Define Instruments ZEN–LOG-HV-RS Manual page 34

Data logging control station
Table of Contents

Advertisement

34
Binary Channel Selection
The Binary Channel selection is PLC RTX, and
uses the four digital inputs (A–D), as shown
below:
DI Com = CS Com
DI A =
Bin 1
DI B =
Bin 2
DI C =
Bin 4
DI D =
Bin 8
A binary value of '0' indicates no voltage on
the terminal, while a value of '1' indicates
5–30V DC on the terminal.
Notes & Recommendations
Analog Output A is used to retransmit the input process values 1–16, and Analog Output
B is used to retransmit the controller setpoints 1–16.
The input and output always share the same range. E.g. If Input 1 is ranged 32–212°F
(0–100°C) and retransmission Channel 1 is selected on DI A–D, then AO A and AO B are
both transmitted as 4–20mA = 32–212°F (0–100°C). Similarly, if Input 2 is ranged for
32–482°F (0–250°C), then AO A and AO B are transmitted as 32–482°F (0–250°C).
If AO A process value or AO B setpoint are transmitted to an indicator, then all the inputs
must be ranged the same, (unless the indicator is ranged to 0–100%).
In the PLC RTX modes, AO B always retransmits the controller setpoint regardless of
whether the controller is enabled or not.
The PLC RTX modes can operate simultaneously with the Scada Comms, allowing a PLC
to read back data that the Scada will be showing.
If multiple Zen units are wired to the same PLC, then it is recommended that the analog
inputs to the PLC be isolated.
ZEN-LOG-MAN-16V03 (0930)
DI A
DI B
DI C
BIN 1
BIN 2
BIN 4
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
Copyright © 2016 Define Instruments
DI D
Retrans.
BIN 8
Channel
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
1
9
10
1
1
11
12
1
1
13
1
14
1
15
1
16