Vexve AUTOMIX 10 Mounting And Operating Instructions

Advertisement

Quick Links

AUTOMIX 10 (EN) 0508
AUTOMIX 10
MOUNTING AND OPERATING INSTRUCTIONS

GENERAL FUNCTIONS

AUTOMIX 10 is an advanced electronic temperature control for hydronic radiator and radiant floor
heating systems. It can easily be integrated into an existing heating system. The main supply and all
sensors have plug-in connections. The quick do-it-your-self installation saves on labor charges.
AUTOMIX 10 works continuously and proportionally. Through impulses from the sensors the controller
directs the motor to keep the valve plug in the position that corresponds to the actual heat requirement
of the house.
DELIVERY PARTS OF ART.NO 1210
1. Valve motor AUTOMIX 10 with built-in electronics and mounting kit
2. Adapter 230/18 VAC 200 mA with 1,7 m wire
3. Supply water sensor T1 with 1 m wire
4. Outdoor sensor T2 with 15 m wire
5. Room sensor AUTOMIX 10RB with 15 m wire, art.no 1211
AUTOMIX 10RB should be installed if the room temperature of the house fluctuates because the building is
affected by e.g. sunlight or wind. With AUTOMIX 10 RB the room temperature can be set between 12° C and
27° C.
6. Remote control AUTOMIX 10RC with 15 m wire, art.no 1212
Remote control AUTOMIX 10RC is designed for floor heating systems. The remote control provides a
convenient way to adjust the supply water temperature without going to the boiler room.

MOUNTING

Supply water sensor T1
Supply water sensor T1 is fastened to a non-insulated part of the supply pipe after the mixing valve.
For optimum temperature measuring the pipe and sensor have to be insulated afterwards.
Outdoor sensor T2
Outdoor sensor T2 is to be mounted on the north or northwestern outside wall at least 3 metres above
ground. The outdoor sensor must never be mounted above a window or near an air valve as this
would influence the sensor.
Room sensor AUTOMIX 10RB
Room sensor AUTOMIX 10RB is mounted at a place with an average temperature of the house. The room
sensor should not be placed where it can be affected by direct sunlight, heat radiation or draught. Radiators
with a thermostatic valve in the same room as the room sensor must be max. opened to obtain a correct
temperature control.
Remote control AUTOMIX 10RC
Remote control AUTOMIX 10RC is mounted at a convenient place for operating.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AUTOMIX 10 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vexve AUTOMIX 10

  • Page 1 5. Room sensor AUTOMIX 10RB with 15 m wire, art.no 1211 AUTOMIX 10RB should be installed if the room temperature of the house fluctuates because the building is affected by e.g. sunlight or wind. With AUTOMIX 10 RB the room temperature can be set between 12° C and 27° C.
  • Page 2 AUTOMIX 10 (EN) 0508 VALVE MOTOR AUTOMIX 10 Turn the spindle of valve A counter clockwise to the end position (open or closed). Remove the knob/handle without changing the position of the spindle. Screw the anti-rotation stop B into a convenient hole on the valve (if necessary remove an existing screw).
  • Page 3 AUTOMIX 10 (EN) 0508 WIRING AUTOMIX 10 is delivered with wires. The main supply and all sensors have plug-in connections. The quick do-it-your-self installation minimizes installation problems. Left side of motor A. Adapter B. Supply water sensor T1 18 V Right side of motor C.
  • Page 4 AUTOMIX 10 (EN) 0508 GRAPH SETTING The regulating graph for a certain house is dependent on dimensions, location, insulation etc. Therefore it is not possible to decide on a graph in advance. It has to be tried out. The graph is set with knobs D and F. The knobs work steplessly.
  • Page 5 AUTOMIX 10 (EN) 0508 SETTING MIN. AND MAX. SUPPLY WATER TEMPERATURE Min. supply water temperature can be set between 15°C – 35°C and max. supply water temperature between 40°C – 90°C. When min. supply water temperature is set to 30° C or below, the max.
  • Page 6 AUTOMIX 10 (EN) 0508 OPTIONALS AUTOMIX 10RB is a room sensor for measuring and setting the temperature inside the house. AUTOMIX 10RB should be installed if the room temperature fluctuates because the building is affected by sunlight or wind. A green LED indicates that power is on. When the motor runs, the LED dims slightly.

This manual is also suitable for:

Am10