VAMP 259 Operation And Configuration Instructions

VAMP 259 Operation And Configuration Instructions

Line manager, technical description
Table of Contents

Advertisement

Quick Links

VAMP 259
Line manager
Operation and configuration
instructions
Technical description

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 259 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for VAMP 259

  • Page 1 VAMP 259 Line manager Operation and configuration instructions Technical description...
  • Page 2 VM259EN007...
  • Page 3: Table Of Contents

    2.4.7. Configuration menu CONF ........34 2.4.8. Protocol menu Bus ..........36 2.4.9. Single line diagram editing ........39 2.4.10. Blocking and interlocking configuration ..... 39 3. VAMPSET PC software ............40 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 4: General

    Broken line protection I< Undercurrent protection >, U >> Zero sequence voltage protection T> Thermal overload protection U>, U>>, U>>> Overvoltage protection U<, U<<, U<<< Undervoltage protection P<, P<< Reverse and underpower protection VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 5: User Interface

    Disconnecting a live circuit may cause dangerous voltages! Any operational measures must be carried out according to national and local handling directives and instructions. Carefully read through all operation instructions before any operational measures are carried out. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 6: Local Panel User Interface

    2.1. Front panel The figure below shows, as an example, the front panel of VAMP 259 and the location of the user interface elements used for local control. Figure 2.1-1. The front panel of VAMP 259 1. LCD dot matrix display 2.
  • Page 7 LOCALPANEL CONF/Display backlight ctrl setting is used for selecting trigger input for backlight control. When the selected input activates (rising edge), display backlight is set on for 60 minutes. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 8: Menu Navigation And Pointers

    4. Keys for selecting submenus [selecting a digit in a numerical value] (LEFT/RIGHT) 5. Additional information key (INFO) NOTE! The term, which is used for the buttons in this manual, is inside the brackets. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 9: Operation Indicators

    (For more resetting depends on the information about output type of configuration, relay configuration, please connected or latched. see chapter 2.4.5). A- C LED lit Application-related status Configurable indicators. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 10: Adjusting Display Contrast

    The readability of the LCD varies with the brightness and the temperature of the environment. The contrast of the display can be adjusted via the PC user interface, see chapter 3. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 11: Local Panel Operations

    The active main menu selection is indicated with black back- ground color. The possible navigating directions in the menu are shown in the upper-left corner by means of black triangular symbols. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 12 Figure 2.2.1-2. Principles of the menu structure and navigation in the menus 6. Push the INFO key to obtain additional information about any menu item. 7. Push the CANCEL key to revert to the normal display. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 13: Main Menu

    ExDO External digital outputs Prot Protection counters, combined overcurrent status, protection status, protection enabling, cold load and inrush detectionIf2> and block matrix DIST Common settings for distance zones (Z1 … Z5) VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 14 3rd undervoltage stage Uo> 1st residual overvoltage stage Uo>> 2nd residual overvoltage stage P< reverse and underpower stage P<< reverse and underpower stage f>< over/under-frequency stage f>><< over/under-frequency stage f< 1st underfrequency stage VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 15 There are two extra menus, which are visible only if the access level "operator" or "configurator" has been opened with the corresponding password. Detailed protocol configuration is done with VAMPSET. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 16: Menu Structure Of Protection Functions

    "Configurator". If no front panel button is pressed within five minutes and there is no VAMPSET communication, the force flag will be set to "Off" position. The forcing is explained in chapter 2.3.4. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 17 "Operator". Operating levels are explained in chapter 2.2.5.  t>> 0.60s The total operation delay is set to 600 ms. This value can be edited if the operating level is at least "Operator". VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 18  SetGrp 1 The setting group has been 1. This line can be reached by pressing ENTER and several times the DOWN button. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 19: Setting Groups

    (the LEFT key is used when the active setting group is 2 and the RIGHT key is used when the active setting group is 1). Figure 2.2.3-2. Example of I> setting submenu VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 20: Fault Logs

    (See Figure 2.2.4-2, Log2 = log two). The log two is selected by pressing the RIGHT key once. Figure 2.2.4-2. Example of selected fault log VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 21: Operating Levels

    Opening: Default password is 2 Setting state: Push ENTER Closing: The level is automatically closed after 10 minutes idle time. Giving the password 9999 can also close the level. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 22 Get the serial number of the relay (Example: 12345) Send both the numbers to vampsupport@vamp.fi and ask for a password break. A device specific break code is sent back to you. That code will be valid for the next two weeks.
  • Page 23: Operating Measures

    2. Select the virtual input object (empty or black square) 3. The dialog opens 4. Select “VIon” to activate the virtual input or select “VIoff” to deactivate the virtual input VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 24: Measured Data

    Reverse; ??] P/PHASE SEQUENCIES Io Io/Uo angle [] fAdop P/PHASE SEQUENCIES Adopted frequency [Hz] E/ENERGY Exported energy [MWh] E/ENERGY Exported reactive energy [Mvar] E/ENERGY Imported energy [MWh] E/ENERGY Imported reactive energy [Mvar] VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 25 I/HARM. DISTORTION Total harmonic distortion of phase current IL1 [%] THDIL2 I/HARM. DISTORTION Total harmonic distortion of phase current IL2 [%] THDIL3 I/HARM. DISTORTION Total harmonic distortion of phase current IL3 [%] VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 26 Duration of previous interruption [s] Status U/VOLT. INTERRUPTS Voltage status [LOW; NORMAL] Z12, Z23, Z1<, Z2<, Z3<, Z4<, Z5< Line to line impedance (primary/sec) Z12angle Z1<, Z2<, Z3<, Z4<, Z5< Impedance angle Z23angle Z31angle VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 27: Reading Event Register

    It is possible to set the order in which the events are sorted. If the “Order” -parameter is set to “New-Old”, then the first event in the EVENT LIST is the most recent event. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 28: Forced Control (Force)

    10. Repeat the steps 1...4 to exit the Force function. 11. Push the CANCEL key to return to the main menu. NOTE! All the interlockings and blockings are bypassed when the force control is used. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 29: Configuration And Parameter Setting

    ENTER key again. The parameter can now be set. When the parameter change is confirmed with the ENTER key, a [RESTART]- text appears to the top-right corner of the display. This means that auto-resetting is VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 30: Parameter Setting

    6. Push the ENTER key to accept a new value. If you want to leave the parameter value unchanged, exit the edit state by pushing the CANCEL key. Figure 2.4.1-1.Changing parameters VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 31: Setting Range Limits

    The allowed setting range is shown in the display in the setting mode. To view the range, push the INFO key. Push the CANCEL key to return to the setting mode. Figure 2.4.2-2. Allowed setting ranges show in the display VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 32: Disturbance Recorder Menu Dr

     Operation counters (DI COUNTERS)  Operation delay (DELAYs for DigIn)  The polarity of the input signal (INPUT POLARITY). Either normally open (NO) or normally closed (NC) circuit.  Event enabling EVENT MASK1 VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 33: Configuring Digital Outputs Do

    The relay includes several protection functions. However, the processor capacity limits the number of protection functions that can be active at the same time. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 34: Configuration Menu Conf

     Rated current of the motor VOLTAGE SCALING  Rated VT primary voltage (Uprim)  Rated VT secondary voltage (Usec)  Rated U VT secondary voltage (Uosec)  Voltage measuring mode (Umode) VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 35 "User".  Offset, i.e. constant error, of the synchronization source (SyOS).  Auto adjust interval (AAIntv).  Average drift direction (AvDrft): "Lead" or "lag".  Average synchronization deviation (FilDev). VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 36: Protocol Menu Bus

     Message counter [Msg#]. This can be used to verify that the device is receiving messages.  Communication error counter [Errors]  Communication time-out error counter [Tout].  Same information as in the previous menu. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 37 I/O modules connected to the extension port. Only one instance of this protocol is possible.  Bit rate [bit/s]. Default is "9600".  Parity [Parity]. Default is "Even". For details see the technical description part of the manual. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 38 CPU and the Profibus ASIC. For details see the technical description part of the manual. VAMP 24h support phone +358 (0)20 753 3264 VM259EN007...
  • Page 39: Single Line Diagram Editing

    Furthermore, the interlocking between objects can be configured in the same blocking matrix of the VAMPSET software. For more information, please refer to the VAMPSET manual (VMV.EN0xx). VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 40: Vampset Pc Software

    The VAMPSET program can also use TCP/IP LAN connection. Optional hardware is required. There is a free of charge PC program called VAMPSET available for configuration and setting of VAMP relays. Please download the latest VAMPSET.exe from our web page www.vamp.fi. For more information about the VAMPSET software, please refer to the user’s manual with the code...
  • Page 41 3.1. Event log ................. 145 3.2. Disturbance recorder ........... 147 3.3. Cold load pick-up and inrush current detection ..152 3.4. Voltage sags and swells ..........154 3.5. Voltage interruptions ............ 156 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 42 6.1.3. Extension port ............223 6.1.4. Ethernet port ............224 6.2. Communication protocols .......... 225 6.2.1. PC communication ..........225 6.2.2. Modbus TCP and Modbus RTU ......225 6.2.3. Profibus DP ............. 226 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 43 8.1. Rear panel view ............249 8.2. Auxiliary voltage ............256 8.3. Serial communication connection ......256 8.3.1. Pin assignments of communication options ..259 8.3.2. Front panel connector ......... 262 8.4. Optional two channel arc protection card ....263 8.5.
  • Page 44 9.4.4. Voltage sag & swell ..........293 9.4.5. Voltage interruptions ..........293 10. Abbreviations and symbols ..........294 11. Constructions ..............296 12. Order information ............... 297 13. Revision history ..............299 14. Reference information ............302 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 45: Introduction

    This part of the user manual describes the protection functions, provides application examples and contains technical data. The numerical VAMP line protection device includes as main protection full scheme distance and line differential protection functions backed up with several standard protection functions...
  • Page 46: Main Features

    40 to 265 V or V . The alternative power supply is for 18 to 36 V  Built-in disturbance recorder for evaluating all the analogue and digital signals. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 47: Principles Of Numerical Protection Techniques

    Figure 1.2-2 shows the heart of the numerical technology. That is the main block diagram for calculated functions. Figure 1.2-3 shows a principle diagram of a single-phase overvoltage or overcurrent function. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 48 1 Introduction Technical description techniques Figure 1.2-1 Principle block diagram of the VAMP hardware Figure 1.2-2 Block diagram of signal processing and protection software Figure 1.2-3 Block diagram of a basic protection function VAMP 24h support phone +358 (0)20 753 3264...
  • Page 49: Protection Functions

    Thermal overload protection U>, U>>, U>>> Overvoltage protection U<, U<<, U<<< Undervoltage protection P<, P<< Reverse and underpower protection 81H/81L f><, f>><< Overfrequency and underfrequency protection f<, f<< Underfrequency protection Prg1...8 Programmable stages VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 50: General Features Of Protection Stages

    After testing the force flag will automatically reset 5-minute after the last local panel push button activity. The force flag also enables forcing of the output relays and forcing the optional mA outputs. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 51 This parameter is important when grading the operation time delay settings between relays. Figure 2.3-1. Definition for retardation time. If the delay setting would be slightly shorter, an unselective trip might occur (the dash line pulse). VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 52 (the dashed 40 ms pulse in the figure). In VAMP devices the retardation time is less than 50 Reset time (release time) Figure 2.3-2 shows an example of reset time i.e. release delay, when the device is clearing an overcurrent fault.
  • Page 53 (dead band) acts according this figure. Figure 2.3-4. Behaviour of a less than comparator. For example in under- voltage and under frequency stages the hysteresis (dead band) acts according this figure. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 54: Distance Protection Z

    If impedance is inside the tripping zone (normally presented in R-X plane), the distance function operates. In short circuit faults there are 3 possible fault loops. The VAMP distance protection function calculates the impedances of the fault loops continuously and thus separate pick-up conditions are not needed.
  • Page 55 A 0.5 second cyclic buffer storing the phase-to-earth voltages is used as voltage memory. The stored phase angle information is used as direction reference if all the phase voltages drop below 1% during a fault. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 56 ―DI for remote open ctr‖ or ―DI for local open ctr‖ input of the object. Outputs of the relay programmable logic can be connected to ―DI for remote open crt‖ or ―DI for local open ctr‖ inputs via the internal ―Virtual output‖ signals. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 57: Earth-Fault Distance Protection Ze< (21N)

    Figure 2.4.2-1 An example of tripping zone. Gray area is the tripping zone, polygonal characteristics. Figure 2.4.2-2 Earth-fault fault loops. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 58 Load angle  LoadR 0.05 .. 250.00 1.00 Load resistance Common parameters for all earth fault zones 0.00 .. 10.00 0.00 Earth factor φ ( -60 .. 60 ° Earth factor angle VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 59 ―Virtual output‖ signals. 2.4.3. Double earth fault Vamp 259 -line manager is equipped with DEF (Cross country fault) functionality which operates together with distance protection (21). DEF is planned to operate in compensated and isolated meshed network. The single phase to earth -fault in this case does not correspond to a short-circuit cause only a small capacitive or compensated earth-current flows.
  • Page 60 DEF –algorithm in Vamp 259 –relay is enabled together with distance protection Z1e<. Enabling is done by selecting network grounding as ―Comp‖ compensated. When DEF -function is enabled earth fault loop Z1e<...
  • Page 61 Selected relay sees the fault 1 (L1-G) inside the zone Z1e<. If phase priority is selected as ―1-> 2-> 3‖ this relay would trip and the same would do to the relay opposite the protected line. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 62 ―1-> 2-> 3‖ this relay would NOT trip because fault L2-G inside the zone does not have the highest priority at the moment when the double earth-fault occurs. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 63 (same applies to residual current if triggering condition U is selected). Selected relay does not see any fault inside the zone Z1e<. There is no reason to trip. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 64 (same applies to residual current if triggering condition U is selected). Selected relay sees the fault but outside the zone Z1e< so there is no reason to trip. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 65 ―same‖ line. Both lines will be separated from the network due the activation of SC-distance stage. Note! Simple over-current and earth-fault protection is preferred to have as a back-up for “DEF algorithm”. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 66: Distance Protection Applications

    R setting. This is because the R value is greater than the X value. If the allowed inaccuracy is for example 5 % and R setting is 10 Ω the allowed tolerance would be 0.5 Ω. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 67 X value is greater than the R value. If the allowed inaccuracy is for example 5 % and X setting is 10 Ω the allowed tolerance would be 0.5 Ω. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 68 X value is greater than the R value. If the allowed inaccuracy is for example 5 % and X setting is 10 Ω the allowed tolerance would be 0.5 Ω. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 69 1.0 Ω / 40 ms (40 ms is fixed value). If the speed of the swing exceeds the 1.0 Ω / 40 ms limit there won‘t be block and the distance stage trips normally. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 70 (IoCalc) is less than 10%. These mentioned parameters I2/I1 and IoCalc are fixed in the relay and can not be set by users. Figure 2.4.4-1 How to use power swing blocking with certain zones. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 71: Line Differential Protection Ldi> (87)

    The threshold characteristics is biased for CT saturation as presented in Figure 2.5-1 . RESISTIVE Slope Trip region dI> pick-up (Basic setting) Start of slope (Basic limit) Phase current (pu) Figure 2.5-1 LDP tripping threshold characteristics VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 72 Default 0.050 CT primary [10 .. 20000] CT ratio of the other unit other Default 500 Recorded SCntr Start counter (Start) values reading TCntr Trip counter (Trip) reading dI> status Protection state VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 73: Overcurrent Stage I> (50/51)

    See chapter 0. Setting groups There are two settings groups available for each stage. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 74 Force flag for status forcing for test purposes. This is a common flag for all stages and output relays, too. This flag is automatically reset 5 minutes after the last front panel push button pressing. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 75 Parameters of the overcurrent stages I>>, I>>> (50/51) Parameter Value Unit Description Note Status Current status of the stage Blocked Start Trip SCntr Cumulative start counter TCntr Cumulative trip counter SetGrp 1 or 2 Active setting group VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 76 Three phase fault Maximum fault current Load 1 s average phase currents before the fault EDly Elapsed time of the operating time setting. 100% = trip SetGrp Active setting group during fault VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 77: Directional Overcurrent Protection I

    (For networks having the maximum possible earth fault current less than the over current setting, use 67N, the directional earth fault stages.) Figure 2.7-1 Example of protection area of the directional overcurrent function. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 78 If this fault situation remains on longer than the delay setting, a trip signal is issued. Four independent stages There are four separately adjustable stages available: I >, >>, I >>> and I >>>>. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 79 Description Note Status Current status of the stage Blocked Start Trip TripTime Estimated time to trip SCntr Cumulative start counter TCntr Cumulative trip counter SetGrp 1 or 2 Active setting group VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 80 Undirectional (50/51) Offset  Angle offset in degrees   Measured power angle U1 Measured positive sequence voltage A, B, C, D, User‘s constants for standard equations. Type=Parameters. See chapter 2.24. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 81 For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 82 1 s average phase currents before the fault EDly Elapsed time of the operating time setting. 100% = trip Angle  Fault angle in degrees Positive sequence voltage during fault SetGrp Active setting group during fault VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 83 Relative negative sequence value component Recorded SCntr Cumulative start counter values TCntr Cumulative start counter Maximum I fault component EDly Elapsed time as compared to the set operating time, 100% = tripping VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 84: Undercurrent Protection I< (37)

    Min. value of fault current as per times Imot Load 1s mean value of pre-fault currents I —I EDly Elapsed time as compared to the set operate time, 100% = tripping VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 85: Directional Earth Fault Protection I 0Φ > (67N)

    Since residual voltage is calculated from the phase voltages, therefore any separate zero sequence voltage transformers are not needed. The setting values are relative to the configured voltage transformer (VT) voltage/3. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 86 Each stage can be connected to supervise any of the following inputs and signals:  Input I for all networks other than rigidly earthed.  Calculated signal I for rigidly and low impedance 0Calc earthed networks. I 0Calc VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 87 2.24 for more information. Setting groups There are two settings groups available for each stage. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 88 Figure 2.10-3 Two example of operation characteristics of the directional earth fault stages in sector mode. The drawn I phasor in both figures is inside the trip area. The angle offset and half sector size are user‘s parameters. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 89 Pick-up setting relative to the parameter "Input" and the corresponding CT value Uo> Pick-up setting for U Measured U Curve Delay curve family: Definite time Inverse time. See chapter 2.24. IEEE IEEE2 PrgN VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 90 See chapter 2.24. For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 91: Earth Fault Protection I > (50N/51N)

    If the fault situation remains on longer than the user's operation time delay setting, a trip signal is issued. Figure 2.11-1. Block diagram of the earth fault stage I > VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 92 There are four separately adjustable earth fault stages: I >, >>, I >>>, and I >>>>. The first stage I > can be configured for definite time (DT) or inverse time operation characteristic VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 93 TCntr Cumulative trip counter SetGrp 1 or 2 Active setting group SGrpDI Digital signal to select the active setting group None Digital input Virtual input LED indicator signal LEDx Virtual output VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 94 See chapter 2.24. For details of seting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 95 F = Editable when force flag is on Recorded values of the latest eight faults There is detailed information available of the eight latest earth faults: Time stamp, fault current, elapsed delay and setting group. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 96: Zero Sequence Voltage Protection U (59N)

    > and U >>). Setting groups There are two settings groups available for both stages. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 97 Definite operation time For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 98 Time stamp of the recording, date hh:mm:ss.ms Time stamp, time of day Fault voltage relative to Un/3 EDly Elapsed time of the operating time setting. 100% = trip SetGrp Active setting group during fault VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 99: Thermal Overload Protection T> (49)

    (Setting value) k Ambient temperature factor (Permitted current due to tamb) Figure 2.13-1. The rated current (I or I mode Cooling time coefficient (cooling time constant =  C x   VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 100 5 % over the maximum defined by the rated current and the service factor k. The temperature rise starts to approach value 110 %. At about 340 minutes the temperature rise is 100 % and a trip follows. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 101 The thermal overload stage is provided with a separately settable alarm function. When the alarm limit is reached the stage activates its start signal. Figure 2.13-2. Example of the thermal model behaviour. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 102 1...16 For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 103: Overvoltage Protection U> (59)

    Setting groups There are two settings groups available for each stage. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 104 Pick-up value scaled to U>>> primary value U>, U>>, Pick-up setting relative to U U>>> t>, t>>, Definite operation time t>>> RlsDly Release delay (U> stage only) Hyster Dead band size i.e. hysteresis (default) VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 105: Undervoltage Protection U< (27)

    15 % to the blocking action to be enough fast. The self blocking can be disabled by setting the low voltage block limit equal to zero. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 106 Figure 2.15-1 Under voltage state and block limit. Three independent stages There are three separately adjustable stages: U<, U<< and U<<<. All these stages can be configured for definite time (DT) operation characteristic. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 107 Recorded values of the latest eight faults There are detailed information available of the eight latest faults for each of the stages: Time stamp, fault voltage, elapsed delay, voltage before the fault and setting group. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 108: Reverse Power And Underpower Protection P

    Sn. The nominal apparent power is determined by the configured voltage and current transformer values. Equation 2.16-1    Rated imary Rated imary There are two identical stages available with independent setting parameters. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 109 Active power value Recorded SCntr Start counter values (Start) reading TCntr Trip counter (Trip) reading Max value of fault EDly Elapsed time as compared to the set operating time, 100% = tripping VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 110: Overfrequency And Underfrequency Protection F>, F< (81H/81L)

    2.22). All the stages have definite operation time delay (DT). Setting groups There are two settings groups available for each stage. Switching between setting groups can be controlled by digital inputs, virtual inputs (mimic display, communication, logic) and manually. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 111 For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 112: Rate Of Change Of Frequency (Rocof) Protection Df/Dt (81R)

    However, in case of a heavy short circuit fault or in case the new load exceeds the generating capacity, the average frequency keeps on decreasing. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 113 0.5 Hz/s and the delay settings are t=0.60 s and t =0.60 s. Equal times t == t will give a definite time delay characteristics. Although the frequency slope fluctuates the stage will not release but continues to calculate the average VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 114 Equation 2.18-1   where, TRIP Resulting operation time (seconds). TRIP df/dt i.e. slope setting (hertz/seconds). Operation time setting t (seconds). Measured average frequency slope (hertz/seconds). VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 115 Figure 2.18-4 An example of inverse df/dt operation time. The time to trip will be 0.3 s, although the setting is 0.6 s, because the average slope 1 Hz/s is steeper than the setting value 0.5 Hz/s. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 116 SCntr Start counter (Start) values reading TCntr Trip counter (Trip) reading %Hz/s Max rate of change fault value EDly Elapsed time as compared to the set operating time, 100% = tripping VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 117: Synchrocheck (25)

    This time must be longer than ―CB time‖. Sync mode = Synchronization is tried to make exactly when angle difference is zero. In this mode df-setting should be very small (<0.3Hz). VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 118 Circuit-breaker control ShowInfo Off; On Additional information display about the sychrocheck status to the mimic. SGrpDI Digital The input for changing inputs the setting group. SetGrp 1; 2 The active setting group. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 119 The ―OK‖-signal is active, when the synchronising conditions are met, or the voltage check criterion is met. The ―fail‖-signal is activated, if the function fails to close VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 120 L12 (phase to phase sync voltage) L1 (phase to ground sync voltage) Number of synchrocheck stages Availability of U directional I stages Power measurement 3-phase power, 3-phase power, nonsymmetrical loads nonsymmetrical loads VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 121: Second Harmonic O/C Stage I F2 >(51F2)

    Definite operating time S_On Enabled; Enabled Start on event Disabled S_Off Enabled; Enabled Start off event Disabled T_On Enabled; Enabled Trip on event Disabled T_Off Enabled; Enabled Trip off event Disabled VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 122: Circuit Breaker Failure Protection Cbfp (50Bf)

    The CBFP stage is supervising all the protection stages using the same selected trip relay, since it supervises the control signal of this device. See chapter 5.4 for details about the output matrix and the trip relays. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 123 CBFP (50BF) Parameter Value Unit Description yyyy-mm-dd Time stamp of the recording, date hh:mm:ss.ms Time stamp, time of day EDly Elapsed time of the operating time setting. 100% = trip VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 124: Programmable Stages (99)

     Hyster Dead band (hysteresis)  NoCmp Only used with compare mode under (‗<‘). This is the limit to start the comparison. Signal values under NoCmp are not regarded as fault. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 125 Voltage behind circuit breaker Voltage behind 2 circuit breaker ILmin, ILmax Minimum and maximum of phase currents ULLmin, ULLmax Minimum and maximum of line voltages ULNmin, ULNmax Minimum and maximum of phase voltages VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 126 Pick up setting in pu Definite operation time. Hyster Dead band setting NoCmp Minimum value to start under comparison. (Mode=‘<‘) Set = An editable parameter (password needed) C = Can be cleared to zero VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 127: Arc Fault Protection (50Arc/50Narc)- Optional

    Binary input of the arc card. 48 Vdc.  S1/BI Light sensor S1 or the binary input.  S2/BI Light sensor S2 or the binary input.  S1/S2/BI Light sensor S1 or S2 or the binary input. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 128 BO, indicators etc. offered by the output matrix (See chapter 5.4). BI is a dry input for 48 Vdc signal from binary outputs of other VAMP devices or dedicated arc protection devices by VAMP.
  • Page 129 Sensor 1, 2 and BI in use For details of setting ranges see chapter 9.3. Set = An editable parameter (password needed) C = Can be cleared to zero F = Editable when force flag is on VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 130 Time stamp, time of day Type Fault type value. Only for ArcI> stage. Fault value Load Pre fault current. Only for ArcI> stage. Edly Elapsed time of the operating time setting. 100% = trip VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 131: Inverse Time Operation

    ‗PrgN‘'. There are maximum three different programmable curves available at the same time. Each programmed curve can be used by any number of protection stages. See chapter 2.24.3. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 132 The full scope of inverse delay curves goes up to 20 times the setting. At high setting the maximum measurement capability limits the scope of inverse curves according the following table. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 133: Standard Inverse Delays Iec, Ieee, Ieee2, Ri

    = 0.2 A 0.1 A *) The availableI values depend on the order code. VAMP 259 has 5 A, 1 A or 0.2 A residual current inputs available. Desired input needs to be specified when ordering the relay. Example of limitations...
  • Page 134 There are three different delay types according IEC 60255-3, Normal inverse (NI), Extremely inverse (EI), Very inverse (VI) and a VI extension. Additional there is a de facto standard Long time inverse (LTI). VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 135 The operation time in this example will be 5 seconds. The same result can be read from Figure 2.24.1-1. Figure 2.24.1-1 IEC normal inverse Figure 2.24.1-2 IEC extremely inverse delay. delay. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 136 Table 2.24.1-3. The IEEE standard defines inverse delay for both trip and release operations. However, in the VAMP device only the trip time is inverse according the standard but the release time is constant. The operation delay depends on the measured value and other parameters according Equation 2.24.1-2.
  • Page 137 The operation time in this example will be 1.9 seconds. The same result can be read from Figure 2.24.1-8. Figure 2.24.1-5 ANSI/IEEE long Figure 2.24.1-6 ANSI/IEEE long time inverse delay time very inverse delay VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 138 Technical description Figure 2.24.1-7 ANSI/IEEE long Figure 2.24.1-8 ANSI/IEEE time extremely inverse delay moderately inverse delay Figure 2.24.1-9 ANSI/IEEE short Figure 2.24.1-10 ANSI/IEEE short time inverse delay time extremely inverse delay VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 139 There are four different delay types according Table 2.24.1-4. The old electromechanical induction disc relays have inverse delay for both trip and release operations. However, in VAMP devices only the trip time is inverse the release time being constant.
  • Page 140 The operation time in this example will be 0.38 seconds. The same result can be read from Figure 2.24.1-11. Figure 2.24.1-11 IEEE2 moderately Figure 2.24.1-12 IEEE2 normal inverse delay inverse delay VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 141      pickup Equation 2.24.1-5 RXIDG  5  RXIDG pickup = Operation delay in seconds = User‘s multiplier = Measured value = User‘s pick up setting pickup VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 142 The operation time in this example will be 3.9 seconds. The same result can be read from Figure 2.24.1-16. Figure 2.24.1-15 Inverse delay of Figure 2.24.1-16 Inverse delay of type RI. type RXIDG. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 143: Free Parametrisation Using Iec, Ieee And Ieee2 Equations

    The minimum definite time delay start latest, when the measured value is twenty times the setting. However, there are limitations at high setting values due to the measurement range. See chapter 2.24 for more details. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 144: Programmable Inverse Time Curves

    The minimum definite time delay start latest, when the measured value is twenty times the setting. However, there are limitations at high setting values due to the measurement range. See chapter 2.24 for more details. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 145: Supporting Functions

    Modification can be done in ―Local panel conf‖ – menu. Alarm screen (popup screen) can also be enabled in this same menu when Vampset –setting tool is used. The oldest one VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 146 FORMAT OF EVENTS ON THE LOCAL DISPLAY Code: CHENN CH = event channel, NN=event code Event description Event channel and code in plain text yyyy-mm-dd Date (for available date formats see chapter 3.10) hh:mm:ss.nnn Time VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 147: Disturbance Recorder

    (includes all the inputs). Also the digital outputs reserve one channel (includes all the outputs). If digital inputs and outputs are recorded, there will be still 10 channels left for analogue waveforms. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 148 ReadyRec n = Available recordings m = maximum number of recordings The value of 'm' depends on sample rate, number and type of the selected channels and the configured recording length. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 149 Total harmonic distortion of input Ub THDUc Total harmonic distortion of input Uc DI_2 Digital inputs 21-32 Prms Active power rms value Qrms Reactive power rms value Srms Apparent power rms value VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 150 Set = An editable parameter (password needed) *) This is the fundamental frequency rms value of one cycle updated every 10 ms. **) This is the fundamental frequency rms value of one cycle updated every 20 ms. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 151 3.2 Disturbance recorder Running virtual comtrade files with VAMP relays Virtual comtrade files can be run with VAMP relays with the v.10.74 software or a later version. Relay behaviour can be analysed by playing the recorder data over and over again in the relay memory.
  • Page 152: Cold Load Pick-Up And Inrush Current Detection

    It is also possible to use the detection signal to block any set of protection stages for a given time. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 153 Pickup Pick-up setting for minimum start current Maximum transition time for start recognition Pickupf2 Pick-up value for relative amount of 2 harmonic, I Set = An editable parameter (password needed) VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 154: Voltage Sags And Swells

    One of the most important power quality functions are voltage sag and swell monitoring. VAMP provides separate monitoring logs for sags and swells. The voltage log is trigged, if any voltage input either goes under the sag limit (U<) or exceeds the swell limit (U>). There are four registers for both sags and swells in the fault log.
  • Page 155 Maximum voltage value during the sag/swell in the input 1 Max2 Maximum voltage value during the sag/swell in the input 2 Max3 Maximum voltage value during the sag/swell in the input 3 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 156: Voltage Interruptions

    On the other hand, if the limit U < is high and the voltage has been near this limit, and then there is a short but very deep dip, it will be recognized (Figure 3.5-2). VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 157 Number of voltage sags during the previous observation period Total Total (summed) time of voltage sags during the current observation period Prev Total (summed) time of voltage sags during the previous observation period VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 158: Current Transformer Supervision

    Display Imax>, Setting values as primary values Imin< Recorded Date Date of CT supervision alarm Values Time Time of CT supervision alarm Imax Maximum phase current Imin Minimum phase current VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 159: Voltage Transformer Supervision

    Measured negative value sequence voltage Measured negative sequence current Recorded Date Date of VT supervision alarm Values Time Time of VT supervision alarm Recorded negative sequence voltage Recorded negative sequence current VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 160: Circuit Breaker Condition Monitoring

    The points 4...8 are not needed for the CB in Figure 3.8-1. Thus they are set to 100 kA and one operation in the table to be discarded by the algorithm. Figure 3.8-1. An example of a circuit breaker wearing characteristic graph. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 161 The operations left can be read from the counters "A Ln" (Alarm 1) and "A Ln" (Alarm2). There are three values for both alarms, one for each phase. The smallest of three is supervised by the two alarm functions. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 162 Using = 10000 = 80 = 31 kA = 1.25 kA and the Equation 3.8-2 and Equation 3.8-3, the device calculates 10000   5038 31000 1250 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 163 Thus Alarm2 counters for phases are decremented by 3. In phase the currents is less than the alarm limit current 6 kA. For such currents the decrement is one.   VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 164 'Alarm1 off' event enabling 'Alarm2 on' event enabling 'Alarm2 off' event enabling Clear  Clearing of cycle counters Clear Set = An editable parameter (password needed) The breaker curve table is edited with VAMPSET. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 165: Energy Pulse Outputs

    Pulse length of active DURATION exported energy 100 … 5000 Pulse length of reactive exported energy 100 … 5000 Pulse length of active imported energy 100 … 5000 Pulse length of reactive imported energy VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 166 The peak pulse frequency will be 50000/10 = 5000 pulses/h. Set pulse length to 3600/5000  0.2 = 0.5 s or less. The lifetime of the mechanical output relay will be 50x10 /190 h = 30 a. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 167 PLC having common minus and using an external wetting voltage Figure 3.9-4. Application example of wiring the energy pulse outputs to a PLC having common minus and an internal wetting voltage. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 168: System Clock And Synchronization

    1000, if some other period than one week has been used. For example if the drift has been 37 seconds in 14 days, the relative drift is 37*1000/(14*24*3600) = 0.0306 ms/s. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 169 NOTE! When the internal time is roughly correct – deviation is less than four seconds – any synchronizing or auto-adjust will never turn the clock backwards. Instead, in case the clock is leading, it is softly slowed down to maintain causality. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 170 *) Astronomically a range –11 ... +12 h would be enough, but for political and geographical reasons a larger range is needed. **) If external synchoronization is used this parameter will be set automatically. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 171 Auto-lag/lead The device synchronizes to the sync source, meaning it starts automatically leading or lagging to stay in perfect sync with the master. The learning process takes few days. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 172: Running Hour Counter

    Date and time of the last activation Stopped at Date and time of the last inactivation Set = An editable parameter (password needed). (Set) = An informative value which can be edited as well. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 173: Timers

    3.12 Timers 3.12. Timers The VAMP protection platform includes four settable timers that can be used together with the user's programmable logic or to control setting groups and other applications that require actions based on calendar time. Each timer has its own settings.
  • Page 174 The timer switches on and off every day except Saturdays and Sundays MTWTFS The timer switches on and off every day except Sundays. SatSun The timer switches on and off every Saturday and Sunday. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 175: Combined Overcurrent Status

    Several events are enabled Several events of an increasing fault is disabled ClrDly 0 ... Duration for active alarm 65535 status Alr , Alr2, Alr VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 176 Not used with Spabus, because Spabus masters usually don't like to have unpaired On/Off events. **) Used with SPA-bus protocol, because most SPA-bus masters do need an off-event for each corresponding on-event. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 177: Self Supervision

    Error registers There are four 16-bit error registers which are readable through remote protocols. The following table shows the meaning of each error register and their bits. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 178 E2prom error 0 (LSB) +12V Internal voltage fault SelfDiag4 ComBuff BUS: buffer error The error code is displayed in self diagnostic events and on the diagnostic menu on local panel and VAMPSET. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 179: Short Circuit Fault Location

    4. The fault distance quantities are calculated. 5. Two phases with the biggest fault current are selected. 6. The load currents are compensated. 7. The faulty line length reactance is calculated. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 180 Time Fault time Cntr Number of faults Pre-fault current (=load current) Fault Current during the fault Post Post-fault current Udrop Voltage dip during the fault Durati Fault duration Xfault Fault reactance VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 181 3 Supporting functions 3.15 Short circuit fault location Below is presented an application example where the fault location algorithm is used at the incomer side. Notice following things while commissioning the relay: VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 182 3.15 Short circuit fault location 3 Supporting functions Technical description Below is presented an application example where the fault location algorithm is used at the feeder side. Notice following things while commissioning the relay: VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 183: Earth-Fault Location

    4. The fault distance is calculated by dividing the change of the voltage by the change of the negative sequence current. 5. Only the imaginary part is used, so then the reactance is solved. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 184 Measured and recorded values of earth-fault location EFDi: Parameter Value Unit Description Measured Fault ph Fault phase information values/ Fault reactance recorded Date Fault date values Time Fault time Time Fault time Count Number of faults VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 185: Measurement Functions

    Figure 4-1 Example of various current values of a transformer inrush current. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 186: Measurement Accuracy

    The specified frequency range is 45 Hz – 65 Hz. THD and harmonics Inaccuracy I, U > 0.1 PU 2 % units Update rate Once a second The specified frequency range is 45 Hz – 65 Hz. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 187: Rms Values

    RMS voltages The device calculates the RMS value of each voltage input. The minimum and the maximum of RMS values are recorded and stored (see chapter 4.5).     VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 188: Harmonics And Total Harmonic Distortion (Thd)

     Another way to calculate THD is to use the RMS value as reference instead of the fundamental frequency value. In the example above the result would then be 13.0 %. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 189: Demand Values

    Demand of power factor PF kvar Demand of reactive power Q Demand of apparent power S RMS values Demand of phase current I Demand of phase current I Demand of phase current I VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 190: Minimum And Maximum Values

    Demand values of phase currents, rms values (rms value) PFda Power factor demand value The clearing parameter "ClrMax" is common for all these values. Parameters Parameter Value Description ClrMax Reset all minimum and maximum values  Clear VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 191: Maximum Values Of The Last 31 Days And Twelve Months

    The available modes are:  ―3LN/LLy‖ The synchrocheck voltage transformer is connected to line-to- line voltages U  ―3LN/LNy ‖ The synchrocheck voltage transformer is connected to line-to- line voltages U VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 192: Power Calculation

    = Complex conjugate of the measured phase fundamental frequency current phasor. Apparent power, active power and reactive power are calculated as follows   real  imag   VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 193: Direction Of Power And Current

    Power Current Power cos Power factor quadrant related to direction voltage + inductive Lagging Forward + capacitive Leading Forward   inductive Leading Reverse   capacitive Lagging Reverse   VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 194: Symmetric Components

           = 33 % = 33 % = 100 % When using a single phase test device, the relative unbalance will always be 100 %. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 195                    = 19.2 % = 38.5 % = 19.2 % = 50 % VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 196 Figure 4.10-1 Example of symmetric component calculation using line-to- neutral voltages. Unscaling the geometric results gives = 100/3 x 2/3 = 38.5 % = 1003 x 1/3 = 19.2 % = 1/3:2/3 = 50 % VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 197: Primary, Secondary And Per Unit Scaling

     Primary current is I = 4x500/5 = 400 A Example 2: Primary to secondary. CT = 500/5 The device displays I = 400 A  Injected current is I = 400x5/500 = 4 A VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 198 Example 4: Per unit to secondary for residual current. Input is I = 50/1 The device setting is 0.03 pu = 3 %.  Secondary current is = 0.03x1 = 30 mA VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 199: Voltage Scaling

    = 3x58x12000/110 = 10902 V Example 2: Primary to secondary. VT = 12000/110 The device displays U = 10910 V.  Symmetric secondary voltages at Ua, U and U = 10910/3x110/12000 = 57.7 V4 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 200 Example 2: Per unit to secondary. VT = 12000/110 The device displays U = 20 %.  If U = 0, then secondary voltages at U = 3x0.2x110 = 38.1 V VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 201: Control Functions

    NAMES for OUTPUT RELAYS (editable with VAMPSET only) Description String of Names for DO on VAMPSET max. 32 screens. Default is characters ―Trip relay n‖, n=1…14 or ‖Alarm relay n‖, n=1...5 Set = An editable parameter (password needed) VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 202: Digital Inputs

    Label and description texts can be edited with VAMPSET according the application. Labels are the short parameter names used on the local panel and descriptions are the longer names used by VAMPSET. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 203 Default is "DIn", n=1...32 Description String of Long name for DIs. max. 32 Default is characters "Digital input n", n=1...32 Set = An editable parameter (password needed) VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 204 50…250 VAC X8:12 Common for D27…28  If T5 not in X8:19...20 If T6 not in X8:17...18 External 18…265 VDC 50…250 VAC If T7 not in X8:15...16 If T8 not in X8:13...14 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 205: Virtual Inputs And Outputs

    Virtual outputs are shown in the output matrix and the block matrix. Virtual outputs can be used with the user's programmable logic and to change the active setting group etc. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 206: Output Matrix

    The selection of the input is done with the VAMPSET software under the menu "Release output matrix latches". Under the same menu, the "Release latches" parameter can be used for resetting. Figure 5.4-1 Output matrix. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 207: Blocking Matrix

    The connection of an object to specific output relays is done via an output matrix (object 1-6 open output, object 1-6 close output). There is also an output signal ―Object failed‖, which is activated if the control of an object fails. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 208 0.02 … 600 s changes If changing states takes longer than the time defined by ―Object timeout‖ setting, object fails and ―Object failure‖ matrix signal is set. Also undefined-event is generated. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 209: Local/Remote Selection

    The selection of the L/R digital input is done in the ―Objects‖ menu of the VAMPSET software. NOTE! A password is not required for a remote control operation. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 210: Auto-Reclose Function (79)

    If the reclaim time runs out, the auto-reclose sequence is successfully executed and the AR function moves to ready - state and waits for a new AR request in shot 1. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 211 Reclaim time between different shots is defined by shot specific reclaim time settings. < 5.53 Reclaim time setting defines reclaim time between different shots during sequence and also reclaim time after manual closing. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 212 1 or skipping shots is not possible. AR request lines must be enabled to consecutive shots starting from shot 1. If AR sequence is not yet started, an AR request which is not enabled VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 213 CB will be controlled close immediately. AR info for mimic display setting (firmware version >= 4.95) When AR info is enabled, the local panel mimic display shows small info box during AR sequence. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 214 On; Off Indicates if this AR signal starts this shot On; Off Indicates if this AR signal starts this shot Start1 0.02 … 300.00 0.02 AR1 Start delay setting for this shot VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 215 Shot2 start counter Shot3 * Shot3 start counter Shot4 * Shot4 start counter Shot5 * Shot5 start counter *) There are 5 counters available for each one of the two AR signals. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 216 I> setting. 10. Reclaim time starts. After the reclaim time the AR sequence is successfully executed. The AR function moves to wait for a new AR request in shot 1. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 217: Logic Functions

    Maximum number of outputs is 20. Maximum number of input gates is 31. An input gate can include any number of inputs. For detailed information, please refer to the VAMPSET manual (VMV.EN0xx). VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 218: Communication

    VX003 cable is inserted. See Figure 6.1-1 and chapter 8. Figure 6.1-1. Communication ports and connectors. The type of connectors X9 or X10 depends on the type of the communication option (see chapter 8). VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 219: Local Port

    Physical interface The physical interface of this port is RS-232, but the connector type depends on the option module type. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 220 Clr = Clearing to zero is possible 1) The communication parameters are set in the protocol specific menus. For the local port command line interface the parameters are set in configuration menu. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 221: Remote Port X9

    TTL (for external converters only) Plastic fibre interface HFBR-0500 Not available RS-485 (isolated) screw crimp Glass fibre interface (62.5/125m) Plastic Rx/glass (62.5/125 m) Tx HFBR-0500/SMA fibre interface SMA/HFBR-0500 Glass (62.5/125m) Rx/plastic fibre interface VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 222 Clr = Clearing to zero is possible 1) The communication parameters are set in the protocol specific menus. For the local port command line interface the parameters are set in configuration menu. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 223: Extension Port

    Clr = Clearing to zero is possible 1) The communication parameters are set in the protocol specific menus. For the local port command line interface the parameters are set in configuration menu. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 224: Ethernet Port

    0.0.0.0 = no SNTP VS Port IP port for Vampset KeepAlive TCP keepalive interval nnnnnnnnnnnn MAC address Msg# Message counter Errors Error counter Tout Timeout counter Set = An editable parameter (password needed) VS_EtherConf VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 225: Communication Protocols

     Settings (SPA-bus and embedded SPA-bus only) 6.2.1. PC communication PC communication is using a VAMP specified command line interface. The VAMPSET program can communicate using the local RS-232 port or using ethernet interface. It is also possible to select SPA-bus protocol for the local port and configure the VAMPSET to embed the command line interface inside SPA- bus messages.
  • Page 226: Profibus Dp

    Device profile "Request mode" Using the request mode it is possible to read all the available data from the VAMP device and still use only a very short buffer for Profibus data transfer. The drawback is the slower overall speed of the data transfer and the need of increased data processing at the Profibus master as every data item must be separately requested by the master.
  • Page 227 4) If the value is "", Profibus protocol has not been selected or the device has not restarted after protocol change or there is a communication problem between the main CPU and the Profibus ASIC. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 228: Spa-Bus

    9600 (default) 19200 Emode Event numbering style. (Set) Channel Use this for new installations. (Limit60) (The other modes are for compatibility with old (NoLimit) systems.) Set = An editable parameter (password needed) VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 229: Iec 60870-5-103

    = 90. "Private range" function types are used for such data items, which are not defined by the standard (e.g. the status of the digital inputs and the control of the objects). VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 230 Technical description The function type and information number used in private range messages is configurable. This enables flexible interfacing to different master systems. For more information on IEC 60870-5-103 in Vamp devices refer to the ―IEC103 Interoperability List‖ document. Parameters Parameter...
  • Page 231: Dnp 3.0

    Application layer confirmation mode EvOnly (default) DBISup Double-bit input support No (default) SyncMode 0  65535 Clock synchronization request interval. 0 = only at boot Set = An editable parameter (password needed) VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 232: Iec 60870-5-101

    The IEC 60870-5-101 standard is derived from the IEC 60870-5 protocol standard definition. In Vamp devices, IEC 60870-5-101 communication protocol is available via menu selection. The Vamp unit works as a controlled outstation (slave) unit in unbalanced mode. Supported application functions include process data...
  • Page 233: External I/O (Modbus Rtu Master)

    Additional information can be obtained from the separate documents ―IEC 61850 conformance statement.pdf‖, ―IEC 61850 Protocol data.pdf‖ and ―Configuration of IEC 61850 interface.pdf‖ on our website. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 234 T Selector 0 – 64000 Transport selector IED Name String Identifcation of the device. Each device must have unique name. command Delete Send command to clear dynamic all dynamic datasets datasets VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 235: Ethernet/Ip

    / response), Class 3 connection (cyclic request / response) and Class 1 connection (cyclic IO messages containing assemblies‘ data) EtherNet/IP implementation on VAMP relay serves as a server and is not capable of initiating communication VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 236: Applications

    7.1. Subtransmission line protection In this application example VAMP 259 line managers are used in subtransmission application. Protected line is 110 kV and the length of the line is 40 km. In this example the line is protected with line differential and distance functions.
  • Page 237: Distributed Generation Application

    7.2 Distributed generation application 7.2. Distributed generation application In this application example VAMP 259 line managers are used in medium voltage application. Protected line is 20 kV and in the line is connected distributed generation. In this example the line is protected with line differential and distance functions.
  • Page 238: Medium Voltage Ring Network Protection

    All of the fault situations can be cleared with minimum operating time. Figure 7.3-1 VAMP Line protection devices used in ring network feeders with distributed generation. By using distance and linedifferential relays the back-up protection in the ring network can also be set to very fast and precise operation.
  • Page 239: Trip Circuit Supervision

    T5 … T8. These inputs are not sharing the common terminal with others inputs. 7.4.1. Internal parallel digital inputs In VAMP 259-3C7 and VAMP 259-3C8, the output relays T5 (DI29), T6(DI30), T7(DI31) and T8(DI32) have internal, parallel digital inputs available for trip circuit supervision. 7.4.2.
  • Page 240 R. The circuit-breaker is in the closed position. The supervised circuitry in this CB position is double-lined. The digital input is in active state when the trip circuit is complete. This is applicable for dry inputs DI7...DI20. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 241 Figure 7.4.2-3 An example of digital input DI7 configuration for trip circuit supervision with one dry digital input. Figure 7.4.2-4 An example of output matrix configuration for trip circuit supervision with one dry digital input. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 242 Select the next bigger standard size, for example 0.5 W. When the trip contacts are still closed and the CB is already open, the resistor has to withstand much higher power (Equation 7.4.2-3) for this short time. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 243 In this application using the other wet inputs for other purposes is not limited unlike, when using the dry inputs. Figure 7.4.2-5 Trip circuit supervision using one of the VAMP 200 series internally wetted digital input (DI1...DI6) and auxiliary relay K1 and an external resistor R.
  • Page 244 + 10 % = 121 V – 10 % = 96 V K1min = 20 k. K1coil = 4.8 mA K1min K1min K1coil = 6.1 mA K1max K1max K1coil /P = 242 . CBcoil VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 245 A 1 W resistor should be selected to withstand this short time peak power. However, if the trip relay can be closed for longer time than a few seconds, a 20 W resistor should be used. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 246: Trip Circuit Supervision With Two Digital Inputs

    Note: In many applications the optimum digital inputs for trip circuit supervision are the optional inputs DI19 and DI20 because they don't share their terminals with any other digital inputs. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 247 DI7...D20 only. Figure 7.4.3-2 Trip circuit supervision with two dry digital inputs. The CB is in the open position. The two digital inputs are now in series. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 248 Figure 7.4.3-4 An example of logic configuration for trip circuit supervision with two dry digital inputs DI7 and DI13. Figure 7.4.3-5 An example of output matrix configuration for trip circuit supervision with two dry digital inputs. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 249: Connections

    Connections 8.1. Rear panel view VAMP 259 is connected to the protected object through the following measuring and control connections: Figure 8.1-1 Connection on the rear panel of the VAMP 259-4C6 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 250 8.1 Rear panel view 8 Connections Technical description Figure 8.1-2 Connection on the rear panel of the VAMP 259-4C7 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 251 Technical description 8 Connections 8.1 Rear panel view Figure 8.1-3 Connection on the rear panel of the VAMP 259-4C8 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 252 Residual current I (S2) (S2) Phase to ground voltage U (S2) (S2) Phase to ground voltage U (S2) (S2) Phase to ground voltage U (S2) Usync (S2) Synchrocheck voltage input (S2) VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 253 Alarm relay 1, normal open connector A1 NC Alarm relay 1, normal closed connector Trip relay 2 Trip relay 2 Trip relay 1 Trip relay 1 Uaux Auxiliary voltage Uaux Auxiliary voltage VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 254 Trip relay 7/ Digital input 31 Trip relay 7/ Digital input 31 Trip relay 6/ Digital input 30 Trip relay 6/ Digital input 30 Trip relay 5/ Digital input 29 Trip relay 5/ Digital input 29 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 255 Digital input 19 DI20 Digital input 20 DI20 Digital input 20 S1>+ Arc sensor 1, positive connector * S1> Arc sensor 1, negative connector * *) Arc sensor itself is polarity free VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 256: Auxiliary Voltage

    ―logical communication ports‖ REMOTE, LOCAL and EXTENSION port are available for both modules (RS-232 signal levels). Depending on the module type one or more of these ports are physically available at the external connector. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 257 Figure 8.3-2 Internal connection to communication modules The internal connection of the communication modules contain the RX/TX signals from the communication ports, general output (UART_OUT), clock sync/general input (Sync.in) and OPTx_ID for module detection. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 258 The device has a 31mm high ―slot‖ for Communication option 1 and 18mm high ―slot‖ for Communication option 2. The option modules are either 31mm or 18mm high, the 18mm modules can be used either in the 31mm or 18mm slot. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 259: Pin Assignments Of Communication Options

    6= REM RX 7= LOC RX 8= EXT RX VCM 485-2 REMOTE, RS-485 3-pole screw 1= - LOCAL or connector (2-wire 2= + EXTENSION connection) 3= GND port selectable with a dip switch VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 260 VCM fiber REMOTE or Light, ST & Snap-in LOCAL switch for connectors selectable with echo/ no- a dip switch. echo and light/ no- light selection VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 261 Technical description 8 Connections 8.3 Serial communication connection Figure 8.3.1-1 VCM TTL− module‘s dip-switches Figure 8.3.1-2 VCM 485-2− module‘s dip-switches Figure 8.3.1-3 VCM 485-4− module‘s dip-switches Figure 8.3.1-4 VCM Fiber− module‘s dip-switches VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 262: Front Panel Connector

    NOTE! DSR must be connected to DTR to activate the front panel connector and disable the rear panel X4 RS232 port. (The other port in the same X4 connector will not be disabled.) VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 263: Optional Two Channel Arc Protection Card

    The binary output of the arc option card may be activated by the arc sensors or by any available signal in the output matrix. The binary output can be connected to an arc binary input of another VAMP protection device. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 264: Optional Digital I/O Card (Di19/Di20)

    For example trip circuit supervision is such application. The inputs are connected to terminals X6:1 – X6:2 and X6:3 – X6:4. Connections: X6:1 DI19+ X6:2 DI19- X6:3 DI20+ X6:4 DI20- X6:5 X6:6 X6:7 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 265: External I/O Extension Modules

    NOTE! If ExternalIO protocol is not selected to any communication port, VAMPSET doesn’t display the menus required for configuring the IO devices. After changing EXTENSION port protocol to ExternalIO, restart the device and read all settings with VAMPSET. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 266 Modbus register type Modbus register for the 1…9999 measurement 1…247 Modbus address of the I/O device C, F, K, mA, Ohm or Unit selection Active value On / Off Enabling for measurement VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 267 Modbus register for the 1…9999 measurement 1…247 Modbus address of the I/O device On / Off Enabling for measurement Analog input alarms have also matrix signals, ―Ext. Aix Alarm1‖ and ―Ext. Aix Alarm2‖. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 268 CoilS, InputS, Modbus register type InputR or HoldingR Modbus register for the 1…9999 measurement 1…247 Modbus address of the I/O device 0 / 1 Active state On / Off Enabling for measurement VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 269 External digital outputs configuration (VAMPSET only) Range Description Communication errors Modbus register for the 1…9999 measurement 1…247 Modbus address of the I/O device 0 / 1 Output state On / Off Enabling for measurement VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 270 ―Modbus Max‖ 0…42x108, -21…+21x108 Minimum limit for lined value, corresponding to ―Modbus Min‖ Link selection -21x107… Minimum & maximum output values …+21x107 Active value On / Off Enabling for measurement VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 271: Block Diagrams

    Technical description 8 Connections 8.7 Block diagrams 8.7. Block diagrams 8.7.1. VAMP 259-4C6 Figure 8.7.1-1 Block diagram of VAMP 259-4C6. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 272: Vamp 259-4C7

    8.7 Block diagrams 8 Connections Technical description 8.7.2. VAMP 259-4C7 Figure 8.7.2-1 Block diagram of VAMP 259-4C7 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 273: Vamp 259-4C8

    Technical description 8 Connections 8.7 Block diagrams 8.7.3. VAMP 259-4C8 Figure 8.7.3-1 Block diagram of VAMP 259-4C8 VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 274: Block Diagrams Of Option Modules

    Block diagrams of option modules 8.8.1. Optional arc protection Figure 8.8.1-1 Block diagram of optional arc protection module. 8.8.2. Optional DI19/DI20 Figure 8.8.2-1 Block diagram of optional DI19/DI20 module with one arc channel. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 275: Connection Examples

    Technical description 8 Connections 8.9 Connection examples 8.9. Connection examples Figure 8.9-1 Connection example of VAMP 259-3C7 without a synchrocheck function in use. The voltage measurement mode is set to ―3LN‖. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 276 8.9 Connection examples 8 Connections Technical description Figure 8.9-2 Connection example of VAMP 259-4C7 with a synchrocheck function from phase to phase voltage. The voltage measurement mode is set to ―3LN/LLy‖. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 277 Technical description 8 Connections 8.9 Connection examples Figure 8.9-3 Connection example of VAMP 259-4C7 with a synchrocheck function from phase to ground voltage. The voltage measurement mode is set to ―3LN/LNy‖. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 278: Technical Data

    - Continuous voltage withstand 250 V - Burden < 0.5V A Rated frequency f 45 – 65 Hz Terminal block: Maximum wire dimension: - Solid or stranded wire 4 mm (10-12 AWG) VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 279: Auxiliary Voltage

    Breaking capacity, DC (L/R=40ms) at 48 V dc: at 110 V dc: at 220 V dc Contact material AgNi 90/10 Terminal block: Maximum wire dimension: - Phoenix MVSTBW or equivalent 2.5 mm (13-14 AWG) VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 280: Alarm Contacts

    ProfiBus DP (option, with external module) DNP 3.0 9.1.8. Ethernet connection Number of ports Electrical connection Ethernet RJ-45 (Ethernet 10-Base-T) Protocols VAMPSET Modbus TCP IEC 61850 Data transfer rate 10 Mb/s VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 281: Arc Protection Interface (Option)

    20 periods in X-, Y- and Z axis direction Shock (IEC 60255-21-1) half sine, acceleration 5 g, duration 11 ms Class I 3 shocks in X-, Y- and Z axis direction VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 282: Environmental Conditions

    *) EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse MI= Moderately Inverse **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 283 ±2% of set value or ±0.5% of the rated value - operating time ±1% or ±150 ms NOTE! Stage Blocking is functional when all phase currents are below the block limit. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 284 - Operate time ±1% or ±30 ms **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 285 0.5 V. Angle memory is active for maximym of 500 ms. So if the tripping time of zones is more than 0.5 s, there won’t be trip. Direction checkin of angle memory function is based on U1. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 286: Directional Current Protection

    - Operate time at definite time function ±1% or ±30 ms **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 287: Voltage Protection

    **) The measurement range is up to 160 V. This limits the maximum usable setting when rated VT secondary is more than 100 V. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 288: Frequency Protection

    **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 289: Power Protection

    - Operating time at definite time function ±1 % or ±150 ms NOTE! When pick-up setting is +1 … +200% an internal block will be activated if max. voltage of all phases drops below 5% of rated. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 290: Synchrocheck Function

    <95 ms Inaccuracy - Operating time ±20 ms **) This is the instantaneous time i.e. the minimum total operational time including the fault detection time and operation time of the trip contacts. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 291: Arc Fault Protection Stages (Option)

    Reset time (Delayed ARC L) <120 ms Reset time (BO) <85 ms Reset ratio 0.90 Inaccuracy: - Starting 10% of the set value - Operating time ±5 ms - Delayed ARC light ±10 ms VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 292: Supporting Functions

    Reset time <60 ms Reset ratio 3% of the pick-up value Inaccuracy: - Activation U2> ±1%-unit - Activation I2< ±1%-unit - Operating time at definite time function ±1% or ±30 ms VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 293: Voltage Sag & Swell

    Voltage low limit (U1) 10 – 120 % Definite time function: - Operating time <60 ms (Fixed) Reset time <60 ms Reset ratio: 1.03 Inaccuracy: - Activation 3% of the set value VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 294: Abbreviations And Symbols

    Data terminal ready. An RS232 signal. Output and always true (+8 Vdc) in front panel port of VAMP devices. Fast Fourier transform. Algorithm to convert time domain signals to frequency domain or to phasors.
  • Page 295 Calculated phase to phase voltage U Calculated phase to phase voltage U Voltage transformer i.e. potential transformer PT Nominal primary value of voltage transformer Nominal secondary value of voltage transformer World wide web  internet VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 296: Constructions

    Technical description 11 Constructions Constructions VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 297: Order Information

    12 Order information Technical description Order information When ordering, please state:  Type designation: VAMP 259  Quantity:  Options (see respective ordering code): VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 298: Technical Description

    VCM FIBRE PG Serial fibre interface (Plastic/Glass) VCM FIBRE GP Serial fibre interface (Glass/Plastic) VCM 232 RS 232 w ith RJ45 connector VCM RTD RTD interface (Glass fibre) VCM TTL TTL/RS-232 interface VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 299: Revision History

    New text and pictures of Trip circuit supervision added. Earth-fault distance protection Ze< (21N) Added. VAMP 257 / 259 order codes are modified to support inbuilt Ethernet and IEC 61850. Line differential protection LdI > (87) added. VM259.EN004 From this version onwards, the manual does not applied to VAMP 257 anymore.
  • Page 300 Support for SNTP version 4. 10.19 VIO12 RTD module support added. 10.26 VCM RTD option module support added. IEC 61850 updates including GOOSE added. UTF-8 support for local HMI panel (Russian) added. VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 301 Double earth fault blocking first version added. I> and I > - I >>>> -stages with faster operation time. Harmonic driver to 10ms priority. I0CALC driver to 10ms priority. Logic outputs to GOOSE. VM259.EN007 VAMP 24h support phone +358 (0)20 753 3264...
  • Page 302: Reference Information

    VAMP Ltd. P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205 URL: http://www.vamp.fi 24h support: Tel. +358 (0)20 753 3264 Email: vampsupport@vamp.fi VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007...
  • Page 303 VM259.EN007...
  • Page 304 We reserve the right to changes without prior notice VAMP Ltd. Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 P.O.Box 810, FIN 65101 Vaasa, Internet: www.vamp.fi Finland Email: vamp@vamp.fi VM259.EN007...

Table of Contents