ABB SPAJ 141 C User Manual And Technical Description page 43

Combined overcurrent and earth-fault relay
Table of Contents

Advertisement

Switch
Function
number
SGR3/1
When SGR3/1 = 1, the starting signal of stage I> is linked to TS1
SGR3/2
When SGR3/2 = 1, the tripping signal of stage I> is linked to TS1
SGR3/3
When SGR3/3 = 1, the starting signal of stage I>> is linked to TS1
SGR3/4
When SGR3/4 = 1, the tripping signal of stage I>> is linked to TS1
SGR3/5
When SGR3/5 = 1, the starting signal of stage I
SGR3/6
When SGR3/6 = 1, the tripping signal of stage I
SGR3/7
When SGR3/7 = 1, the starting signal of stage I
SGR3/8
When SGR3/8 = 1, the tripping signal of stage I
Checksum for factory setting of SGR3
PAINOS
PAINOS
Factory Checksum
setting
0
0
0
0
> is linked to TS1
0
o
> is linked to TS1
0
o
>> is linked to TS1
0
o
>> is linked to TS1
0
o
11
value
1
2
4
8
16
32
64
128