Summary of Contents for Gicam WIN6

  • Page 1 Manuale Manual Handbuch...
  • Page 2 Manuale d’istallazione e d’uso Installation and user manual Installations- und Bedienungsanleitung LIMITATORE di carico load LIMITER LASTBEGRENZER...
  • Page 3: Table Of Contents

    Sommario / Table of contents / Inhaltsverzeichnis Sommario / Table of contents / Inhaltsverzeichnis ..............1 Installation manual ........................3 Technical specification ........................... 3 Symbology ..............................4 Warnings ................................ 4 Identification plate of the instrument ......................4 Power supply of the instrument ........................5 Connection of the load cells ...........................
  • Page 4 Analog output operation mode ......................19 Test analogue output ..........................19 Range analogue output ........................19 Offset adjustment (calibration) ......................19 Limit values ............................... 19 Output configuration ............................. 20 Set point programming ......................... 20 Excitation delay ............................. 20 Programming polarity of intervention of the logic output 3 ..............20 Serial protocol ..............................
  • Page 5: Installation Manual

    Installation manual Technical specification Board power supply 12 – 24 V ac ± 15 % Power consumption Insulation Class III Storage temperature - 20 °C / + 60 °C (-4 °F / 140 °F) Operating temperature - 10 °C / + 50 °C (14 °F / 122 °F) Humidity Max.
  • Page 6: Symbology

    Symbology Attention! This operation has to be carried out by specialized personnel.  Pay particular attention to the following indications! Further information Warnings  The procedures listed below have to be executed by specialized operators!  All connections have to be executed with the instrument shut off! Identification plate of the instrument ...
  • Page 7: Power Supply Of The Instrument

    Power supply of the instrument  The instrument is powered via terminals 14 and 15.  The power cable must be routed separately from other power cables with different voltages, load cell cables and logic inputs / outputs. Supply voltage: 12 – 24 V ca ± 15%, 4 VA Terminal board connection: 14 –...
  • Page 8: Connection Logical Input

    Connection logical input The logic input is isolated from the instrument through an optocoupler.  The connection cable of the logic input must not be channeled with power or power cables  Use a connection cable as short as possible (no longer than 5 meters). If a longer length is required, use a relay relay.
  • Page 9: Serial Rs232 Connection

    Serial RS232 connection  To make the serial connection, use a shielded cable, taking care to connect the screen to ground at only one of the two ends. If the cable has more conductors than those used, con- nect the free wires to the screen. ...
  • Page 10: Connection Summary

    Connection summary Number 6-point terminal block Number 18-point terminal block Power supply cells - RS232 TX Power supply cells + RS232 RX Reference + RS232 ground Reference - RS485 TX/RX + Signal - RS485 TX/RX - Signal + Input dry contact Input dry contact + Power supply - Power supply...
  • Page 11 In the case of connection to two RS422 pairs and two nodes, the resistors are placed near the farthest receiver and the value can go down to 120 Ohm (figure on the side). n the case of connection to two RS422 but multi-node pairs, the same 120 Ohm value is indicated in the figure opposite,...
  • Page 12 Pagina – page – Seite...
  • Page 13: User Manual

    User manual Main characteristics of use The main operating characteristics are:  Weight control detected by alarm and pre-alarm thresholds  Alarm due to cell failure or power failure Display signals The weight of the scale is normally displayed on the 6-digit display. According to the various programming procedures, the display is used for programming the parameters to be inserted in the memory, ie messages indicating the type of operation being carried out and therefore helping the operator in the management and programming of the instrument.
  • Page 14: Use Of The Keyboard

    Use of the keyboard The instrument is programmed and controlled through the keypad consisting of 4 keys, all with multiple func- tions. The instrument, according to the operation in progress, automatically stabilizes the selection of one of the key functions. Function S4 + S1 (Long press) Access to the set points programming menu...
  • Page 15: Input And Output

    Input and output Input Reset displayed value (auto tare) Output Set-point output 1 positive intervention Set-point output 2 positive intervention Set-point output 2 positive or negative intervention The relays are normally energized. When a set point is exceeded, the relative relay de-energizes. When a set point has a value of zero, its output is always de-energized.
  • Page 16: Calibration Data Menu

    Calibration data menu Weighing system capacity Set the value corresponding to the sum of the nominal capacities of the load cells, CAPAC in kg. This data constitutes the full scale value of the weighing system. Values between 1 and 60,000 kg are accepted. After a change, the set points are reset. Password protected setting.
  • Page 17: Weight Calibration And Linearization

    Weight calibration and linearization During the calibration phase, the display shows the weight intermittently with the word "CAL". During the linearization phase the display shows the weight intermittently with the wording "LIN n" where in- stead of n there is the number of the point to be set (from 1 to 9). Zero calibration Carry out the operation with the scales unloaded but complete with the tare weight, with stabilized weight.
  • Page 18: Weighing Parameters Setting Menu

    Weighing parameters setting menu Weight filter This parameter adjusts the action of the digital filter applied to the detected weight. FIltEr If a low value is programmed the filter action is lower, by programming a high value the weight is more filtered (minimum value 0, standard value 5, max value 9). In the first case, a faster response of weight variations is obtained.
  • Page 19: Weighing Parameters Setting Menu

    Weighing parameters setting menu Autozero at power up This parameter is the maximum weight zeroed at power up. The auto-zero func- Auto 0 tion consists in carrying out an automatic zero calibration when the instrument is switched on, only if the detected weight stabilizes within the set threshold. To disable the function, set the value 0.
  • Page 20: Analog Output Set-Up And Test Menu (Optional)

    Analog output set-up and test menu (optional) Pagina – page – Seite...
  • Page 21: Full Scale Analog Output

    Full scale analog output The weight corresponding to the full scale of the analogue output, which may be F-SCAL different from the weight of the weighing system. Analog output operation mode Selection of the transmitted value by the analogue output. ModE nEt GroSS (The analogue output assumes the value corresponding to the net weight / gross weight)
  • Page 22: Output Configuration

    Output configuration Set point programming SEt 1 The set threshold values are compared with the weight to drive the relative relay. SEt 2  If the value of the threshold in memory is 0, the relative relay is always de-energized. In this way the instrument can only be used with a weight lower than a set threshold.
  • Page 23: Serial Protocol

    Serial protocol Continuous transmission protocol This protocol is used for continuous transmission, usually towards the repeater panel. COMMUNICATION PARAMETERS ARE SELECTABLE (see serial menu on page 39) STRING TRANSMITTED AT A FREQUENCY OF 10 Hz: STX <state> <net> ETX <csum> EOT <state>...
  • Page 24: Troubleshooting Guide

    Troubleshooting Guide Problem Possible cause Solution The threshold control does not The thresholds have not been set Set the threshold values by follow- work ing the relevant instructions The instrument checks the thresh- Parameters for the threshold con- Make sure that they are set accord- olds incorrectly trol have not been set ing to the desired modes...
  • Page 25 Pagina – page – Seite...
  • Page 26 Pagina – page – Seite...
  • Page 27 La versione più aggiornato di questo materiale è disponibile sul nostro sito: www.gricamgra.com The latest version of this manual can be downloaded from our website: www.gicamloadcells.com Die neueste Version dieses Handbuches finden Sie auf: www.gicamwaegesystemwiegezellen.com...