AIR PRODUCTS
AND
CONTROLS
PRODUCT DESCRIPTION
The Multi-Flex family of smoke detector sounder bases and syn-
chronization modules provide today's most advanced functionality
and performance, delivering flexible notification capabilities for
any installation.
The bases offer selectable steady or temporal pattern output and
selectable high or low volume levels. The three-pulse temporal
pattern is required by NFPA 72 for fire alarm evacuation for com-
mercial and residential applications.
Available (SM) synchronization modules allow temporal pattern
sounder base circuits to be completely synchronized and installed
in almost limitless configurations, and also provide an on-board
latching test function.
The sounder base requires an external 24VDC power supply. In the
absence of a synchronization module, a means for polarity reversal
is required for test and general alarm functionality. The connec-
tions for the external power supply and the communication loop
are opto-isolated to prevent electrical interaction between them.
+
L2
L1
The 6-inch diameter sounder base mounts to 4-inch octagonal
JP1
JP2
-
and 4-inch square boxes. When mounting detectors on a ceiling,
NEG POS
VOL.
TEMP
HIGH
3 OR
24VDC
install at least 4 inches from a wall. When mounting detctors on
/LOW
CONT
a wall, install 4 to 12 inches from ceiling.
COMPATIBILITY
-R
The Multi-Flex series is compatible with Apollo analog addressable
(XP95A and Discovery Series) and conventional (Series 60A and
Series 65) smoke detectors, including heat, photoelectric and ion-
ization types. Please refer to the individual detector documentation
xxx
for more information.
The smoke detectors and bases are designed to operate in con-
junction with UL Listed Fire Alarm Control Panels (FACP). Refer
to the FACP manual for guidance on maximum allowable devices
per loop. Contact Air Products and Controls or refer to your
FACP manual for approved compatibility.
TEST /FORCED FUNCTION
The MB-SDRT-CV is fully compatible with the previous genera-
POS
NEG
tion MB-SDR-S60 sounder base. Likewise, the MB-SDRT-AA is
also backwards compatible with the MB-SDR-XP95 sounder
External 24VDC
base and MB-RLY-XP95 relay base models. The bases are also
Connections
compatible with the new MB-RLYT-CV and MB-RLYT-AA relay
bases, respectively.
BEFORE INSTALLING
Ensure familiarity with requirements for detector spacing, place-
ment, zoning, wiring and special applications. NFPA 72 and NEMA
© Air Products and Controls Inc. 2009
You in Control
+R
ADDRESS
LABEL
SPACE
POS
AIR PRODUCTS AND CONTROLS INC.
INSTALLATION GUIDE FOR MULTI-FLEX
SOUNDER BASES AND SYNCHRONIZATION MODULES
MB-SDRT-AA Analog Addressable Detector Sounder Base
MB-SDRT-CV Conventional Detector Sounder Base
MB-SDRT-SM Synchronization Module
guidelines should be observed. The detector used with this base
must be tested and maintained regularly in accordance with NFPA
72 requirements. Canadian Installations must comply with the
Canadian Standard for installation for Fire Alarm System CAN/
ULC-S524 and the Canadian Electrical Code C22.1, Part 1.
NOTE: A COPY OF THIS GUIDE SHOULD BE LEFT WITH
THE OWNER/USER OF THIS EQUIPMENT.
INSTALLATION (CONVENTIONAL)
Connect zone circuit (IDC) to wiring terminals L1 and L2 on detec-
tor mounting base. (see Fig. 1). Provide regulated or unregulated
24VDC external power supply to sounder base terminals as shown
in Fig.1. Power supply must be UL Listed for Fire Protective Signal-
ing Systems. Please also refer to Fig. 6 and Fig. 7. for zone wiring.
EXTERNAL
24VDC SUPPLY
(UL LISTED)
Fig. 1 MB-SDRT-CV Conventional Sounder Base
INSTALLATION (ANALOG ADDRESSABLE)
Connect analog addressable loop (SLC) to wiring terminals L1 and
L2 on detector mounting base. (see Fig. 3). Provide regulated or un-
regulated 24VDC external power supply to sounder base terminals
as shown in Fig. 3. Power supply must be UL Listed for Fire Protec-
tive Signaling Systems. Please also refer to Fig. 8. for loop wiring.
Address label spaces
Fig. 2 XPERT Card
Page 1
®
FAMILY
ALIGNMENT MARK
+
L2
JP1
-
NEG POS
VOL.
HIGH
24VDC
/LOW
-R
XPERT CARD
2
1
INST APD0281 D090201
FIG. 7: TYPICAL CLASS A, STYLE D CIRCUIT
X-pert Card
TO PANEL DCC/EARTH/GROUND
FIG.
L1
OUT
JP2
TEMP
3 OR
SUPER
CONT
BY FIRE
CONTR
L1
IN
8
3 2
4
1 6
6 4
UL
C
F
CO
U
PO
Need help?
Do you have a question about the Multi-Flex Series and is the answer not in the manual?
Questions and answers