This operating manual should be read through carefully before installing and operating this AC power distribution panel. DPAC1UT-AB-I-2-590 only 1.75 inches (1 rack space) high to minimize rack space and can be mounted in either a 19- or 23-inch relay rack with corresponding brackets. It can be mounted from the front of the rack with offsets every ¼-inch from front to back to align...
Page 4
DPAC1UT-AB-I-2-590 OPERATING MANUAL The AC input/output connections are provided on the back of the 1U panel with a single 10 position terminal block on each side A and B, see Figure 3 below. Figure 3 - Rear View Figure 4 below is a schematic for the internal wiring while figure 5 is for the external wiring.
Page 5
DPAC1UT-AB-I-2-590 OPERATING MANUAL A - SIDE B - SIDE LOAD LOAD 12 AWG Figure 5 - External Wiring The input terminals on each side are marked G, N, L1 & L2 and are supplied by a single phase 120/240VAC source. The input current rating is 25A for each side. N, L1 & L2 terminals of the A side are paralleled with the B side as shown in the external wiring schematic, figure 5 and rear view photo, figure 3, with #12AWG wire.
God, negligence or the failure of customer to fully follow instructions with respect to installation, application or maintenance. For a complete text of UNIPOWER’s warranty conditions please request a copy from your local Sales Office.
Also save the shipping carton and packing materials as evidence of damage for the freight carrier’s inspection. UNIPOWER will cooperate fully in case of any shipping damage investigation. Always save the packing materials for later use in shipping the unit. Never ship the distribution panel without proper packing.
US +1 954 346 2442 UK +44 (0)1903 768200 This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.