar ORKS signed long BACnet Pump #1 Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Value Present Value ED 15117...
  • Page 47: Condenser Pump Run Hours

    Object Name CondPump1RunHours Pump #2 Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Value Present Value Object Name CondPump2RunHours ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoCondPumpHrs McQuayChiller SNVT_count_f two bytes Condenser Refrigerant Pressure This read only network variable indicates the current condenser refrigerant pressure.
  • Page 48: Condenser Pump Status

    0 = Pump Off Request 1 = Pump On Request ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoCndWPump McQuayChiller SNVT_switch two bytes Valid Range State Value Pump Status unused Pump Commanded Off unused Pump Commanded On ED 15117...
  • Page 49: Cool Setpoint - Network

    Cool Setpoint - Network This read/write network variable is used to change the Cooling setpoint from the network. It sets the temperature of the Leaving Chilled Water when the chiller is operating in the Cooling Mode. It cannot be set below the local Cool Setpoint. Measurement Units Data Type...
  • Page 50: Default Values

    Present Value Object Name EntEvapWaterTemp ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoEntChWTemp Chiller temp_p two bytes Evaporator Flow Switch Status This read only network indicates the status of the water flowing through the evaporator. ED 15117...
  • Page 51: Evaporator Leaving W Temperature

    Measurement Units Data Type Usable Range Default Value Flow State BACnet: Enumerated See Below : Structure ORKS BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Binary Input Present Value Object Name EvapWaterFlowStatus Property Values 0 = No Flow (Inactive) 1 = Flow (Active) ORKS...
  • Page 52: Evaporator Pump Status

    1 = Pump On Request Pump #2 Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Binary Input Present Value Object Name EvapPump2State Property Values 0 = Pump Off Request 1 = Pump On Request ED 15117...
  • Page 53: File Directory Address

    ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoChWPump SNVT_switch two bytes McQuayChill Valid Range State Value Pump Status unused Pump Off Request unused Pump On Request Evaporator Water Flow Rate This read only network variable indicates the rate of water flow through the evaporator. Measurement Units Data Type...
  • Page 54: Heat Recovery Leaving Water Temperature

    Temperature °F/°C BACnet: Real 100.04 to 150.08°F 134.96°F/57.2°C : Fixed Point Scalar 37.8-65.6°C ORKS signed long BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Analog Value Present Value Object Name NetworkHeatTempSetpoint ORKS ED 15117...
  • Page 55: Heat Setpoint

    Name Profile SNVT Type SNVT Index SNVT Size SCPT_Reference SCPT Index ORKS nviHeatSetpt Chiller SNVT_temp_p 105 two bytes Heat Setpoint Unless the configuration parameter nciDefaults =1, the Heat Setpoint Network variable (nviHeatSetpt) is set to this configuration value (nciHeatSetpt) upon unit controller power-up or loss of communication.
  • Page 56: Maximum Send Time

    The variables that use Minimum Send Time are:  nvoActCapacity  nvoCapacityLim  nvoCmpDisRefPres  nvoCmpDisSRefTmp  nvoCompDisTemp  nvoCompPercRLA  nvoCondFlowRate  nvoCondRefPres  nvoCondSatRefTmp  nvoCurrent  nvoEntChWTemp  nvoEntCndWTemp  nvoEntHRWTemp  nvoEvapFlowRate  nvoKiloWatts ED 15117...
  • Page 57: Object Status

     nvoLvgChWTemp  nvoLvgCndWTemp  nvoLvgHRWTemp  nvoOutdoorTemp  nvoSatSuctRefTmp  nvoSuctionTemp  nvoSuctRefPress  nvoVoltage Measurement Units Data Type Usable Range Default Value Elapsed Time seconds BACnet: Unsigned Integer 0–6553.4 sec 0 (no automatic update) : Fixed Point Scalar ORKS - unsigned long ORKS...
  • Page 58: Object Request

    A zero bit in the status mask means that the bit is never set by the device. Measurement Units Data Type Valid Range Uses Heartbeat Default Value Object Request Structure ED 15117...
  • Page 59: Outdoor Air Temperature

    BACnet No BACnet equivalent ORKS LonWorks Name Profile Uses Heartbeat SNVT Type SNVT Number nviRequest Node Object SNVT_obj_status Enumeration Definitions (object_request_t) Value Identifier Notes RQ_NORMAL Enable object and remove override RQ_DISABLED Disable object (not supported) RQ_UPDATE_STATUS Report object status RQ_SELF_TEST Perform object self-test (not supported) RQ_UPDATE_ALARM Update alarm status (not supported)
  • Page 60: Receive Heartbeat

    Measurement Units Data Type Usable Range Default Value Chiller Status BACnet: See Below Enumerated ORKS Structure BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Binary Input Present Value Object Name UnitOFF ED 15117...
  • Page 61: Software Identification Version )

    Property Values 0 = Off (Inactive) 1 = Run Allowed (Active) ORKS The L equivalent of this data point is part of the Chiller Status network variable. ORKS Name Profile SNVT Type SNVT Index SNVT Size ORKS nvoChillerStat Chiller chlr_status 3 bytes Property Values (run_enabled)
  • Page 62 Object Name Units Property Values 1 = English (Inactive) 2 = Metric (Active) ED 15117...
  • Page 63: Alarms-Bacnet

    Alarms-BACnet Alarm Classes BACnet alarms in a Magnitude Chiller Unit Controller are divided into three classes: Faults, Problems, and Warnings. Fault alarms have the highest severity level. Problem alarms have medium severity level. Warning alarms have the lowest severity level. Fault Alarms Fault alarms require an acknowledgment from the operator.
  • Page 64 Data Type Usable Range Default Value Integer Enumerated BACnet Object Identifier Property Identifier Object Type Type Enumeration Instance Property Name Property Enumeration Binary Output Present Value Object Name AlarmDigitalOutput Property Values 0 = No Alarm 1 = Alarm ED 15117...
  • Page 65: Clearing Alarms-Bacnet

    Clearing Alarms-BACnet This read/write network variable clears all active alarms. The following alarms cannot be cleared over the network. They can only be cleared at the chiller (i.e. via the unit controller OITS panel).  Low Evaporator Pressure  High Condenser Pressure (by pressure sensor) ...
  • Page 66 Alarm Alarm Message Text Alarm Message Text Number Number Cmp1VFDOverspeed(Hardware) Cmp1DishPressSenFlt Cmp1VFDOverspeed(Software) Cmp1CondRfrCkt1PressSenFlt Cmp1VFDOverspdMonitorFault Cmp1CondRfrCkt2PressSenFlt Cmp1VFDInputVoltageHigh Cmp1SuctTempSenFlt Cmp1VFDPrechargeFault Cmp1DischTempSenFlt Cmp1VFDLowDCBusVolt Cmp1MotorGapTempSenFlt Cmp1VFDHiDCBusVltRunning Cmp1RotorPmpTempSenFlt Cmp1VFDHiDCBusVltRegen Cmp1BearingOrbitSurgeFlt Cmp1VFDHiSteeringBrVltPrechrg Cmp1CommunicationsFlt Cmp1VFDHiSteeringBrVltRunning Cmp1EvapLvgWtrTempSenFlt Cmp1VFDMotorOverload Cmp1CondLvgWtrTempSenFlt Cmp1VFDHiCurrentBridge1 Cmp1SoftwareFlt Cmp1VFDHiCurrentBridge2 Cmp1EvapWtrFlwLoss Cmp1VFDHiCurrentChopper1 Cmp1CondWtrFlwLoss Cmp1VFDHiCurrentChopper2 ED 15117...
  • Page 67: Alarms-Lon Works

    Alarms-L ORKS Two L network variables indicate alarm conditions and one network variable clears alarms. ORKS The Chiller Status network output variable indicates that the unit controller is in alarm, but it does not identify the alarm condition. The Current Alarm network output variable indicates the alarm condition. Current Alarm This network output variable indicates the current alarm.
  • Page 68: Clearing Alarms - Lon Works

    Cmp1Tmr Exp No Strt Cmp1VFDHiTempSide1 Cmp1LowMotorCurrent Cmp1VFDHiTempSide2 Cmp1HiDischTemp Cmp1VFD IGBT FltBridge1 Cmp1MechHiPress Cmp1VFD IGBT FltBridge2 Cmp1HiMotorTemp Cmp1VFD IGBT FltChopper1 Cmp1HiMotorGapTemp Cmp1VFD IGBT FltChopper2 Cmp1LoRotorPumpSuperHt Cmp1VFDTherm1Flt Cmp1SurgeTemp Cmp1VFDTherm2Flt Cmp1SurgeSwitch Cmp1VFDTherm3Flt Cmp1MotorStartFailure Cmp1VFDTherm4Flt Cmp1NoCmpStop Cmp1VFDHiPwrSupTemp Cmp1VFDFault Cmp1VFDHiPwrSupVolt Cmp1VFDRefFault Cmp1VFDClgFanFlt Cmp1VFDLossofMotorSync Cmp1VFDProcessorFlt Cmp1VFDMotorStall Cmp1VFDMaintenanceMode ED 15117...
  • Page 69 Alarm Alarm Alarm Message Text Alarm Message Text Number Number Cmp1VFDSpdCommandFault Cmp1SuctPressSenFlt Cmp1VFDOverspeed(Hardware) Cmp1DishPressSenFlt Cmp1VFDOverspeed(Software) Cmp1CondRfrCkt1PressSenFlt Cmp1VFDOverspdMonitorFault Cmp1CondRfrCkt2PressSenFlt Cmp1VFDInputVoltageHigh Cmp1SuctTempSenFlt Cmp1VFDPrechargeFault Cmp1DischTempSenFlt Cmp1VFDLowDCBusVolt Cmp1MotorGapTempSenFlt Cmp1VFDHiDCBusVltRunning Cmp1RotorPmpTempSenFlt Cmp1VFDHiDCBusVltRegen Cmp1BearingOrbitSurgeFlt Cmp1VFDHiSteeringBrVltPrechrg Cmp1CommunicationsFlt Cmp1VFDHiSteeringBrVltRunning Cmp1EvapLvgWtrTempSenFlt Cmp1VFDMotorOverload Cmp1CondLvgWtrTempSenFlt Cmp1VFDHiCurrentBridge1 Cmp1SoftwareFlt Cmp1VFDHiCurrentBridge2 Cmp1EvapWtrFlwLoss Cmp1VFDHiCurrentChopper1 Cmp1CondWtrFlwLoss Cmp1VFDHiCurrentChopper2 ED15117...
  • Page 70: Appendix A: Protocol Implementation Conformance Statement (Pics)

    Device Management – Dynamic Device Binding – B DM-DDB-B Device Management – Dynamic Object Binding – B DM-DOB-B Device Management – DeviceCommunicationControl – DM-DCC-B Device Management – TimeSynchronization – B DM-TS-B Device Management – UTCTimeSynchronization – B DM-UTC-B ED 15117...
  • Page 71 BIBB Name Designation Device Management – ReinitializeDevice – B DM-RD-B This BIB is not required for B-ASC but is highly desirable for optimum performance on the network. DM-TS-B is not required for B-ASC. DB-RD-B will be implemented such that the BACnet card is reset without resetting the chiller controller. The chiller controller can never be reset via the BACnet network.
  • Page 72: Upported

    Description Present_Value Reliability Relinquish_Default Inactive_Text Active_Text Priority_Array Relinquish_Default Device Description Object_Identifier Location Object_Name Local_Time Description Local_Date Location UTC_Offset UTC_Offset Daylight_Savings_Stat Max_Master Max_Info_Frames Max_Master APDU_Timeout Max_Info_Frames Number_of_APDU_Re tries Multi-state Input Description Reliability State_Text Multi-state Output Description Relinquish_Default Reliability State_Text ED 15117...
  • Page 73 Object-Type Optional Properties Writable Properties not Supported Required to be Writable Multi-state Value Description Present_Value Reliability Relinquish_Default State_Text Priority_Array Relinquish_Default Though the BACnet communication module supports the following object types, not all objects types are currently used. This property will be writable only if defined writable in the CSV file which is downloaded into the unit controller.
  • Page 74: Data Link Layer Options

      ANSI X3.4 ISO 8859-1 /Microsoft DBCS ISO 10646 ISO 10646 (UCS-4) JIS C 6226 (UCS-2) Note: Support for multiple character sets does not imply they can be supported simultaneously. Non-BACnet Equipment/Network(s) Support Communication Gateway Non-BACnet equipment/networks(s): ED 15117...
  • Page 75: Index Of Detailed Point Information

    Index of Detailed Point Information Compressor Power......22, 25, 42 Compressor Run Hours ....22, 25, 42, 43 Active Capacity Limit Output ..22, 25, 30 Compressor Select ........26, 43 Active Setpoint ........22, 25, 28 Compressor Starts....... 22, 25, 43 Actual Capacity.........22, 25, 28 Compressor Suction Refrigerant Pressure..
  • Page 76 Maximum Send Time .......27, 56 Subnet............. 18 Minimum Send Time........27, 56 MSTP..............5 Time..............10 Network Clear Alarm......27, 68 network variable ..........15 Units ............... 23 Neuron ............18 Node ID ............18 Notice ...............4 Warning Alarms ..........63 Notification.............21 XIF..............19 ED 15117...
  • Page 77 This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com. www.mcquay.com (800) 432-1342 ED15117...

Table of Contents