1. DESCRIPTION
e
MT-516
is a temperature controller for cooling or heating applications. Equipped with a cyclic
timer output, it can also be used as alarm output, with the option of an internal audible alarm (buzzer), or
second cooling or heating stage. Another feature available is the turning off of the control functions,
e
making the MT-516
operate only as a temperature meter. Through an intelligent function
blocking system, it prevents unauthorized personnel from changing the control settings.
Product conforming to UL Inc. (United States and Canada).
2. SAFETY RECOMMENDATIONS
- Check the controller for correct assembling;
- Make sure that the power supply is off and that it is not turned on during the controller installation;
- Read the present manual before installing and using the controller;
- Use adequate Personal Protective Equipmenet (PPE);
- For application at sites subject to water spills, such as refrigerated cabinets, install the protecting vinyl
supplied with the controller;
- For protection under more critical conditions, we recommend the Ecase cover, which we make
available as an optional item (sold separately);
- The installation procedures should be performed by a qualified technician.
3. APPLICATIONS
• Milk cooling tanks
• Refrigerated counters
• Air conditioning with automatic winter/summer system
4. TECHNICAL SPECIFICATIONS
Power supply
Control temperature
Operating temperature
Maximum output current
Operating humidity
Dimensions (mm)
Cutout dimensions (mm)
(*)
Admissible variation in relation to the voltage rating.
(**)
This device can measure and control temperatures of up to 200° C when used in conjunction with a model SB59 silicon
sensor cable (sold separately).
Note: Sensor cable length can be increased to up to 200 meters by the user by using a PP 2 x 24 AWG cable.
5. INDICATIONS AND KEYS
LED indicator (2nd stage output on)
LED heating indicator
LED cooling indicator
Quick access
menu key (Flatec)
Set key
e
MT-516
6. WIRING DIAGRAM
6.1. Identifications (see Images I to IV)
- Image I: MT-516E , supplied at 115 Vac.
- Image II: MT-516E, supplied at 230 Vac.
- Image III: MT-516EL, supplied at 12 Vac/dc.
- Image IV: MT-516EL, supplied at 24Vac/dc.
IMPORTANT
THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID DAMAGE IN THE CONNECTION AT INSTRUMENT
TERMINALS:
SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER TERMINALS;
MT-516
DIGITAL TEMPERATURE CONTROL
WITH CONFIGURABLE 2nd STAGE
Alarm
Buzzer
Cyclic
Functions
Timer
Lockdown
MT-516E: 115 or 230 Vac ±10%(*) (50/60 Hz)
MT-516EL: 12 or 24 Vac/dc +10%(*)
-50 to 105ºC (-58 to 221°F)(**)
0 to 50 ºC / 32 to 122°F
OUT1: 16(12)A / 240Vac 2HP
OUT2: 10A / 240Vac 1/4HP
10 to 90% RH (without condensation)
76 x 34 x 77 mm (WxHxD)
71 ± 0,5 x 29 ± 0,5 mm (see image V)
Functions lockdown indication LED
LED control functions shutdown
indicator
LED temperature unit
indicator
e
IP 65
FRONT
Control Functions
Serial
Protection
Shutdown
programming
level
Image I: MT-516E - 115Vac
WIRING
TERMINALS
TEMPERATURE
SENSOR
Image
II:
MT-516E
WIRING
TERMINALS
TEMPERATURE
SENSOR
Image III: MT-516EL - 12Vac/dc
WIRING
TERMINALS
TEMPERATURE
SENSOR
Upper key
Image IV: MT-516EL - 24Vac/dc
Lower key
WIRING
TERMINALS
TEMPERATURE
SENSOR
6.2. Temperature sensor connection
- Connect the sensor wires to terminals '1 and 2': the polarity is not relevant.
- Length of the sensor cables can be increased by user himself to up to 200 meters, using a PP 2x24
AWG cable.
e
e
M T- 51 6
M T- 51 6
CONTROLLER
WIRING
TERMINALS
NC
NO NO
COMMON
COMMON
115 Vac
LOAD
}
POWER
GRID
- 230 Vac
CONTROLLER
WIRING
TERMINALS
NC
NO NO
COMMON
COMMON
230 Vac
LOAD
}
POWER
GRID
CONTROLLER
WIRING
TERMINALS
NC
NO NO
COMMON
COMMON
FONT
12Vac/dc
LOAD
}
POWER
GRID
CONTROLLER
WIRING
TERMINALS
NC
NO NO
COMMON
COMMON
FONT
24Vac/dc
LOAD
}
POWER
GRID
evolution
E251415
S u r g e P r o t e c t i v e
Device (SPD)
(sold separately)
W i r i n g d i a g r a m f o r
instalation of SPD in
magnectic contactor
A1 and A2 are the terminals
of the contactor coil.
A1
A2
W i r i n g d i a g r a m f o r
instalation of SPD in line
with loads
For direct drive take in to
consideration the specified
maximum current.
LOAD