D e m a n d M o o r e R e l i a b i l i t y NET Concentrator System ® Ethernet and MODBUS Interface Module User’s Manual All product names are registered trademarks of their respective companies. - 1 - Moore Industries-International, Inc. www.miinet.com...
Page 2
We perform a sequence of stringent quality assurance checks on every unit we ship. If any Moore Industries product fails to perform up to rated specifications, call us for help. Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide timely, accurate, and practical answers to your process instrumentation questions.
Specific Conditions of Use ..................89 Appendix A Transition from Legacy NCS Devices .......... 90 Appendix B MODBUS Registers ............... 92 Appendix C MODBUS Integer Support ............. 99 Warranty Information and Return Procedures ..........103 - 3 - Moore Industries-International, Inc. www.miinet.com...
Power Module (CPM). Each Interface module can Introduction support a total of 16 I/O modules. Two CPMs would This is the user’s manual for the Moore Industries be required to supply power to 16 modules. NET Concentrator System (NCS), a modular family...
Page 5
I/O modules. For in-depth information regarding each of the Interface Modules’ unique features refer to the corresponding Interface Modules’ user’s manual. - 5 - Moore Industries-International, Inc. www.miinet.com...
Page 6
ICS Triplex ISaGRAF control software (available from Moore Industries). MODBUS RTU Peer-to-Peer Systems are configured via the EMM Interface Module internal Internet Explorer Web browser or using the Moore Industries software package called NCS Config. - 6 - www.miinet.com...
Page 7
® NET Concentrator System Ethernet and MODBUS Interface Module This Section Contains the following: EMM Interface Module EMM Specifications EMM Dimensions EMM Terminal Designations - 7 - Moore Industries-International, Inc. www.miinet.com...
Page 8
First In, First Out (FIFO) buffer in RAM. The most recent 18,000 samples are stored in battery-backed RAM. The data log ® ® is accessible as a .csv file (Microsoft Excel compatible) via the Ethernet interface. - 8 - www.miinet.com Moore Industries-International, Inc.
Page 9
(MODBUS/TCP or OPC Compatible) Additional Stations MODBUS RTU HOST Third-Party MODBUS Device or System (MODBUS Slave Device) EMM Station (MODBUS Slave Device) DCS, PLC or PC with HMI/SCADA Module Module Module Number Number Number - 9 - Moore Industries-International, Inc. www.miinet.com...
Transmit activity on type and add times for each MODBUS 1 occurs; I/O module connected to Weight 612 g (21.6 oz) Off when no Transmit activity the EMM) on MODBUS 1; RX1: Green blinks when - 10 - www.miinet.com Moore Industries-International, Inc.
Page 11
Shield 2 Ethernet Ethernet RJ-45 Input Connection USB connection (reserved for future use) NOTES: 1. Terminal blocks can accommodate 14-22 AWG solid wiring. 2. Your input power requirement will depend upon your unit’s configuration. - 11 - Moore Industries-International, Inc. www.miinet.com...
This Section Contains the following: NCS System Configuration Configuring Ethernet Settings Interface Module Web Server PC Configuration Program Configuring MODBUS Ports Data Logger Security User Accounts Configuring System Time ISaGRAF Control Engine Upgrading Firmware and Web pages - 12 - www.miinet.com Moore Industries-International, Inc.
Page 13
Note that the new settings do not appear in the NAC utility list window. To view the new network settings, click Find All in the NAC utility after the system is rebooted. - 13 - Moore Industries-International, Inc. www.miinet.com...
Page 14
However, the default Guest account does not have FTP access so only the root account (default password of password) can successfully connect using FTP. - 14 - www.miinet.com Moore Industries-International, Inc.
Page 15
File Download 4. Interface Module–The Interface Module page pop-up window. includes a number of selections that provide all the necessary options for setting the system parameters of the Interface Module. - 15 - Moore Industries-International, Inc. www.miinet.com...
Page 16
Interface Module program, modify passwords, and read or write using a FTP program. 7. Logout–Logging Out ends your session. 8. Help–Connects you to the help system. - 16 - www.miinet.com Moore Industries-International, Inc.
Page 17
Module, or select it from the list (if you have previously Refer to Table 1 for the equipment needed. entered it). 1. Insert the Moore Industries Interface Solution 4. Select “OK” from the Attempting Connection screen Configuration Tools CD into the CD drive of the once the connection has been made.
Page 18
MODBUS Settings The controls in the lower portion of the screen are used to configure the MODBUS settings. Refer to the MODBUS Configuration section for more information. Configuration Figure 2. Interface Module Settings Screen - 18 - www.miinet.com Moore Industries-International, Inc.
Page 19
When enabling Trimming or Custom Curve settings in a channel, check the appropriate box in the right-hand pane. Open the channel from the device tree and then open the enabled setting. Proceed in configuring the parameter. - 19 - Moore Industries-International, Inc. www.miinet.com...
Page 20
1. Ensure that the station is offline. 2. Right-click the module you want to delete and select “Delete” in the pop-up menu. You may also select the Edit dropdown menu and click “Delete”. - 20 - www.miinet.com Moore Industries-International, Inc.
Page 21
Factory default is None. the second register. Configuration Figure 4. MODBUS NCS Config PC Program Configuration Figure 5. MODBUS Configuration Web Page - 21 - Moore Industries-International, Inc. www.miinet.com...
Page 22
Interface Module is in MODBUS Master mode. This is the time that a MODBUS master will wait for a response from a slave, before declaring a fault. The units are represented in - 22 - www.miinet.com Moore Industries-International, Inc.
Page 23
Refer to the Interface Module Web Server section (Step 5) of this manual for information regarding downloading of logged data. Note: Data cannot be downloaded while the Data Logger is running. - 23 - Moore Industries-International, Inc. www.miinet.com...
Page 24
No changes that you make will affect any data stored in the Interface Module’s data logger. 6. Saving the spreadsheet to a different location brings you back to the web page once downloading has completed. - 24 - www.miinet.com Moore Industries-International, Inc.
Page 25
When the NCS Home Page is displayed, click on Security, then any of the options you wish to change. Log out when you are finished. - 25 - Moore Industries-International, Inc. www.miinet.com...
Page 26
Safe Mode Jumper Installation: 1. Power down the Interface Module by removing the power cables from it. 2. Remove the left side panel from the Interface Module by removing the six side panel screws. - 26 - www.miinet.com Moore Industries-International, Inc.
Page 27
EMM Interface Module Safe Mode (Passwords Reset) Normal Mode Safe Mode Jumper Safe Mode Jumper Ear l ier Models may have Safe Mode Jumper Located as shown here 2017 an d Ol d er Versions - 27 - Moore Industries-International, Inc. www.miinet.com...
Page 28
NCS’ clock in an effort to make it match the time server. Errors related to accessing the time server cause error bits to be set in the System Time Substatus register. - 28 - www.miinet.com Moore Industries-International, Inc.
Page 29
NCS. Blocks provide the ability to read and write local MODBUS registers, to control the data logger, and an implementation of a PID control algorithm. - 29 - Moore Industries-International, Inc. www.miinet.com...
Page 30
Then if a resource with a different number is downloaded, there may not be enough room for the retain variables. Clearing the Retain Variables removes this left over data, making room for the new data. - 30 - www.miinet.com Moore Industries-International, Inc.
Page 31
Installed Interface Module See Connecting the Interface in approximately 45 seconds. It will restart in about Server Module three minutes. Moore Industries Contact Moore Industries for more Web Page Files information Interface Module Default username is Root and Administrator-Level password is Password...
Page 32
During the upgrade process, do not remove or disturb power to the Interface Module server. Removing power during the upgrade will corrupt the Interface Module’s memory and the server will not boot up. - 32 - www.miinet.com Moore Industries-International, Inc.
® NET Concentrator System NCS as MODBUS Slave - 33 - Moore Industries-International, Inc. www.miinet.com...
Page 34
16 bit register as a scaled integer. Refer to the Scaled Integers section registers via MODBUS/TCP, the MODBUS/TCP master must be configured to poll the NCS’ IP for more information. - 34 - www.miinet.com Moore Industries-International, Inc.
Page 35
MODBUS integer register, accessible using function codes 3 or 4. When using function codes 1 or 2, the 16 status register bits are mapped to 16 consecutive coils, with the status register’s least-significant-bit in the lowest addressed coil. - 35 - Moore Industries-International, Inc. www.miinet.com...
® NET Concentrator System NCS as MODBUS Master - 36 - www.miinet.com Moore Industries-International, Inc.
Page 37
A scheduler entry corresponds to a single MODBUS query. The format of a single entry consists of a comma separated list of eight required fields (there are also two optional fields). These fields are: - 37 - Moore Industries-International, Inc. www.miinet.com...
Page 38
# Interface Module port 1 in MODBUS Master mode, writing to the slave with address 4 every # 500 milliseconds for 1 coil. Value is read from Interface Module register 3001, and written # to slave register 3001. Coil 3111 enables the transfer, errors are reported # to 3101 - 38 - www.miinet.com Moore Industries-International, Inc.
® NET Concentrator System NCS as MODBUS Peer This Section Contains the following: MODBUS RTU Peer-to-Peer Systems Peer-to-Peer Software Configuration Examples of Peer-to-Peer Configurations Multiple Station Configurations Diagnostics - 39 - Moore Industries-International, Inc. www.miinet.com...
Page 40
When configuring a Peer-to-Peer Network, all stations must be configured with the same mode and bus properties (i.e., baud rate and character format.) Refer to the Peer-to-Peer Software Configuration section for more information. - 40 - www.miinet.com Moore Industries-International, Inc.
Page 41
Repeat the previous steps for all Interface Modules in assigned and the station’s output channels will your system that are to be configured as Peer-to-Peer. have no input (from another station) mapped to them via that port. - 41 - Moore Industries-International, Inc. www.miinet.com...
Page 42
1 for an example of PC software window configuration. P2P Figure 1. Configuration Windows for a Single Station Pair Running Peer-to-Peer on Port 1 and MODBUS Peer-to-Host on Port 2 EMM 1 EMM 2 - 42 - www.miinet.com Moore Industries-International, Inc.
Page 43
ETHERNET/MODBUS MODULE ANAL OG OUTPUT MODULE DISCRE T E INPUT MODULE CHANNEL 1 CHANNEL 5 CHANNEL 2 CHANNEL 6 CHANNEL 3 CHANNEL 7 CHANNEL 4 CHANNEL 8 COMMS Module ETHERNET Number POWER RS-485 - 43 - Moore Industries-International, Inc. www.miinet.com...
Page 44
Map four temperature inputs from Station 1 to four Configuration Software program to view diagnostics analog outputs (4-20mA) of Stations 2, 3 and 4. messages. P2P Figure 3. Configuration Windows for Multiple Station Pairs with Redundant Peer-to-Peer Links Using Point-to-Multipoint Mapping - 44 - www.miinet.com Moore Industries-International, Inc.
Page 45
ANAL OG OUTPUT MODULE ANAL OG OUTPUT MODULE ETHERNET/MODBUS MODULE ETHERNET/MODBUS MODULE Module Module Number Number ETHERNET ETHERNET POWER RS-485 POWER RS-485 COMMS COMMS P2P Figure 5. Configuration Window for Analog Output Temperature Scaling - 45 - Moore Industries-International, Inc. www.miinet.com...
Page 46
PC Configuration Software program on the output channel configuration. Process Data page of the consumer station, the same page where system level faults are listed. Descriptions of all present faults are shown simultaneously. - 46 - www.miinet.com Moore Industries-International, Inc.
Input/Output Modules for NET Concentrator System This Section Contains the following: Introduction Hot-Swapping an I/O Module CPM Module AIM Module TIM Module DIM Module AOM Module ROM Module Custom Curve Trimming File Management - 47 - Moore Industries-International, Inc. www.miinet.com...
Page 49
Base Clip Step 1: Gently pull base clips away from base Note: Earlier Models have a different DIN latch but overall dimensions are the same and both versions are interchangeable. - 49 - Moore Industries-International, Inc. www.miinet.com...
Page 50
® NET Concentrator System NET Concentrator System Power Module This Section Contains the following: CPM Introduction CPM Connection Diagram CPM Specifications CPM Dimensions - 50 - www.miinet.com Moore Industries-International, Inc.
Page 51
I/O Module I/O Module I/O Module I/O Module I/O Module I/O Module I/O Module I/O Module NCS POWER MODULE READY STATUS Module Module Module Module Module Number Number Number Number Number POWER 24Vdc Power – Supply - 51 - Moore Industries-International, Inc. www.miinet.com...
Page 52
87mm (3.45 in) 118mm (4.66 in) READY STATUS POWER LEFT SIDE 75mm (2.96 in) Note: Earlier Models have a different DIN latch but overall dimensions are the same and both versions are interchangeable. - 52 - www.miinet.com Moore Industries-International, Inc.
Page 53
® NET Concentrator System NET Concentrator System Analog Input Module (AIM) This Section Contains the following: AIM Introduction AIM Specifications AIM Dimensions AIM Connection Diagram Configuring the AIM - 53 - Moore Industries-International, Inc. www.miinet.com...
Page 54
CHANNEL 3 91mm (4.66 in) CHANNEL 4 (3.6 in) Note: Earlier Models have a different DIN latch but overall dimensions RIGHT SIDE AIM FRONT LEFT SIDE are the same and both versions are interchangeable. - 54 - www.miinet.com Moore Industries-International, Inc.
Page 55
Transmitter Excitation – –PS – NOTE: To install wires into the terminals, insert a small, athead screwdriver into the pry slot, open wire terminal and place wire. AIM Module Figure 2. AIM Connection Diagram - 55 - Moore Industries-International, Inc. www.miinet.com...
Page 56
Input Ranging- Allows you to either input or capture the upper and lower ranges that you want to have measured. - 56 - www.miinet.com Moore Industries-International, Inc.
Page 57
® NET Concentrator System AIM Module Figure 3. AIM Configuration Web Page AIM Module Figure 4. AIM Configuration with NCS Config - 57 - Moore Industries-International, Inc. www.miinet.com...
Page 58
® NET Concentrator System NET Concentrator System Temperature Input Module This Section Contains the following: TIM Introduction TIM Specifications TIM Dimensions TIM Temperature Input Type and Accuracy Table TIM Connection Diagram - 58 - www.miinet.com Moore Industries-International, Inc.
Page 59
CHANNEL 2 (4.66 in) Note: (3.6 in) CHANNEL 3 Earlier Models CHANNEL 4 have a different DIN latch but overall dimensions are the same and both versions are interchangeable. SIDE TIM FRONT SIDE - 59 - Moore Industries-International, Inc. www.miinet.com...
Page 60
-202 to 2372°F 0.005% of reading 100°C ±0.8°C 0 to 2300°C 0 to 2338°C 0.00043°C + 0.005% 32 to 4172°F (180°F) (±1.44°F) 32 to 4240.4°F of reading -50 to 1000mV microvolts 0.5 microvolts + 0.005% - 60 - www.miinet.com Moore Industries-International, Inc.
Page 61
Power before applying power Supply 24Vdc OR 90-260Vac (EMM 20-30Vdc) Terminal Connections Potentiometer Millivolt Thermocouple – – Increasing 4-Wire RTD & 2-Wire RTD & 3-Wire RTD & Direct Resistance Direct Resistance Direct Resistance - 61 - Moore Industries-International, Inc. www.miinet.com...
Page 62
Trimming- Each channel of the TIM can be trimmed with two data points within the selected zero and span measurement range. Refer to Trimming section of this manual for more information. - 62 - www.miinet.com Moore Industries-International, Inc.
Page 63
® NET Concentrator System TIM Module Figure 3. TIM Configuration Web Page TIM Module Figure 4. TIM Configuration with NCS Config - 63 - Moore Industries-International, Inc. www.miinet.com...
Page 64
® NET Concentrator System NET Concentrator System Discrete Input Module This Section Contains the following: DIM Introduction DIM Specifications DIM Dimensions DIM Connection Diagram Configuring the DIM - 64 - www.miinet.com Moore Industries-International, Inc.
Page 65
Module, 1W maximum according to Isolation: 500Vrms, Diagnostic Information: IEC1000-4-3-1995 continuous, from channel Refer to Appendix B Table 9 to channel, from each Weight 536 g (18.8 oz) channel to case, and from - 65 - Moore Industries-International, Inc. www.miinet.com...
Page 66
24Vdc OR 90-260Vac (EMM 20-30Vdc) Terminal Connections (Typical) Voltage Input Contact Closure Input NOTE: To install wires into the terminals, insert a small, athead screwdriver into the pry slot, open wire terminal and place wire. – - 66 - www.miinet.com Moore Industries-International, Inc.
Page 67
These tags can also be read by the OPC Server and can therefore be used to access process data in the microNCS when configuring an OPC client. - 67 - Moore Industries-International, Inc. www.miinet.com...
Page 68
® NET Concentrator System DIM Module Figure 3. DIM Configuration Web Page DIM Module Figure 4. DIM Configuration with NCS Config - 68 - www.miinet.com Moore Industries-International, Inc.
Page 69
® NET Concentrator System NET Concentrator System Analog Output Module This Section Contains the following: AOM Introduction AOM Specifications AOM Dimensions AOM Connection Diagram Configuring the AOM - 69 - Moore Industries-International, Inc. www.miinet.com...
Page 70
AOM 20V/m@20-1000MHz, 1kHz resistance on current AM when tested according to is 16ms output ENC61000-4-3-1996 765 g (27 oz) Weight Specifications and information subject to change without notice. - 70 - www.miinet.com Moore Industries-International, Inc.
Page 71
Current Sink Voltage Output Current Source NOTE: To install wires into the terminals, insert a small, athead screwdriver into the pry slot, open wire terminal and place wire. +Iout -Iout +Iout -Iout -Vout +Vout - 71 - Moore Industries-International, Inc. www.miinet.com...
Page 72
IP address that the Moore Industries NAC Client software lists for your Loop Test- This function allows you test the other instruments on the loop by setting the AOM to output Interface Module.
Page 73
(EGU). The data can then be viewed on the Process Status page with the correct units. AOM Module Figure 3. AOM Configuration Web Page - 73 - Moore Industries-International, Inc. www.miinet.com...
Page 74
® NET Concentrator System AOM Module Figure 4. AOM Configuration with NCS Config - 74 - www.miinet.com Moore Industries-International, Inc.
Page 75
® NET Concentrator System NET Concentrator System Relay Output Module This Section Contains the following: ROM Introduction ROM Specifications ROM Dimensions ROM Connection Diagram Configuring the ROM - 75 - Moore Industries-International, Inc. www.miinet.com...
Page 76
CHANNEL 7 CHANNEL 4 CHANNEL 8 Module Number Note: Earlier Models have a RIGHT SIDE ROM FRONT LEFT SIDE different DIN latch but overall dimensions are the same and both versions are interchangeable. - 76 - www.miinet.com Moore Industries-International, Inc.
Page 77
24Vdc OR 90-260Vac (EMM 20-30Vdc) of the ROM. Terminal Connections Relay Output NOTE: To install wires into the terminals, insert a small, athead screwdriver into the pry slot, open wire terminal and place wire. - 77 - Moore Industries-International, Inc. www.miinet.com...
Page 78
NCS when configuring an OPC client. Relay on Powerup- Checking a box configures the corresponding relay to be on (energized) upon power up for each channel for which you have checked the box. - 78 - www.miinet.com Moore Industries-International, Inc.
Page 79
® NET Concentrator System ROM Module Figure 3. ROM Configuration Web Page ROM Module Figure 4. ROM Configuration with NCS Config - 79 - Moore Industries-International, Inc. www.miinet.com...
Page 80
Once the side panels are removed, gently apply pressure to the edges of the PC boards exposed in order to slide out the board assembly. ROM Module Figure 5. ROM Jumpers Jumpers Jumper Position Normally Normally Closed Open - 80 - www.miinet.com Moore Industries-International, Inc.
Page 81
(i.e. 10e9 = 10000000000) and thus must not represent a number higher than Xe37. Numbers represented as Xe38 and above will produce errors. After entering your values, simply save as a .csv file. - 81 - Moore Industries-International, Inc. www.miinet.com...
Page 82
1. Check the Enabled box in the Custom Curve section of the configuration page and click Commit. 2. From the configuration page for the channel requiring the custom curve, click Load .csv. 4. The Load Custom Curve window will disappear. - 82 - www.miinet.com Moore Industries-International, Inc.
Page 83
5. If performing 2 point trimming, repeat Steps 4 and 5 for the upper trim point. 6. Click Submit to save the trimming values and continue to the next channel. Repeat these steps for each channel that requires trimming. - 83 - Moore Industries-International, Inc. www.miinet.com...
Page 84
6. Select the channel and download to save the continue to the next channel. trimming values and continue to the next channel. Repeat these steps for each channel that requires Repeat these steps for each channel that requires trimming. trimming. - 84 - www.miinet.com Moore Industries-International, Inc.
Page 85
® NET Concentrator System I/O Modules Figure 6. Trimming Web Page I/O Modules Figure 7. Trimming Configuration on PC program - 85 - Moore Industries-International, Inc. www.miinet.com...
Page 86
FTP site. Open the cfg folder and then select, and delete, the files you no longer need. Refer to the Upgrading Interface Module Firmware and Web Pages section of this manual for instruction regarding access of the associated FTP site. - 86 - www.miinet.com Moore Industries-International, Inc.
® NET Concentrator System Installation & Maintenance Installation and Maintenance This Section Contains the following: Installation Maintenance Customer Support - 87 - Moore Industries-International, Inc. www.miinet.com...
Page 88
Moore Industries recommends the following ground unit. wiring practices: The Interface Module and external I/O modules • Any Moore Industries product in a metal case connect together via DB-25 connectors integrated into or housing should be grounded. the side(s) of each module.
If any To prevent ignition of flammable or combustible Moore Industries product fails to perform up to rated atmospheres, disconnect power before servicing. specifications, call us for help. Our highly skilled staff...
Page 90
® NET Concentrator System Appendix - A Transition from EIM and MIM - 90 - www.miinet.com Moore Industries-International, Inc.
DCS/MODBUS Master does not poll them) will not be impacted. If they are used, the MODBUS registers/coils which are polled will need to be updated. Refer to Appendix B for more information. - 91 - Moore Industries-International, Inc. www.miinet.com...
® NET Concentrator System Appendix - B MODBUS Registers - 92 - www.miinet.com Moore Industries-International, Inc.
Page 93
2048 + 64(M – 1) + 16(C – 1) + B 1 or 2 Discrete Discrete Module Status Register 2003 + 4(M – 1) 3 or 4 Integer Discrete Module Status Flags 2048 + 64(M – 1) + B 1 or 2 Discrete - 93 - Moore Industries-International, Inc. www.miinet.com...
Page 94
B represents bit position (0-15) within the Interface Module register. 2. When using function codes 3, 4, 6 or 16, to access Discrete Variables, one discrete variable is delivered per MODBUS register, with a non-zero integer value representing logic 1. - 94 - www.miinet.com Moore Industries-International, Inc.
Page 95
PV is invalid floating-point value FLASH failure Low current error SRAM failure Front-end reset occurred EEPROM failure FLASH failure Channel not used SRAM failure I/O channel failure EEPROM failure Channel not used I/O channel failure - 95 - Moore Industries-International, Inc. www.miinet.com...
Page 96
Check the "Clock Battery Fail" bit in the System Time Substatus register The logger con guration le is either missing Data Logger could not be initialized or was corrupted. Click Update on the Con gure Data Logger web page - 96 - www.miinet.com Moore Industries-International, Inc.
Page 97
I/O Wiring module type mismatch. physically present. Either correct the resource, or install the correct modules. Reserved Reserved Reserved ISaGRAF has caused a system fault. Reboot and check if the condition clears itself. - 97 - Moore Industries-International, Inc. www.miinet.com...
Page 98
Loss of a Communication Link to a of the stations in the Peer-to-Peer system do not match Producer Station on Port 1 The producer station does not have Peer-to-Peer enabled on Port 1 - 98 - www.miinet.com Moore Industries-International, Inc.
® NET Concentrator System Appendix - C MODBUS Integer Support - 99 - Moore Industries-International, Inc. www.miinet.com...
Page 100
(prior to Firmware Version 3.12) Value Name Default Value Scaled Integer Zero 4096 (0x1000) Scaled Integer Full 61440 (0xF000) Scaled Integer Zero Limit 0 (0x0000) Scaled Integer Full Limit 65535 (0xFFFF) - 100 - www.miinet.com Moore Industries-International, Inc.
Page 101
(0x41DE.) The following calculation is performed to convert this value to Floating point: FloatFull-FloatZero Float PV= (Scaled Int PV-4096) + FloatZero 57344 1760-(-400) Float PV= (16862-4096) + (-400) 57344 Float PV= 80.862°F The scaled integer value of 16862 (0x41DE) equals 80.862 degrees Fahrenheit - 101 - Moore Industries-International, Inc. www.miinet.com...
Page 102
Out of Range 250.0 4096 (0x1000) 2500 In Range 500.0 32768 (0x8000) 5000 In Range 750.0 61440 (0xF000) 7500 In Range 850.0 65535 (0xFFFF) 8500 Out of Range 851.0 65535 (0xFFFF) 9000 Out of Range - 102 - www.miinet.com Moore Industries-International, Inc.
Page 103
Return Policy For a period of thirty-six (36) months from the date of shipment, and under normal conditions of use and service, Moore Industries (“The Company”) will at its option replace, repair or refund the purchase price for any of its manufactured products found, upon return to the Company (transportation charges prepaid and otherwise in accordance with the return procedures established by The Company), to be defective in material or workmanship.