Technibel CAFM1V Series Technical Data Manual page 30

Mini multiset v.r.f. dc inverter r410a, outdoor units
Table of Contents

Advertisement

2. System Design
Dimensions
Type with flare nut at each end
A
Insulator
(divided in 2)
Note: Install the service port so that it faces the extension side.
Ball Valve Installation (for refrigerant R410A only)
Check the size of the ball valve set you separately purchased.
Model name
BV-RXP56AG
ø6.35 • ø12.7
BV-RXP160AG
ø9.52 • ø15.88
1. Installing the ball valve
(1) If the ball valve is to be installed for indoor unit
extension, or near an indoor unit, install it so that
the service port faces the indoor unit side.
(This facilitates indoor unit leak testing and vacu-
um procedures.)
Install the ball valve as close as possible to the
distribution joint.
This ball valve is for use
CAUTION
only in systems that utilize
refrigerant R410A. The ser-
vice port connection size is
ø7.94. The face-to-face dis-
tance between the ø12.7 or
ø15.88 flare nuts is 26 mm
or 29 mm, respectively.
Be sure to use only the
supplied flare nuts. Be
careful to use the correct
tools and materials.
2. Flare nut tightening
The flare nut on the service port side is fully tight-
ened. Recommended tightening torque is
(8~10 N·m).
If the valve is used for extension, it can be used
as-is. In all other cases, use 2 monkey wrenches
in combination to loosen the flare nut.
Figure
E
D
Service port
Size
2 - 23
Design of Mini Multiset
Dimensions
Size
ø6.35 (1/4")
ø9.52 (3/8")
ø12.7 (1/2")
ø15.88 (5/8")
108
Outdoor unit
Ball valve
Service
port
Indoor unit
Valve cap
Tightening torque (19~21 N
Fully tightened (this side only)
Service port
Tightening torque (8~10 N
Unit: mm
B
C
D
E
A
72
42
54
16
44
76
42
54
16
44
89
42
58
20
51
51
68
22
56
Indoor
Outdoor
Indoor unit extension
m)
Plug
m)
(this side only)
2