Honeywell 7800 Series Product Data page 18

Keyboard display module
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

7800 SERIES S7800A KEYBOARD DISPLAY MODULE
Fault Code
Fault 27
*Start Switch On*
Fault 28
*Pilot Flame Fail*
Fault 29
*Lockout ILK*
Fault 30
*Running ILK*
Fault 31
*Low Fire Sw. Off*
65-0090—4
Table 7. Hold and Fault Message Summary (Continued).
System Failure
Start Switch was on during
PREPURGE (Device specific).
Pilot flame failure.
Lockout Interlock fault.
Running Interlock fault.
Low Fire Interlock Switch failure
to close during RUN (Device
specific).
Recommended Troubleshooting
1. Start Switch held on too long.
2. Check wiring; verify that Start Switch is correctly connected.
3. Make sure that the Start Switch is functioning properly and that
the switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE; set the
Run/Test Switch to Test. Make sure there is no power at
terminal 6 during PREPURGE.
5. If steps 1 through 4 are correct and the fault persists, replace
the relay module.
1. Check pilot valve wiring and operation. Correct any errors.
2. Check fuel supply.
3. Check pilot pressure and repeat pilot turndown test.
4. Check ignition transformer electrode, flame detector, flame
detector sighting and flame amplifier.
5. If steps 1 through 4 are correct and the fault persists, replace
the relay module.
1. Check wiring and correct any errors.
2. Inspect the fan; make sure that there is no blockage of the air
intake and that it is supplying air.
3. Make sure that the Lockout Interlock Switches are working
properly and that all switch contacts are free from
contaminants.
4. Reset and sequence the relay module to PREPURGE (place
the Run/Test Switch in the Test position, if available). Measure
the voltage between terminals 7 and L2(N). Line voltage
should be present.
5. If steps 1 through 4 are correct and the fault persists, replace
the relay module.
1. Inspect the Running Interlocks, including the Airflow Switch,
and the connections.
2. Make sure that the Running Interlocks, including the Airflow
Switch, are functioning properly and that switch contacts are
free from contaminants.
3. Reset and sequence the relay module to PREPURGE. Set the
Run/Test Switch, if available, to Test. Measure the voltage
between terminal 7 and L2(N). Line voltage should be present.
4. If steps 1 through 3 are correct and the fault persists, replace
the relay module.
1. Check wiring and correct any errors.
2. Reset and sequence the relay module.
3. Use either the manual motor position to drive the motor to the
Low Fire position, or use the Run/Test Switch option, if
available. Sequence to Run drive to Low Fire and place the
switch in the Test position. Adjust the Low Fire Switch while in
this state to make sure it is closing properly.
4. While in Run, drive to Low Fire state, measure the voltage
between terminal 18 and L2(N). Line voltage should be
present. If not, the switch adjustment is incorrect and/or the
switch is defective and needs replacement.
5. Reset and sequence the relay module. If line voltage was
present between the Low Fire Switch and terminal 18, and the
fault persists, replace the relay module.
18

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7800a

Table of Contents