Installation, Operation, & Maintenance Instructions IOM JS500.03 Vertical Float Switches 2016.04 Table of Contents Principle of Operation Switch Assembly Identification Model Number – Part 1: Switch Assembly Model Number – Part 2: Spare Enclosure & Pressure Tube Model Number – Part3: Conversion Kits Electrical Characteristics, Wiring Examples, & Switch Ratings Switch Mechanisms – Simple Apparatus Installation – Part 1: Switch Assembly Installation – Part 2: Spare Enclosure & Pressure Tube Installation – Part 3: Conversion Kits Installation Specific to Hazardous Area Putting the Switch into Service Taking the Switch out of Service Maintenance Dimensional Data 12‐13 Switching Point Adjustment Bolting: Torque Values & Tightening Sequence Switch Mechanism Replacement Spare/Replacement Parts Parts Store www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
IOM JS500.03 Vertical Float Switches 2016.04 Principle of Operation ‘Primary’ magnet encased in Secondary ® Switching is achieved with the Jerguson Tri-Magnet 316 stainless steel switch mechanism system, giving snap-action, “latch-on” switching. magnet Contact pair on Vertical movement of the primary magnet A in a glandless contact blades...
Model Number - Part 1: Switch Assembly 1F SA7F 1 X4 1 1 WN Product Line/Tagging = Jerguson ® (Omitted) = Magne-Sonics Chamber Design Style (A-Z, Not w/in Ex scope) = Bottle/Sealed Chamber = Flanged Chamber or Head Ass'y Only = Top Mount (No Chamber) Chamber/Process Conn.
HLA Switch Two switch pump control circuit using auxiliary contacts on starter. Note diagram shows starter fitted with 250V coil for 3-phase LLA Switch 3-wire supply connect coil terminal N to line 1 and fit 440V coil. www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
That suitable temperature rated cable is used. Note: The cable entry temperature may exceed 70°C d. The float is protected from impact or friction, or static electrical build-up from fast flowing non- conductive fluids, that could generate an ignition source. www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
Before energizing, ensure the cover locking safety grub screw is replaced and tightened. Do not energize if the cover locking safety grub screw is missing. Before energizing, ensure that the fiber sealing washer and hexagon bolt were reinstalled Weatherproof models: at the top of the cover. www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
Installation shall be carried out by suitably trained personnel in accordance with applicable codes of practice. For hazardous area installations, also see ‘Installation Instructions Specific to Hazardous Areas’ section, page 10. 1. Refer to Document JS500.06 for complete conversion instructions. www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
Ambient Air Temperature (Ta) (-50°C ≤ Ta ≤ +60°C) T Class Process Temperature (Tp) Allowable process temperature (Tp) ‐50°C TO 80°C FM Approval Standards: FM Class 3600:2011, FM Class 3615:2006, FM Class 3616:2011, ‐50°C TO 95°C FM Class 3810:2005. ‐50°C TO 130°C The Temperature Class applicable for each application is determined by the ‐50°C TO 195°C process temperature (Tp) as shown in the table above. ‐50°C TO 295°C ‐50°C TO 455°C www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
3. Remove any remaining fluid from the chamber using a drain valve, drain plug, or the lowest connection. ® Maintenance of the Jerguson Vertical Float Switch Inspection and maintenance shall be carried out by suitably trained personnel in accordance with all local and national codes.
G = Enclosure Height. See table on page 13. Model -4F JB_5F JX_5F 2.00 Dim C1 (in) 5.00 Dim C2 (in) Dim D (in) Default trip locations at minimum operating SG. See ‘Switching Point Adjustment’ section, page 13. www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...
(SG) of the unit. Higher application SG’s will cause the switch to trip sooner, at a lower elevation. Any change made to the factory default switch positions are done at the customers discretion, and should be tested in the application fluid to ensure that each switch mechanism can be tripped and also reset. www.Jerguson.com ● JergusonApp@clark‐reliance.com ● +1.440.572.1500...