Unitek Classic Q3x/x-240-840A Series Manual

4 quadrant thyristor drive

Advertisement

Quick Links

Part 1
Thyristor Drive
Part 2
Analogue Control Electronics
Hans-Paul-Kaysser-Straße 1
71397 Leutenbach – Nellmersbach
Tel.: 07195 / 92 83 – 0
Fax: 07195 / 92 83 - 129
info@unitek-online.de
www.unitek-online.de
M A N U A L
Classic Q3 240-840A
4 Quadrant
Thyristor Drive
Industrie Elektronik
G m b H
Q3x/x-240-840A
REGx
Ausgabe / Version
01/2014
V 01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Classic Q3x/x-240-840A Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Unitek Classic Q3x/x-240-840A Series

  • Page 1 Part 2 Analogue Control Electronics REGx Industrie Elektronik G m b H Hans-Paul-Kaysser-Straße 1 71397 Leutenbach – Nellmersbach Ausgabe / Version Tel.: 07195 / 92 83 – 0 Fax: 07195 / 92 83 - 129 01/2014 V 01 info@unitek-online.de www.unitek-online.de...
  • Page 2: Table Of Contents

    Basic - Information 1 Inhaltsverzeichnis Basic - Information ......................2 Safety advice ........................2 Standards and guidelines: ....................2 General and features ......................4 Technical Data ........................6 Specifiation ......................... 8 Interface ..........................8 Mechanical installation ....................9 Mounting ..........................9 Dimensions Q3 240-360A ....................
  • Page 3: Basic - Information

    Basic - Information 2 Basic - Information Safety advice Electronic equipment is not fault proof. Attention – High voltage 360-550V~, 450-550V= Shock hazard / Danger of life!! Before installation or commissioning begins, this manual must be thoroughly read and understood by the technical staff involved. The devices are electrical equipment (EB) to the power electronics for the control of power flow in electrical power systems.
  • Page 4 Basic - Information The user must ensure that in the event of: - device failure - incorrect operation - loss of regulation or control the axis will be safely de-activated. It must be ensured that the machines, equipment or vehicles are fitted with device independent monitoring and safety feature.
  • Page 5: General And Features

    Basic - Information General and features This manual describes the basic unit and is only in connection with the manual of the control electronics (e.g. REGxx) valid. Manual use in connection with: - an analogue control REGxx - field regulation internal QS-F - field regulation external F2xx...
  • Page 6 Basic - Information Characteristics Series Classic Q3 Thyristor drive for dc motors Power range 6.75kW to 1.1MW Drive and brake in all 4 quadrants Energy recovery Intrinsically safe power section Fast analogue current control Temperature watchdog - power section Circular current-free dual bridge circuit Controlled or uncontrolled field rectifier 26-pin interface Features of the control electronics:...
  • Page 7: Technical Data

    Basic - Information Technical Data Q3 400/450-x Power connection 360 … 440V~ Auxiliary voltage connection 360 … 440V~, 200 … 250V~ or option Output voltage max. ± 450V= Cooling ventilation fan Q3 400/450- Input current Output current - peak 5s - continuous El.
  • Page 8 Basic - Information Q3 400/450-x Power connection 360 … 440V~ Auxiliary voltage connection 360 … 440V~, 200 … 250V~ or option Output voltage max. ± 450V= Cooling ventilation fan Q3 400/450- Input current Output current - peak 5s 1680 - continuous El.
  • Page 9: Specifiation

    Basic - Information Specifiation Specification Mains frequency 50 or 60Hz ±5% Protection rating IP 00 Format VDE 0100 group C, VDE 0160 Humidity rating class F acc. to DIN 40040 Site of installation < 1000m above sea level Operating temperature range 0 ...
  • Page 10: Mechanical Installation

    Mechanical installation 3 Mechanical installation Mounting Q3-Montage-V616 Ambient temperature 0 to <45°C (reduced, up to 60°C) Max. cooling unit-temperature 80°C Air-mass throughput 240A 600m³h 360A 600m³h 480A 696³h 840A 800m³h Dissipation loss with max. power Unit Q3-x/X Unit W Mains choke W 1000 1440 1890...
  • Page 11: Dimensions Q3 240-360A

    Mechanical installation Dimensions Q3 240-360A E-Q3-M022-Maßbild240 Q3 240-840A...
  • Page 12: Dimensions Q3 840A

    Mechanical installation Dimensions Q3 840A E-Q3-M657-Maßbild840 Dimensions Unit Q3-x/x Width Height Depth Drill hole Weight 275 x 490 275 x 490 375 x 540 375 x 540 486.5 375 x 540 40.8 Q3 240-840A...
  • Page 13: Three-Phase Power-Choke

    Mechanical installation Three-phase power-choke Features 400V~50/60Hz Protection IP00 rating Isolation class T40/E Vertical angle bracket Q3-V257-UID-Trafo und Q3-V256-UI-Trafo Q3-x/x- Choke type L m H PV W Dimension Weight Screw KD5-250 0.12 31.5 K170-400 0.08 KU150-600 0.06 KU150-600 0.06 KU150-800 0.04 Q3 240-840A...
  • Page 14: Electrical Installation

    Electrical installation 4 Electrical installation Connections E-Q3-647 Q3-Relais-1V647 E-Q3-Schaltfolge-1-V647 Q3 240-840A...
  • Page 15: Connection Diagram

    Electrical installation Connection diagram E-Q3A019 Q3 240-840A...
  • Page 16: Ce-Advice

    Electrical installation CE-Advice The devices adhere to the EU guidelines 89/336/EWG and the technical standards EN 61000-2 and 61000-4 provided that the following conditions are observed: - The device, transformer and filter capacitors are mounted on a 800x800x2mm mounting plate - The mounting plate must be connected to ground using a 10mm²...
  • Page 17: Connection Advice

    Electrical installation Connection advice Attention: The order of the connections to the connector numbers or screw terminals is obligatory. All further advice is non-obligatory. The input and output conductors may be altered or supplemented in accordance with the electrical standards. Note: - Connection and operating instructions - Local regulations...
  • Page 18: Power Connection

    Electrical installation Power connection Direct power connection Line protection Phase Bolt X10:16 Phase Bolt X10:15 Phase Bolt X10:14 Power choke Note: L1, L2, L3 – clockwise rotating field Protecting earth – PE connection Unit Q3 x/x- Power choke Fuses A Type current KD-three-phase current Superfast acting...
  • Page 19: Option

    Electrical installation Option Option - External synchronization For special applications it might be necessary to tap the synchronization before the power commutating choke, e.g. - when operating via field triggering circuit - in case of an instable power supply When changing to external synchronization, the 3 resistors 0W (R15, R34, and R40) on the board ‘Q3 - on3’...
  • Page 20: Motor-Connection

    Electrical installation Motor-connection Positive command value Motor – bolt X10:13 Motor + bolt X10:10 Attention: Amature choke only for a few applications: Inductance: L [mH] = U x 0,8 Standard version without a choke Q3-Motor-V647-1 Motor lines have to be shielded Unit Q3 x/x- Power choke* Min.
  • Page 21: Field-Connection

    Electrical installation Field-connection Constant field Connection Plug-in terminal connectors Input X5:20, X5:21 Field negative X5:22 Field positive X5:23 Signal contact X5:24, X5:25 Field voltage Power supply Field supply 230V~ 210V= 400V~ 360V= variable 0.9 x transformer secondary voltage with auto-transformer Field current max.
  • Page 22: Actual Value

    Ground referenced actual value Fuses 2x 0.1A directly in the armature circuit For armature voltage >180V= additional resistors are required Use unit UNITEK EXZU-UA1 Note: Observe Manual REG Option: In case of internal potential-free armature voltage controL please indicate on order. Q3 240-840A...
  • Page 23: Adjustments

    Adjustments 5 Adjustments Components E-Q3-B628 Variable elements Function Range P-amplification current controller 1 18kΩ to 470kΩ P-amplification current controller 2 18kΩ to 470kΩ Exact adjustment current limit 100kΩ to 470kΩ R101 Trigger angle control 240kΩ to 560kΩ R125 Field current Integral term - current controller 1 0.1µF to 2.2µF Integral term - current controller 2...
  • Page 24: Circuit Diagram

    Adjustments Circuit diagram E-Q3-S654 Q3 240-840A...
  • Page 25: Current Controller

    Adjustments Current controller Current controller – PI loop circuit Bridge 1 negative R14, C80 Bridge 2 positive R33, C81 Q3-Strom-PI-pos-V647-1 Q3-Strom-P1-1-V647 Basic set-up Amplification ~0.4 Integration time ~18ms Changing the amplification 18��Ω �� ��14 18��Ω �� ��33 Bridge 1 Bridge 2 18��Ω...
  • Page 26 Adjustments Optimization of the current controller - Connect an oscilloscope across the current actual value X3:21 - Current command value step-change ±1V X3:16 - Increase the current command value by 1V steps to ±10V - Alter the P-amplification by means of the resistors R14 and R33 - Optimal adjustment fig.
  • Page 27: Displays

    Adjustments Displays BTB signal - Drive ready BTB signal X3:25 >+5V Error X3:25 <+5V Error Voltage error 24V, 15V, 5V saved Phase error, rotating field saved Defective input fuse saved Over-temperature saved In case of errors or failure the power section is immediately internally disabled without delay. To clear the saved error re-enable the drive (switch off/on or reset key) Measurements Measurement advice...
  • Page 28: Commissioning

    Commissioning Commissioning Commissioning Q3 x/x-x with REG4 Check the following connections before commissioning Observe the type plate! Basic connection - power connections Q3 Power supply power bolts X10:14, X10:15, X10:16 Power supply auxiliary voltage terminals X5:17, X5:18 Power supply field terminals X5:20, X5:21 Motor connection A1/A2...
  • Page 29 Commissioning Enable off Command value 0V Switch on the power Check the auxsiliary voltages -terminal X1:3 = >20V LED 7 bright -terminal X1:5 = +10V -terminal X1:7 = -10V Power supply of > check fuses FE1, FE2 LED 3 bright -Power supply off LED 6 dark -Check the tacho connection...
  • Page 30: Protocol Q3 X/X-X With Regxx

    Commissioning Protocol Q3 x/x-x with REGxx Customer Machine no. Device Serial no. Control voltage [V~] Power supply voltage [V~] Field voltage [V=] Inputs Enable Contact? Voltage [V=] Command value Type Voltage [V=] Command value, additional Type Voltage [V=] Current command value Voltage [V=] max1 external Current command value...
  • Page 31 Commissioning Current controller adjustments Current controller settings P-amplification R14=…. R13=…. I-term C80=…. C81=…. 50/60 Hz Jumper SW1 Pos. 1-2 (50Hz) Pos. 2-3 (60Hz) Measured data Armature voltage max. [V=] Armature current peak [A=] Armature current continuous [A=] Tacho voltage max. [V=] Acceleration X4:16...
  • Page 32: Fauls

    Fauls 7 Fauls Fauls Switch of Power Voltaqges applying across X10: 14, 15, 16 Check the pre-fuse and X5: 17, 18 the contactor circuit X5: 20, 21 Fuses FE1 and FE2 defective All LEDs dark Power section defective Internal short-circuit Check the tacho / tacho connection LED3 dark For armature voltage control check...
  • Page 33: Error Diagnosis

    Fauls Error diagnosis Error diagnosis Malfunction Causes -Wrong power supply and motor connections Motor does not run -Activated fuses -Missing enable or command value -Current limit too low -Missing BTB -Wrong polarity of the actual value (Tacho armature voltage) -Values of the tacho switch S9 too low Motor speeds up -Command value too high For armature voltage control...
  • Page 34: Warranty

    UNITEK undertakes no warranties for devices which have been modified for special applications. During the warranty period, UNITEK will, at its option, either repair or replace products that prove to be defective, this includes guaranteed functional attributes. UNITEK specifically disclaims the implied warranties or merchantability and fitness for a particular purpose.