Startup Guide
750-426
03/2018

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProtoNode and is the answer not in the manual?

Questions and answers

Summary of Contents for CleaverBrooks ProtoNode

  • Page 1 Cloud Enabled ProtoNode Gateway Startup Guide 750-426 03/2018...
  • Page 2 TO: Owners, Operators and/or Maintenance Personnel This operating manual presents information that will help to properly operate and care for the equipment. Study its con- tents carefully. The unit will provide good service and continued operation if proper operating and maintenance instruc- tions are followed.
  • Page 3 ProtoNode Gateway Cloud Enabled (BACnet, N2, Modbus, Ethernet/IP) (LonWorks) for interfacing Cleaver-Brooks products: Falcon Hydronic, Falcon Steam, CB780, CB120, HSC, LCS, PCS, HAWK 1000, HAWK 2000, HAWK 4000, HAWK 4500, HAWK 5000, HAWK Master, HAWK ADAC, HAWK ICS, Shark100, Shark200,...
  • Page 4 ProtoNode Gateway Technical Support: Thank you for purchasing the ProtoNode for Cleaver-Brooks products. For the latest edition of this Startup Guide, go to: http://www.cleaverbrooks.com/protonode For ProtoNode Gateway technical support, please contact your Cleaver-Brooks authorized service representative. C-B representative contact information is available at www.cleaverbrooks.com/Find- a-Rep/Index.aspx...
  • Page 5 ProtoNode (Section 1.2). 2. Record the ProtoNode part number in case needed for technical support (Section 2.1). 3. Set the device's COM settings and Node-ID for each of the devices that are to connect to the ProtoNode RER or LER (Section 2.3).
  • Page 6 Certifications BACNET TESTING LABORATORY The BTL Mark on ProtoNode RER is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing.
  • Page 7: Table Of Contents

    Web Configurator ........... 21 4.1 Connect the PC to ProtoNode via the Ethernet Port ......21 4.2 Connecting to ProtoNode’s Web Configurator .
  • Page 8 D.1. Boiler Network Wiring Connections to ProtoNode........128...
  • Page 9 Connection from ProtoNode to RS-485 Field Network ........
  • Page 10: Introduction

    Ethernet devices to the gateway, profiles must be selected in the ProtoNode's Web Configurator. The Web Configurator shows all the stored profiles/devices on the ProtoNode. It will also show all the RS- 485 devices that were previously discovered. After selecting the device, the Modbus Node-ID and, only for Ethernet Devices, the IP Address must also be entered.
  • Page 11: Methods Of Configuration - Cleaver-Brooks' Devices

    • Web Configurator for Ethernet devices and RS-485 devices that cannot be identified by Auto-Discovery A list of C-B products for use with the ProtoNode, together with their respective means of configura- tion, is shown in the table below. Devices...
  • Page 12: Setup

    2. PROTONODE SETUP 2.1 Record Identification Data Each ProtoNode has a unique part number located on the underside of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows: Model...
  • Page 13: Configuring Device Communications

    The OFF position is when the DIP switches are set closest to the outside of the box. • ProtoNode LER units do not use the “S” bank DIP switches to select a Field Protocol. On ProtoNode LER units, these DIP switches are disabled; the Field Protocol is always LonWorks.
  • Page 14: Enabling Auto-Discovery

    See the table in Figure 6 for the DIP switch setting to enable Auto-Discovery. If the ProtoNode is being installed for the first time, set S3 to the ON position to enable Auto-Discovery. The ON position is when the DIP switches are set closest to the inside of the box.
  • Page 15: Bms Network Settings: Mac Address, Device Instance And Baud Rate

    Slave Addresses and can not be discovered by BMS Front Ends that support auto discovery of BAC- net MS/TP devices. Set “A” bank DIP switches A0 - A7 to assign a MAC Address to the ProtoNode for BACnet MS/TP. Please refer to Appendix C for the complete range of MAC Addresses and DIP switch settings.
  • Page 16: Bacnet Ms/Tp (Rer): Setting The Baud Rate For Bms Network

    ProtoNode Gateway 2.5.3 BACnet MS/TP: Setting the Baud Rate for BMS Network DIP switches B0 – B3 can be used to set the field baud rate of the ProtoNode to match the baud rate required by the BMS for BACnet MS/TP.
  • Page 17: Interfacing Protonode To Devices

    ProtoNode Gateway 3. INTERFACING PROTONODE TO DEVICES 3.1 ProtoNode Connection Ports Connection Ports FIGURE 9 - ProtoNode 750-426...
  • Page 18: Device Connections To Protonode

    An RS-485 network with more than one device needs to have biasing to ensure proper communica- tion. The biasing only needs to be done on one device. The ProtoNode has 510 Ohm resistors that can be used to set the biasing. The ProtoNode's default positions from the factory for the biasing jumpers are OFF.
  • Page 19: End Of Line Termination Switch For The Modbus Rs-485 Device Network

    On short cabling runs the EOL switch does not to need to be turned ON. If the ProtoNode is placed at one of the ends of the trunk, set the blue EOL jumper to the ON posi- tion straddling the pins closest to the outside of the board of the ProtoNode.
  • Page 20: Bacnet Ms/Tp Or Metasys N2 (Rer): Wiring Field Port To Rs-485 Network

    Use standard grounding principles for RS-485 GND. See Section 4.4 for information on connecting to BACnet/IP network. If the ProtoNode is the last device on the BACnet MS/TP or Metasys N2 trunk, then the End-Of-Line Termination Switch needs to be enabled (Figure 14).
  • Page 21: Auto-Discovery

    ProtoNode. Do not Enable Auto-Discovery when the unit is powered. When power is applied to a ProtoNode that is set to enable Auto-Discovery, it will take about 3 min- utes to complete the discovery of all of the RS-485 devices attached to the ProtoNode.
  • Page 22: Power Connections

    ProtoNode Gateway Power to ProtoNode ProtoNode Pin # Assignment Power In (+) Pin 4 Power In (-) Pin 5 Frame Ground Pin 6 FRAME GND FIGURE 18 - Power Connections 750-426...
  • Page 23: Web Configurator

    Connect a standard CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and ProtoNode. • The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx net- work. •...
  • Page 24: Connecting To Protonode's Web Configurator

    4.2 Connecting to ProtoNode's Web Configurator After setting a local PC on the same subnet as the ProtoNode (Section 4.1), open a web browser on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.
  • Page 25: Web App Landing Page

    ProtoNode Gateway • From the Web App landing page (Figure 22), click the Configure tab. FIGURE 22 - Web App Landing Page • Then click the <Profiles Configuration> button to go to the Web Configurator page. FIGURE 23 - Configuration Page NOTE: The FieldPoP™...
  • Page 26: Selecting Profiles For Devices Connected To Protonode

    For every device that is added, assign a unique Modbus Node-ID. This specification must match the device's network settings. NOTE: If multiple devices are connected to the ProtoNode, set the BACnet Virtual Server Nodes field to “Yes”; otherwise leave the field on the default “No” setting.
  • Page 27: Web Configurator Showing Available Profiles For Selection

    ProtoNode Gateway FIGURE 25 - Web Configurator showing available profiles for selection • Then press the <Submit> button to add the profile to the list of devices to be configured. • Repeat this process until all the devices have been added.
  • Page 28: Bacnet/Ip And Modbus Tcp/Ip: Setting Ip Address For Field Network

    4.4 BACnet/IP and Modbus TCP/IP: Setting IP Address for Field Network After setting a local PC to the same subnet as the ProtoNode (Section 5.1), open a web browser on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.
  • Page 29: Changing Ip Address Via Fs-Gui

    DHCP Client State should remain disabled; Domain Name Server 1 and 2 should be left at their cur- rent values. NOTE: If the ProtoNode is connected to a managed switch/router, the IP Gateway of the ProtoNode should be set to the IP Address of that managed switch/router.
  • Page 30: Bacnet Ms/Tp And Bacnet/Ip: Setting Node_Offset To Assign Specific Device Instances

    5. BACNET MS/TP AND BACNET/IP: SETTING NODE OFFSET TO ASSIGN SPECIFIC DEVICE INSTANCES After setting a local PC to the same subnet as the ProtoNode (Section 4.1), open a web browser on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.
  • Page 31: How To Start The Installation Over: Clearing Profiles

    6. HOW TO START THE INSTALLATION OVER: CLEARING PROFILES • After setting your PC to be on the same subnet as the ProtoNode (section 4.1), open a web browser on your PC and enter the IP address of the ProtoNode; the default address is 192.168.1.24.
  • Page 32: Commissioning Protonode On A Lonworks Network

    Connect a CAT5 Ethernet cable (straight through or crossover) between the PC and the ProtoNode. • The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx net- work. •...
  • Page 33: Generating An Xif File

    ProtoNode Gateway • Open a web browser and go to the following address: [IP Address of ProtoNode]/fserver.xif. Example: 192.168.1.24/fserver.xif • If the web browser prompts to save the file, save the file onto the local PC. If the web browser displays the xif file as a web page, save the file onto the local PC as “fserver.xif”.
  • Page 34: Smc Cloud User Setup, Registration And Login

    8. SMC CLOUD USER SETUP, REGISTRATION AND LOGIN 8.1 User Setup When configuring the ProtoNode, the startup technician will prepare an account for the individual who will be the Enterprise Customer Administrator for the site (see SMC Cloud Startup Guide 750- 431 for OEM and Enterprise Customer user hierarchy).
  • Page 35: Registration Process

    Record the email account and password for future use. 8.2 Registration Process Once SMC Cloud user credentials have been generated, the ProtoNode can be registered onto the SMC Cloud server. Click on the FieldPoP™ tab on the left-hand side of the screen.
  • Page 36: Registration Information Page

    Domain Name Server (DNS) settings: DNS1=8.8.8.8 DNS2=8.8.4.4 Ensure that the ProtoNode is properly connected to the Internet NOTE: If changes to the network settings are done, remember to click “Update IP Settings” and then power cycle the ProtoNode.
  • Page 37: Smc Cloud Registration Page

    ProtoNode Gateway On the registration page, fill in user credentials and all other device information fields for registration of each individual ProtoNode in the field. The Username and Password are the same as those on the user’s FieldPoP account. FIGURE 38 - SMC Cloud Registration Page To input the device location do one of the following: •...
  • Page 38: Login

    ProtoNode Gateway FIGURE 39 - Device Registered for SMC Cloud 8.3 Login After the ProtoNode is registered, go to www.fieldpop.io and type in the appropriate login information as per registration credentials. FIGURE 40 - SMC Cloud Login Page If the login password is lost, see the SMC Cloud Start-up Guide for recovery instructions.
  • Page 39: Smc Cloud Landing Page

    ProtoNode Gateway FIGURE 41 - SMC Cloud Landing Page NOTE: For additional SMC Cloud instructions see the SMC Cloud Start-up Guide. 750-426...
  • Page 40: Appendix A. Troubleshooting

    Extract the executable file and complete the installation. FIGURE 42 - Ethernet port location Connect a standard CAT5 Ethernet cable between the user's PC and ProtoNode. Double click on the FS Toolbox Utility and click Discover Now on the splash page.
  • Page 41: Viewing Diagnostic Information

    ProtoNode Gateway A.2. Viewing Diagnostic information Type the IP address of the ProtoNode into your web browser or use the FieldServer Toolbox to con- nect to the ProtoNode. Click on Diagnostics and Debugging button, then click on view, and then on connections.
  • Page 42: Check Wiring And Settings

    Check baud rate, parity, data bits, stop bits Check Modbus device address Verify wiring Verify the Modbus device is connected to the same subnet as the ProtoNode Verify the Modbus device was discovered in Web Configurator. (Section 4) • Field COM problems: If Ethernet protocols are used, observe Ethernet LEDs on the ProtoNode (Appendix A.4)
  • Page 43: Led Diagnostics For Communications Between Protonode And Devices

    ProtoNode Gateway A.4. LED Diagnostics for Communications Between ProtoNode and Devices See the diagram below for ProtoNode RER and LER LED Locations. Table 2: Description The SPL LED will light if the unit is not getting a response from one or more of the configured devices.
  • Page 44: Take Diagnostic Capture With The Fieldserver Toolbox

    Sierra Monitor Resource Center Software Downloads. Extract the executable file and complete the installation. FIGURE 44 - Ethernet Port Location Connect a standard Cat 5 Ethernet cable between the PC and ProtoNode. Double click on the FS Toolbox Utility •...
  • Page 45: Mounting Protonode

    Once the Diagnostic test is complete, a .zip file will be saved on the PC. • Choose <Open> to launch explorer and have it point directly at the correct folder. • Send the Diagnostic zip file to customer service representative (found by visiting www.cleaverbrooks.com/ Find-a-Rep/Index.aspx) A.6. Mounting ProtoNode The following mounting options are available: •...
  • Page 46: Update Firmware

    7. When the download is complete, click on the “System Restart” button. A.8. BACnet: Setting Network_Number for more than one ProtoNode on Subnet For both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet, they must be assigned unique Network_Number values.
  • Page 47: Securing Protonode With Passwords

    ProtoNode Gateway A.9. Securing ProtoNode with Passwords Access to the ProtoNode can be restricted by enabling a password. There are 2 access levels defined by 2 account names: Admin and User. • The Admin account has unrestricted access to the ProtoNode.
  • Page 48: Appendix B. Data Point Mappings For Cleaver-Brooks Applications

    ProtoNode Gateway APPENDIX B — DATA POINT MAPPINGS for CLEAVER-BROOKS APPLICATIONS B.1. FALCON HYDRONIC FALCON HYDRONIC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus (Bit Point Name Data Object Data EIP Tag Name...
  • Page 49 ProtoNode Gateway FALCON HYDRONIC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus (Bit Point Name Data Object Data EIP Tag Name Lon Name Lon SNVT Type Address Register Type Type...
  • Page 50: Falcon Steam

    ProtoNode Gateway B.2. FALCON STEAM FALCON STEAM Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet Modbus Point Name Data Object Data Point (Bit) EIP Tag Name Lon Name Lon SNVT Type Register Type Type...
  • Page 51 ProtoNode Gateway FALCON STEAM Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet Modbus Point Name Data Object Data Point (Bit) EIP Tag Name Lon Name Lon SNVT Type Register Type Type Address LEAD/LAG_ENABLE...
  • Page 52: Cb780

    ProtoNode Gateway B.3. CB780 CB780 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data (Bit) EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type...
  • Page 53 ProtoNode Gateway CB780 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data (Bit) EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type...
  • Page 54: Cb120

    ProtoNode Gateway B.4. CB120 CB120 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data (Bit) EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type...
  • Page 55 ProtoNode Gateway CB120 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data (Bit) EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type...
  • Page 56: Hsc

    ProtoNode Gateway B.5. HSC HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type...
  • Page 57 ProtoNode Gateway HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type C Boiler 5 Outlet Temp...
  • Page 58 ProtoNode Gateway HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type C Boiler 10 Outlet Temp...
  • Page 59 ProtoNode Gateway HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type NC Boiler E Outlet Temp...
  • Page 60 ProtoNode Gateway HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type NC Boiler J Outlet Temp...
  • Page 61 ProtoNode Gateway HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type Damper Mod 4 Input (Prove) Data...
  • Page 62 ProtoNode Gateway HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type Cond Boiler 2 Run Cycles...
  • Page 63: Lcs

    ProtoNode Gateway B.6. LCS LCS Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data EIP Tag Name Lon Name Lon SNVT Type Data Type Object Id Address Register Type...
  • Page 64: Pcs

    ProtoNode Gateway B.7. PCS PCS Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type...
  • Page 65: Hawk 1000

    ProtoNode Gateway B.8. HAWK 1000 Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Drive Fault 10001 nvoDrvFlt_XXX...
  • Page 66 ProtoNode Gateway Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Firing Rate Manual 10059 nvoFirRatMan_XXX...
  • Page 67 ProtoNode Gateway Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Gas Actuator Modbus Comm Error Node 2...
  • Page 68 ProtoNode Gateway Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type AI Slot8 Ch0 Value 2Stg Econ Temp IN...
  • Page 69 ProtoNode Gateway Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type * AWB[0]9 00010 nviAWB_0_9_XXX SNVT_switch...
  • Page 70: Hawk 2000

    ProtoNode Gateway B.9. HAWK 2000 Hawk 2000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Actuator Modbus Comm Fault...
  • Page 71 ProtoNode Gateway Hawk 2000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Modbus Comm Error: F2-2 10096 nvoMdCmErF22_XXX...
  • Page 72: Hawk 4000

    ProtoNode Gateway B.10. HAWK 4000 Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Drive Fault 10001 nvoDrvFlt_XXX...
  • Page 73 ProtoNode Gateway Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Firing Rate Manual 10059 nvoFirRatMan_XXX...
  • Page 74 ProtoNode Gateway Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Gas Act 2 Modbus Comm Error Node 3...
  • Page 75 ProtoNode Gateway Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type AI Slot8 Ch2 Value (EU)
  • Page 76 ProtoNode Gateway Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type AI[29] 30131 nvoAI_29_XXX SNVT_count_f Elapsed Time...
  • Page 77: Hawk 5000

    ProtoNode Gateway B.11. HAWK 5000 Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Comb Air Blower Running...
  • Page 78 ProtoNode Gateway Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Bad Ql- Drum Level (06:01)
  • Page 79 ProtoNode Gateway Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type LAlm - Remote Modulation 10100 nvoLAlRmMdIn_XXX...
  • Page 80 ProtoNode Gateway Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type CPU Battery Alm 10150 nvoCPUBatAlm_XXX...
  • Page 81 ProtoNode Gateway Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Flue Gas O2 30015 nvoFluGsO2_XXX...
  • Page 82 ProtoNode Gateway Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Air Flo or Usr Def (07:07)
  • Page 83: Hawk Master

    ProtoNode Gateway B.12. HAWK MASTER PANEL Hawk Master Panel Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Boiler A Ethernet Comm Error...
  • Page 84 ProtoNode Gateway Hawk Master Panel Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Boiler H Start Output...
  • Page 85 ProtoNode Gateway Hawk Master Panel Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Blr G Lead Lag Entered Seq...
  • Page 86 ProtoNode Gateway Hawk Master Panel Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type * Lag 2 Boiler Selection...
  • Page 87: Adac

    ProtoNode Gateway B.13. ADAC ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Deaerator Lvl BAD QUALITY 11351...
  • Page 88 ProtoNode Gateway ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Feed Pump 1 ON 11399 nvoFdPmp1ON_XXX...
  • Page 89 ProtoNode Gateway ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Surge Tank Lvl Lo 11449 nvoSgTkLvlLo_XXX...
  • Page 90 ProtoNode Gateway ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type DAB1[9]4 11499 nvoDAB1_9_4_XXX SNVT_switch DAB1[9]5 11500...
  • Page 91 ProtoNode Gateway ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type Surge Header Pressure 30929 nvoSrgHdrPrs_XXX SNVT_count_f...
  • Page 92 ProtoNode Gateway ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Data Lon Name Lon SNVT Type Object Id Address Register Type Type DAI1[23] 31181 nvoDAI1_23_XXX SNVT_count_f DAI1[24] 31182...
  • Page 93: Hawk Ics

    ProtoNode Gateway B.14. HAWK ICS Hawk ICS Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Drive Fault 10001 nvoDrvFlt_XXX...
  • Page 94 ProtoNode Gateway Hawk ICS Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type External Device Start 10050 nvoExtDevSt_XXX...
  • Page 95 ProtoNode Gateway Hawk ICS Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Lon Name Lon SNVT Type Data Type Object Id Address Register Type Boiler Efficiency 30007 nvoBlrEff_XXX SNVT_lev_percent...
  • Page 96: Shark 100

    ProtoNode Gateway B.15. SHARK 100 Shark 100 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon Name Lon SNVT Type Object Id Address Register Type Type...
  • Page 97: Shark 200

    ProtoNode Gateway B.16. SHARK 200 Shark 200 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon Name Lon SNVT Type Address Register Type Type Volts A-N...
  • Page 98: Udc 2500

    ProtoNode Gateway B.17. UDC 2500 UDC 2500 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon SNVT Name Lon SNVT Name Address Register Type Type...
  • Page 99: Pim

    ProtoNode Gateway B.18. PUMP INTERFACE MODULE Pump Interface Module Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon SNVT Name Lon SNVT Name Address Register...
  • Page 100: Bim

    ProtoNode Gateway B.19. BOILER INTERFACE MODULE Boiler Interface Module Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Data EIP Tag Name Lon SNVT Name Lon SNVT Name Object ID Address...
  • Page 101: Cb780 / 783 Farc

    ProtoNode Gateway B.20. FARC CB780/783 FARC CB 780/783 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon SNVT Name Lon SNVT Name Address Register Type...
  • Page 102 ProtoNode Gateway FARC CB 780/783 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon SNVT Name Lon SNVT Name Address Register Type Type BC_Flt_Hist_Code_Rec3...
  • Page 103 ProtoNode Gateway FARC CB 780/783 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon SNVT Name Lon SNVT Name Address Register Type Type Fuel ID...
  • Page 104 ProtoNode Gateway FARC CB 780/783 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) BACnet BACnet N2 Point Modbus Point Name Data Object Data EIP Tag Name Lon SNVT Name Lon SNVT Name Address Register Type Type R7999 Fault Info Word 33...
  • Page 105: Hawk 4000 V2

    ProtoNode Gateway B.21. HAWK 4000 V2 HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Drive Fault 10001 nvoDrvFlt_XXX SNVT_switch...
  • Page 106 ProtoNode Gateway HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Non Recycle Limit Relay 10051 nvoNoRecLmRl_XXX SNVT_switch Drive to Lo Fire (FARC)
  • Page 107 ProtoNode Gateway HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Stack Pressure Input Fail 10103 nvoStkPrInFl_XXX SNVT_switch Hi Stack Pressure Alm...
  • Page 108 ProtoNode Gateway HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Yokogawa O2 Sensor Fault 10155 nvoYokO2SnFl_XXX SNVT_switch Mix O2 Sensor Calibration Fail...
  • Page 109 ProtoNode Gateway HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type AB[12]15 10208 nvoAB_12_15_XXX SNVT_switch Air Actuator 2 Position Deviation...
  • Page 110 ProtoNode Gateway HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Slot8 Ch6 Flo Total 30067 nvoSlC6FlTo_XXX SNVT_count_f Slot8 Ch7 Flo Total...
  • Page 111 ProtoNode Gateway HAWK_4000_V2 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type AWB[0]3 00004 nvoAWB_0_3_XXX SNVT_switch AWB[0]4 00005 nvoAWB_0_4_XXX SNVT_switch...
  • Page 112: Adac 1000

    ProtoNode Gateway B.22. ADAC 1000 ADAC_1000 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Deaerator Lvl BAD QUALITY 10001 nvoDeLvlBdQu_XXX SNVT_switch...
  • Page 113 ProtoNode Gateway ADAC_1000 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Feed Pump 2 In AUTO 10056 nvoFdP2InAut_XXX SNVT_switch Feed Pump 3 In AUTO...
  • Page 114 ProtoNode Gateway ADAC_1000 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Transfer Pump Lead Lag Write Permissive 10113 nvoTrPmpLLWr_XXX SNVT_switch...
  • Page 115 ProtoNode Gateway ADAC_1000 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type DAR1[9] 30019 nvoDAR1_9_XXX SNVT_count_f Stop Lag Feed Pump Limit...
  • Page 116 ProtoNode Gateway ADAC_1000 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Feed Pump 1 LEAD/LAG Status 30133 nvoFdPm1LLSt_XXX SNVT_count_f Feed Pump 2 LEAD/LAG Status...
  • Page 117 ProtoNode Gateway ADAC_1000 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks (Continued) Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type * DAWB[0]7 nviDAWB0_7_XXX SNVT_switch * DAWB[0]8 nviDAWB0_8_XXX SNVT_switch * DAWB[0]9...
  • Page 118: Hawk 4500

    ProtoNode Gateway B.23. HAWK 4500 Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Drive Fault 10001 nvoDrvFlt_XXX SNVT_switch Modbus Comm Error...
  • Page 119 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Non Recycle Limit Relay 10051 nvoNoRecLmRl_XXX SNVT_switch Drive to Lo Fire (FARC)
  • Page 120 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Stack Pressure Input Fail 10103 nvoStkPrInFl_XXX SNVT_switch Hi Stack Pressure Alm...
  • Page 121 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Yokogawa O2 Sensor Fault 10155 nvoYokO2SnFl_XXX SNVT_switch Mix O2 Sensor Calibration Fail...
  • Page 122 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type AB[12]14 10207 nvoAB_12_14_XXX SNVT_switch AB[12]15 10208 nvoAB_12_15_XXX SNVT_switch Air Actuator 2 Position Deviation...
  • Page 123 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Alarm Warn Annunciate 10259 nvoAlmWrnAnn_XXX SNVT_switch Alarm Trip Annunciate...
  • Page 124 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Slot8 Ch7 EU 30077 nvoSl8Ch7EU_XXX SNVT_count_f Stack Pressure 30079 nvoStkPrs_XXX...
  • Page 125 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type Number Of Cycles 30154 nvoNumCyc_XXX SNVT_count_f AB[0] 30201 nvoAB_0_XXX...
  • Page 126 ProtoNode Gateway Hawk 4500 EtherNet/IP Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet BACnet N2 Point Modbus LonWorks Name LonWorks SNVT Object Object ID Data Address Register Type Type * AWR[4] 40009 nvoAWR_4_XXX SNVT_count_f * AWR[5] 40011 nvoAWR_5_XXX...
  • Page 127: Appendix C. "A" Bank Dip Switch Settings

    ProtoNode Gateway APPENDIX C — “A” BANK DIP SWITCH SET- Address TINGS Address 750-426...
  • Page 128 ProtoNode Gateway Address Address 750-426...
  • Page 129 ProtoNode Gateway Address Address 750-426...
  • Page 130: Appendix D. Interfacing Protonode Gateway To Boiler Networks

    6 Pin Phoenix connector - pin outs D.2. ClearFire Boiler Modbus Network The diagram below shows a typical application using the ProtoNode Gateway in a ClearFire Lead Lag system NOTE: In the diagram above there are two independent Modbus networks. One is dedicated for Fal- con lead lag control;...
  • Page 131: Falcon System Display Modbus Gateway Connection (Com2) Wiring To The Protonode

    ProtoNode Gateway D.3 Falcon System Display Modbus Gateway Connection (COM2) Wiring to the ProtoNode • Connect Falcon Display COM 2 port (Modbus A) to Pin 1, labeled Tx/+ on the ProtoNode’s 6 pin Phoenix connector. • Connect Falcon Display COM 2 port (Modbus B) to Pin 2, labeled Rx/- on the ProtoNode’s 6 pin Phoenix connector.
  • Page 132: Cb780E Modbus Connections To Protonode

    ProtoNode Gateway D.4 CB780E Modbus connections to ProtoNode D.5. CB120E Modbus connections to ProtoNode D.6. HSC Modbus connections to ProtoNode MJ2 PORT (HSC SYSTEM ADMINISTRATOR) 750-426...
  • Page 133: Appendix E. Specifications \ Ul Compliance

    (Specifications subject to change without notice) E.1.1. Compliance with UL Regulations For UL compliance, the following instructions must be met when operating ProtoNode. • The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating tem- perature range.
  • Page 134: Appendix F. Limited 2 Year Warranty

    ProtoNode Gateway APPENDIX F — LIMITED 2 YEAR WARRANTY Cleaver-Brooks warrants this product to be free from defects in workmanship or material under nor- mal use and service for two years after date of shipment. C-B will repair or replace any equipment found to be defective during the warranty period.