1. DESCRIPTION
Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK503 is a fast
response fusible element type sprinkler designed for early fire suppression. With a
16.8 (242 metric*) nominal K-Factor and special deflector, this sprinkler produces large,
high-momentum water droplets in a hemispheric pattern below the deflector. This per-
mits penetration of the fire plume and direct wetting of the burning fuel surface while
cooling the atmosphere early in the development of a high-challenge fire.
Viking Sprinkler VK503 may be used in the protection of ordinary types of storage.
However, it is primarily intended to protect the following types of storage, which tend
to produce severe-challenge fires: palletized and solid pile storage and single, double,
multiple row, and portable open rack storage (no open-top containers or solid shelves).
Viking ESFR Pendent Sprinkler VK503 provides protection of most common storage
materials, including:
--Encapsulated or unencapsulated Class I, II, III, and IV commodities*.
--Cartoned and uncartoned unexpanded plastics*.
--Cartoned expanded plastics*.
* Refer to the Approval Charts and Commodity Selection and Design Criteria Overview for cULus
Listing and FM Approval requirements that must be followed.
In addition, some storage arrangements of rolled paper, aerosols, and rub-
ber tires may be protected by Viking ESFR Pendent Sprinkler VK503.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNWH
Successfully meets UL 1767 test standard and compliance
program for ESFR sprinklers installed in-rack storage with
high clearances to ceiling (20 ft or greater)
FM Approved: Class 2027
NYC Approved: MEA 89-92-E, Volume 41
CCCF Approved: Approved by the China Certification Center for
Fire Products (CCCF)
Refer to the Approval Charts and Commodity Selection and Design
Criteria Overview for cULus Listing and FM Approval requirements
that must be followed.

3. TECHNICAL DATA

Specifications:
Available since 2007.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi
(34.5 bar).
Thread size: 3/4" NPT or 20 mm BSPT
Nominal K-Factor: 16.8 U.S. (242 metric*)
* Metric K-factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Overall Length: 2-7/8" (73 mm)
Deflector Diameter: 1-3/4" (44.5 mm)
Covered by one or more of the following patents: US5,829,532; US6,059,044; US6,336,509; US6,502,643; US6,868,917; AU722593; GB2336777
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000
Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Compression Screw: Stainless Steel UNS-S31603
Form No. F_120106
18.10.11
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Rev 18.2
ESFR PENDENT SPRINKLER
VK503 (K16.8)
TABLE 1
SPRINKLER GENERAL INFORMATION
Item
Sprinkler Identification
Number (SIN)
K-factor, gpm/psi
(lpm/bar
½
Thread Size
Sprinkler Orientation
Maximum Working Pressure
Replaces Form No. F_120106 Rev 18.1
(Replaced design criteria tables; added P65 Warning.)
Page 1 of 6
Description
VK503
)
16.8 (242)
½
3/4" NPT (20 mm BSPT)
Pendent
175 psi (12 bar)

Advertisement

loading

Summary of Contents for Viking VK503

  • Page 1: Technical Data

    Viking Sprinkler VK503 may be used in the protection of ordinary types of storage. However, it is primarily intended to protect the following types of storage, which tend to produce severe-challenge fires: palletized and solid pile storage and single, double, multiple row, and portable open rack storage (no open-top containers or solid shelves).
  • Page 2: Installation

    Ordering Information: (Also refer to the current Viking price list.) Order ESFR Pendent K16.8 Sprinkler VK503 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to sprinkler base part number.
  • Page 3: Operation

    Installation standards require sprinklers to be tested and, if necessary, replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25) and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers that have operated cannot be reassembled or reused, but must be replaced.
  • Page 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES...
  • Page 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 1 (UL) ESFR Pendent Sprinkler VK503...
  • Page 6 IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data, the latest standards of NFPA, FM Global, VdS, LPCB, and any other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and standards whenever applicable.