Page 2
Service Manual for Tri-Channel Cold Pan SUB-GP IMPORTANT WARNING AND SAFETY INFORMATION WARNING READ THIS MANUAL THOROUGHLY BEFORE OPERATING, INSTALLING, OR PERFORMING MAINTENANCE ON THE EQUIPMENT. WARNING FAILURE TO FOLLOW INSTRUCTIONS IN THIS MANUAL CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH.
Service Manual for Tri-Channel Cold Pan SUB-GP SPECIFICATIONS Inside Unit Provide adequate space along the front and MODEL DESCRIPTION VOLTAGE AMPS back taking care to not block airflow to the fan. SUB-GP Tri-Channel 120 VAC (60Hz) Cold Pan 220 VAC (50Hz) Outside Unit Be sure that the unit has access to ample air;...
Service Manual for Tri-Channel Cold Pan SUB-GP MAINTENANCE CAUTION: N e v e r u s e a n a c i d - b a s e d cleanser! Be sure to clean all f o o d p r o d u c t s...
Service Manual for Tri-Channel Cold Pan SUB-GP PREVENTIVE MAINTENANCE Figure 2 Location of Condensing Coil Figure 3 Location of Condensing Coil Cleaning the Condenser Coil The condenser coil is located and accessed Failure to maintain a clean condenser coil can from the front of the unit, (Figure 3).
Service Manual for Tri-Channel Cold Pan SUB-GP PARTS REPLACEMENT 9. Install thermostat probe in evaporator coil. 10. Using tags, connect thermostat wiring. Thermostat Replacement 11. Install control panel cover and mounting screws. 12. Install condenser 13. Connect unit to power source and test refrigeration assembly.
Service Manual for Tri-Channel Cold Pan SUB-GP Refrigeration System Replacement NOTE: Before installing replacement refrigeration assembly, pressure check evaporator coils for leaks. General 9. Install replacement refrigeration assembly onto slide bars. 10. Slide in refrigeration assembly to original position. 11. Install refrigeration assembly mounting hardware.
Service Manual for Tri-Channel Cold Pan SUB-GP Charging Procedure 1. Install a temporary access valve on the high and low side of process hoses as close to factory crimps as possible. NOTE: Prior to refrigeration system service, special care must be taken during the evacuation 2.
Service Manual for Tri-Channel Cold Pan SUB-GP TROUBLESHOOTING SYMPTOM CAUSE REMEDY Cabinet too warm Unit not plugged in Plug unit in Thermostat set too warm Set thermostat to a higher number for a colder temperature Thermostat switch stuck open in...