UE TX200H Installation And Maintenance Instructions Manual

Hart pressure transmitter

Advertisement

Quick Links

Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties.

GENERAL

The TX200H is a registered HART 7 compliant device. It is a highly accurate,
rugged, SMART pressure transmitter that can communicate digitally and via
the 4-20 mA analog signal output. The TX200H utilizes the HART protocol
and an internal microcontroller to allow the end-user to easily configure and
calibrate the pressure transmitter as it provides process variable measure-
ment and device health data.
HART is an acronym for Highway Addressable Remote Transducer and it has
become the most widely adopted standard for industrial communication. The
Hart protocol is based on a standardized set of commands that is maintained
by the HART Communication Foundation (HCF) and allows any end-user to
easily integrate devices like the TX200H into their HART enabled system. The
TX200H, as a registered HART device has been designed to communicate
with other HART enabled devices such as a software package running on a
PC with HART interface or a field portable HART communicator.
BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR
COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE
SENSOR AND WETTED PARTS.
MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL
INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND
UNDERSTOOD BEFORE UNIT IS INSTALLED.
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION
1, GROUPS A, B, C AND D; CLASS II, DIVISION 1, GROUPS E, F AND G;
CLASS III; OR NON-HAZARDOUS LOCATIONS ONLY. -40˚C (-40˚F) ≤
TAMB. ≤ +85˚C (+185˚F), ENCLOSURE TYPE 4X.
THIS EQUIPMENT IS ATEX CERTIFIED FOR EQUIPMENT CATEGORY 2.
SUITABLE FOR APPROPRIATE USE IN GAS ZONE 1 AND DUST ZONE
21 APPLICATIONS.
EN 60079-0:2012, EN 60079-1:2007, EN 60079-31:2009
0539 DEMKO 08 ATEX 0810742X
II 2 G Ex d IIC T5 Gb
II 2 D Ex tb IIIC T90˚C Db
IP66
-40˚C ≤ Tamb. ≤ +80˚C
UE declarations and third-party issued Agency certifications are available for
download at www.ueonline.com/prod_approval.
PROOF PRESSURE* LIMITS STATED IN THE LITERATURE AND ON
THE TRANSMITTER HOUSING MUST NEVER BE EXCEEDED, EVEN
BY SURGES IN THE SYSTEM. OCCASIONAL OPERATION OF UNIT
HART® is a registered trademark of the
Hart Communication Foundation
TX200H™
HART® Pressure Transmitter
IMTX200H-03
www.ueonline.com

Installation and Maintenance

Instructions
UP TO MAXIMUM PRESSURE IS ACCEPTABLE (E.G. START-UP, TESTING).
CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER
RANGE PRESSURE**.
*Proof Pressure
The maximum pressure to which a pressure sensor may be occasionally sub-
jected, which causes no permanent damage (e.g., start-up, testing).
**Over Range Pressure
The pressure value to which a transmitter may be continuously subjected,
without causing a shift in calibration or damage to the sensor.
THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS.
ANY SUBSTITUTION OF COMPONENTS MAY IMPAIR UNIT SAFETY AND
SUITABILITY FOR CLASS I, DIVISION 1.
THE EPOXY RESIN SHALL NOT BE SUBJECTED TO A TEMPERATURE
GREATER THAN 125˚C.
Please refer to product bulletin for product specifications. Product bulletin
may be found at www.ueonline.com
Date code format on nameplate is "YYWW" for year and week.

Part I - Installation

MouNTING

ALWAYS LOCATE UNITS WHERE SHOCK, VIBRATION AND AMBIENT
TEMPERATURE FLUCTUATIONS ARE MINIMAL. DO NOT MOUNT IN
AMBIENT TEMPERATURE AREAS EXCEEDING 185˚F / 85˚C (IF UL/
cUL APPROVAL IS APPLICABLE) OR 176˚F / 80˚C (IF ATEX APPROVAL IS
APPLICABLE).
IF SEVERE PRESSURE SURGES ARE EXPECTED, CONSIDER THE USE
OF A PRESSURE SNUBBER.
UNIT MAY BE MOUNTED IN ANY POSITION. ALWAYS HOLD A WRENCH
ON THE SENSOR FLATS (PRESSURE PORT) WHEN MOUNTING UNIT.
Panel Mounting via 1/2" NPTM or M20 Electrical Connection
When panel mounting, mount through 7/8" clearance hole in panel. Hold in
place with serrated 1/2" or M20 conduit nut. Always support the unit by hold-
ing a wrench on the hex fitting and not the housing body.
IMTX200H-03

Tools Needed

Adjustable Wrench

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TX200H and is the answer not in the manual?

Questions and answers

Summary of Contents for UE TX200H

  • Page 1: Installation And Maintenance

    Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended Practices, Liabilities and Warranties. GENERAL The TX200H is a registered HART 7 compliant device. It is a highly accurate, UP TO MAXIMUM PRESSURE IS ACCEPTABLE (E.G. START-UP, TESTING). rugged, SMART pressure transmitter that can communicate digitally and via CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER the 4-20 mA analog signal output.
  • Page 2 Green: Earth ground will remain between 4-20mA. In the event that the pressure goes beyond the operating range of the device or in a fault condition, the TX200H will indi- Figure 1 cate the condition on the 4-20mA loop as follows:...
  • Page 3 NoTE: The TX200H ships from UE with the poll address set to O. A poll address of 0 indicates the Process Variable Units: Allows the user to select the units of mea- device is not in multi-drop mode.
  • Page 4 Part III - Dimensions Dimensional drawings for all models may be found at www.ueonline.com Pressure Connection Chart Length Code Description “A”in “B”in [mm] 1/4” NPT (female) 15/16 0.54 [13.7] OR M20 (METRIC) 1/2” NPT (female) 1-3/8 1.01 [25.7] 1/2” NPT (male) 15/16 1.26 [32.0] HF4 Autoclave (female)
  • Page 5 Part IV - TX200H HART CoMMANDS Command Number Universal Commands, Command Function Read Unique Identifier Distributor, model, device id, tag, date, ID code, device type code (E18D) sw rev, device id, Read Primary Variable Read Loop Current and Percentage of Range...
  • Page 6 All but running delayed responses flushed appropriate, this entry point should be sealed to prevent moisture entry. Multi-Definition Error • Unit must not be altered or modified after shipment. Consult UE if modifica- tion is necessary. Lower Range Value too High •...