Honeywell RM7824A Product Data page 13

Relay module
Table of Contents

Advertisement

IMPORTANT
After 200 hours of operation, the configuration
jumper cannot be changed. If it is changed after 200
hours of operation, the RM7824A locks out. The
RM7824A cannot be reset and has to be replaced.
SERVICE NOTE: Clipping and removing a site-configurable
jumper enhances the level of safety.
STATIC CHECKOUT
WARNING
Fire, Explosion or Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
1. Use extreme care while testing the system. Voltage
is present on most terminal connections when
power is on.
2. Open the master switch before installing or
removing a jumper on the subbase.
3. Before continuing to the next test, be sure to
remove the test jumper(s) used in the previous
tests.
4. Replace all limits and interlocks not operating
properly. Do not bypass limits and interlocks.
5. Close all manual fuel shutoff valve(s) before starting
these tests.
RM7824A
Test No.
Models
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property damage.
Make sure all manual fuel shutoff valves are closed.
IMPORTANT
Low fuel pressure limits, if used, could be open. Bypass them with jumpers for the remaining Static Tests (if required).
1
All
None
2
All
None
3
All
3-10
Table 5. Static Checkout.
Test
Jumpers
Voltmeter
3-L2
24 Vdc at terminal 3
6-L2
24 Vdc at terminal 6
Ignition spark (if ignition
transformer relay is connected to
terminal 10.
7800 SERIES RM7824A RELAY MODULE
Equipment Recommended
1. Voltmeter (20K ohm/volt minimum sensitivity) set on the
0-30 Vdc scale.
2. Two jumper wires: No. 14 wire, insulated, 12 in. (305
mm) long, with insulated alligator clips at both ends.
General Instructions
1. Perform all applicable tests listed in Static Checkout,
Table 5, in the order listed.
2. MAKE SURE THAT ALL MANUAL FUEL SHUTOFF
VALVE(S) ARE CLOSED.
3. Perform only those tests designated for the specific
RM7824A model being tested.
4. Raise the set point of the operating controller to
simulate a call for heat.
5. For each test, open the master switch and install the
jumper wire(s) between the subbase wiring terminals
listed in the Test Jumpers column of Table 5.
6. Close the master switch before observing operation.
7. Read the voltage between the subbase wiring terminals
listed in the Voltmeter column of Table 5.
8. If there is no voltage or the operation is abnormal, check
the circuits and external devices as described in the last
column.
9. Check all wiring for correct connections, tight terminal
screws, correct wire, and proper wiring techniques.
Replace all damaged or incorrectly sized wires.
10. Replace faulty controllers, limits, interlocks, actuators,
valves, transformers, motors and other devices as
required.
11. Obtain normal operation for each required test before
continuing the checkout.
12. After completing each test, be sure to remove the test
jumper(s).
Normal Operation
13
If Operation is Abnormal, Check the
Item Listed Below
1. Master switch.
2. Power connected to the master
switch.
3. Overload protection (fuse, circuit
breaker) has not opened the power
line.
1. Limits.
2. Burner controller.
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay..
65-0155—2