Compensation features and also with Instantaneous Differential Highset Element for two winding Power Transformer and AutoTransformers. MIB202 relay, which can be used to operate for internal faults, like phase to phase, phase to earth and inter turn faults in the Transformers.
Page 5
1.2 DIFFERENTIAL BIAS SLOPE: Some unbalance current will appear in the differential circuit of the relay for predictable reasons, e.g. due to the transformer tap position and to CT errors. The current will increase with increasing load or through fault current in the transformer so, to maintain stability, the biasing current must increase proportionately.
Page 6
3.0 MAGNETIZING INRUSH RESTRAINT: Second Harmonic quantities are calculated from the signal I1 - I2 to provide an inhibit signal to prevent the protection operating for magnetizing inrush conditions. Magnetizing inrush on any phase will inhibit all three phases. 4.0 INTERPOSING CT MULTIPLIER (HV AND LV SIDE): This range of settings enable the effective ratio of the HV &...
Page 7
7.0 TYPICAL RELAY SETTING CALCULATION Power Transformer Details: Voltage = 132 / 33KV Rating = 60MVA Tap Changer = +5% - 15% Vector Group = Yd1 Current Transformer Details: CT Ratio For HV Side = 300/1 For LV Side = 1200/1 Calculation: HV rated current = 60MVA / (132 * 1.732)
INSTALLATION 1.1 UNPACKING On receipt, remove the relay from the carton box in which it was received and inspect it for obvious damage. It is recommended that the relay is not removed from the relay case. To prevent the possible ingress of dirt, the sealed polythene bag should not be opened until the relay is to be used.
Page 11
Thus mechanical interlock is provided to avoid unauthorized setting change. 2.1 CURRENT TRANSFORMER TAP SELECTION MIB202 relays are suitable for 1A or 5A application. However the relays are internally wired for either 1A or 5A as per the customer requirement.
Page 12
2) The black colour wire “9A” is inserted to 9 terminal of TB. 3) First, carefully lift the PVC boot of the wire by means of a tool (like nose pliers) to expose terminal 9A. 4) Hold the crimp by means of the same tool at the crimp point and lift to remove from the fixed terminal.
Page 13
- Enter / Reset / Cancel / To check Version SETTING INSTRUCTIONS How to operate HMI ♦ Remove the front cover by unscrewing the four knurling screws. ♦ Apply DC supply. Terminals 22,24 and 23 are for positive, negative and earth respectively as per relay rating. When the relay powers up it takes few seconds to complete the self-test routine.
Page 14
- Vector group compensation setting for LV windings - Highset setting DIFFERENTIAL INITIAL SETTINGS Setting Range: 10% to 50% in steps of 5% (The setting refers to % of rated nominal CT secondary rating) Pressing (represents initial setting is 20% of rated nominal current) display will appear, press (Submenu LED On) to get the Sub menu.
Page 15
3.5 CURRENT AMPLITUDE CORRECTION SETTINGS 3.5.1 HV side ICT multiplier Setting range: 0.50 to 2.50 in steps of 0.01. Pressing repeatedly Main menu (represents current amplitude correction setting of HV winding current input is 1.00), press key (Submenu LED On) to get the Sub menu.
Page 16
3.6.2 Vector group compensation on LV windings Setting available: Yy0, Yy2, Yy4, Yy6, Yy8, Yy10, Yd1, Yd3, Yd5, Yd7, Yd9, Yd11, Ydy0 and Ydy6 Pressing repeatedly Main menu (represents Vector group compensation for LV winding is Yy0), press key (Submenu LED On) to get the Sub menu. Pressing key changes the Vector group compensation setting desired by increment or decrement.
5.0 TO CHECK THE RELAY VERSION Press key four times, example of relay version display is as follows: Represent MIB 202-relay version 1 To get back the main menus press key. 6.0 TO CANCEL SETTING WHILE CHANGING (CANCEL) While the particular setting is being changed (using key) with Submenu LED ON, by pressing key, the original setting is...
Page 18
To enter into this mode, the sub menu key has to be pressed for around 10 secs. After the time delay the relay front LED will display the following signals as in the order given below by pressing the key. - Indicates HV winding r –...
Page 19
- Indicates HV winding b – phase relay current after amplitude and phase angle (Vector group correction) correction. - Indicates LV winding b – phase relay current after amplitude and phase angle (Vector group correction) correction. - Indicates b – phase restraining current - Indicates b –...
Page 20
COMMISSIONING 1. REQUIRED TEST EQUIPMENT'S • 500V insulation test sets. • Variable secondary injection current source rated 10A or greater. • Variable voltage source. • Time interval meter. • A DC supply with a nominal voltage within the working range of the relays DC auxiliary supply ratings.
Page 21
5.2 SECONDARY INJECTION Select the required relay configuration and settings for the application. Note that the MIB202 relay can be connected either as 1A or 5A-rated device. The user should check this before commencing secondary testing.
Page 22
These tests check the ratio and polarity of the star connected CT's with or without a neutral CT and also their connections to the correct terminals of the MIB202 input modules. 5.4 PUTTING INTO SERVICE After completing all tests satisfactorily, the relay should be put...
Page 23
3. Check the relay healthy indication/display. 4. Replace the relay cover. 5. Insert the trip links. 6. Perform trip test by secondary injection. 7. Remove all test connections MIB202 Bias Current Operate Current Fig 1 Circuit For Checking the Bias Characteristics...
2. Terminal No.23 (Earth) is to be connected directly to earthbar. Drawing No. :- 8662W20001 WIRING DIAGRAM FOR MIB 202 RELAY CHECKED EASUN REYROLLE LIMITED., No. Sig. DATE Sig. DATE DATE Sig.