TWINFLEX ® Fire Suppression System Remote Status Indicator (RSI) ® (Suitable for TWINFLEX SRP Control Panel from V01.000) Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-1362-01...
Page 2
Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in respect of such contents.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Contents Introduction ................................5 System Design ..............................5 Equipment Guarantee ..........................5 Anti-Static Handling Guidelines ........................5 Warning ................................ 5 EMC ................................6 The TWINFLEX® SRP System ..........................6 Remote Status Indicator (RSI) ..........................6 Mounting the RSI ..............................
Page 4
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Remote Status Indicator Specification ....................... 25 Fire Alarm System Notice ..........................26 To Enable the Control Panel Keys ......................26 To Manually Operate the Fire Alarm Sounders ..................26 Following a Fire Alarm Operation ....................... 26 Following a Fault Condition ........................
Failure to do so may result in damage to the equipment and could invalidate the warranty. For technical support please contact your distributor. Do not call the Fike Safety Technology support department unless your distributor has first given their advice and attempted to rectify the issue.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual This equipment when installed is subject to the EMC directive 2004/108/EC. It is also subject to UK Statutory Instrument 2006 No. 3418. To maintain EMC compliance, this system must be installed as defined within this manual. Any deviation from this renders the installer liable for any EMC problems that may occur either to the equipment or to any other equipment affected by the installation.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Mounting the RSI First identify the proposed location for the RSI. Ensure that it will be easily accessible and that account is taken of any subsequent work that may affect access. The RSI should be located at an access point to a building which is not covered by the SRP Control Panel.
Page 8
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual...
Page 9
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual...
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Installation and Commissioning Topology & Cabling All system wiring should be installed to comply with BS 5839: Pt 1: 2002 and BS 7671 (wiring regulations) and any other standards relevant to the area or type of installation. A cable complying with BS 5839: Pt 1: 2002 Category 1 (cable required to operate for prolonged periods during fire conditions) is required.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Power Supply & Connections 24V DC Power is provided to the RSI from the Control Panel via the AUX PWR 1 or AUX PWR 2 connectors on the SRP Control Panel connector board. The preferred cable to carry the 24V from the Control Panel to the RSI is 2-core 1.5mm screened fire resistant cable (i.e.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Peripheral Bus Connections Communication between the SRP Control Panel and RSI is established via a multi-drop RS-485 Peripheral Bus using 2-core 1.5mm screened fire resistant cable (i.e. MICC, FP200, Firetuff, Firecell, Lifeline or equivalent).
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Ext Switches SW1 and SW2 Connection Examples EXT SWITCHES SW1 must only be used for the HOLD operation. EXT SWITCHES SW2 must only be used for the RELEASE operation. The maximum cable length from the EXT SWITCHES connector on the RSI Back Board to the SW1-HOLD and SW2-RELEASE switches is 100 metres.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual SRP Control Panel Peripheral Bus Settings To set up the SRP Control Panel to supervise the RSI(s) installed in the system, set the Write Enable switch to ON position, login with Engineer level access, and select “13 RSI SUPERVISION” from the MAIN MENU.
When communication between the RSI and SRP Control Panel is established, the HOME screen shows the same date and time as displayed on the SRP Control Panel: 01/23/2016 04:56 √ TWINFLEX RELEASING FIKE(UK) Turn Key/Press Enter NOTES: The Time/Date format on the RSI is same as the SRP Control Panel.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Commissioning Ensure that the RSI has been correctly and securely mounted to the wall. For each RSI, verify that the Date and Time match the date and time on the SRP Control Panel. ...
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual General Operation of Remote Status Indicator RSI Front Panel General Indication LEDs System Indication LEDs System RSI Information Controls Window Fire Alarm Controls Enable Key Switch Extinguishant Auto/Manual Release Key Switch LED Indication The LED operation of the RSI is described below.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Fire Alarm Controls The main Fire Alarm Controls may be enabled by turning the key switch to the controls enabled position to go from access level 1 to access level 2. The Silence Alarms button will silence any fire alarm sounders that are currently sounding.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Access Level 1 (Normal) At Access Level 1 (NMx - Normal), the main Fire Alarm Controls are disabled and only the View Current Events Menu can be accessed. The Fire Alarm Controls will only be accessible if the key switch is turned to “enabled”.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Access Level 2 (User): At Access Level 2 (user), the main Fire Alarm Controls are enabled and the following menus are accessible. Pressing the enter button when in level 2 shows the MAIN MENU. The available options are shown below and may be scrolled through by pressing the UP and DOWN arrow keys.
Page 24
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual The TEST LCD option causes the LCD to black out each character in succession to ensure correct operation. The test will count down and return to the TEST MODES menu screen. ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒...
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual End User Training A Fire Alarm System is of little use if the end user and/or the responsible persons who will be present in the building do not know how to operate and respond to the system. It is therefore essential that commissioning includes training for the users of the system and responsible persons.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Fire Alarm System Notice To Enable the Control Panel Keys You may gain access to the fire alarm controls by inserting the key turning ¼ turn. The ‘Controls Enabled’ LED should then be illuminated.
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Important Notes FIRE ALARM COMPANY: ADDRESS: FOR SERVICE CALL: (Working hours) (Call Out) FIRE ALARM COMPANY: ________________________________________________________________________________ ADDRESS: ______________________________________________________________________ For Service Phone: _________________(During Working Hours) ________________(Out of Working Hours)
Page 28
® TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual Fire Alarm User Notice Note The Fire alarm system installed in this building has ‘Alarm Confirmation’ technology to help eliminate false alarms. Please read and understand the following information in order to make the most use of the system Action Required If you think that you may have accidentally set off the fire alarms, then check the following:...
Contact your distributor for technical support on this 0834 product. Do not call the Fike Safety Technology technical support department unless your distributor has first given their advice and attempted to rectify the issue. Technical support will not be available if the instruction manual has not been read and understood.