Download Print this page

Honeywell C7046C Product Data page 11

Solid state economizer system, consisting of discharge air sensor or mixed air sensor, solid state enthalpy sensor, solid state temperature sensor, damper actuators, thermostat and solid state economizer logic module
Hide thumbs Also See for C7046C:

Advertisement

OUTDOOR
AIR
ENTHALPY
SENSOR
C7400
UNOCCUPIED
S6005
TIMER
OCCUPIED
Y1
Y2
W2
W1
G
RH
RC
T7300 OR T874
THERMOSTAT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
MOTOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
3
ASSURE THAT EQUIPMENT TRANSFORMER IS SIZED FOR THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
4
1S IS AN ELECTRONIC SWITCH, WHICH CLOSES WHEN POWERED BY A 24 VAC INPUT.
5
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
6
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR
IS ADDED TO S R AND + FOR DIFFERENTIAL ENTHALPY.
Fig. 13. W7459A,D/C7400 used in two-stage cooling system with single enthalpy changeover and with M7415 Actuator.
TR
TR1
+
S O
S
S R
620 OHM
RESISTOR
1
3
T
C7150B MIXED
P
AIR OR
C7046A
DISCHARGE
AIR SENSOR
W
T6031 AMBIENT
LOCKOUT
R
CONTROL
50° F SETPOINT
SOLID STATE ECONOMIZER SYSTEM
W7459A ECONOMIZER PACKAGE
+
+
6
5
1K
5
2
1S
2K
4
4
T1
1S1
P1
MINIMUM POSITION
ADJUSTMENT
C
Y1
Y2
W2
W1
FDR
G
FDR
2
R
HVAC EQUIPMENT
TERMINAL STRIP
11
M7415 ACTUATOR
TR
24 VAC
TR1
T
MIXED
AIR
T1
SENSOR
P1
MINIMUM
P
POSITION
M7415
TR
COOL 1
24 VAC
TR1
COOL 2
SENSOR
T
T1
HEAT 2
P1
MIN
POS
P
HEAT 1
FAN
DELAY
RELAY
1
3
FAN
L2
L1
(HOT)
M10115
63-2484—1