Gira 2120 00 Operating Instructions Manual page 2

Power supply with integrated choke
Table of Contents

Advertisement

Power supply 160 mA, 320 mA, 640 mA, 1280 mA with integrated choke
(1)
Connection of mains
(2)
LED Betrieb, green
On: Normal operation
Flashes: Overload or overvoltage
Off: No mains voltage or internal error
(3)
LED Überlast, red
On: Overload or short-circuit on KNX bus line or output DC 30 V
(4)
LED Überspannung, yellow
On: Overvoltage on KNX bus line or output DC 30 V
(5)
Output DC 30 V
(6)
Output Bus for KNX bus line
(7)
LED Reset, red
Flashes rapidly 2.5 Hz: Reset for 20 seconds
Flashes slowly 0.25 Hz: Permanent reset
Button Reset
(8)
Acknowledge the diagnostic message: Press briefly, < 0.5 seconds
Switch off the KNX bus line for 20 seconds: Press between 2...4 seconds
Permanently switch off the KNX bus line: Press longer than 4 seconds
Terminate the permanent reset: Press the button
(9)
Signal contact for diagnostic message
Closed: Normal operation
Open: After overload, overvoltage or in case of a power failure
3
Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
Intended use
Supplying KNX devices with bus voltage
Supplying devices with direct current
Mounting on DIN rail according to EN 60715 in sub-distribution unit
Product characteristics
Output with integrated inductance for supplying KNX bus lines
DC 30 V output for supplying additional devices
82597322
Figure 2: 1280 mA power supply – view
06.05.2019