Fuses - ABB EAN823 Operating Instruction

Power electronic units
Hide thumbs Also See for EAN823:
Table of Contents

Advertisement

6.3

Fuses

Electronics Fuse type
EAI823 /
EAN823
EBN853
EBN861
1) The 35 A safety fuse and the 16 A thermal circuit breaker are included in the delivery scope. The special starting
conditions of the EBN861 power electronic unit help to ensure safe operation.
OI/PME/LME/EAN823/EBN853/EBN861-EN
Dimensions
External fuse
Mains fuse
Analog setpoint
Heater (optional)
External fuse
Mains fuse
Analog setpoint
Brake fuse
DC link fuse
Heater (optional)
1)
External fuse
Brake fuse
DC link fuse
Fuse for digital
outputs DO 1,DO 2,
DO 3
Heater (optional)
Commissioning and service field (ISF)
Installation
location
-
External
5 x 20 mm
in connection
chamber
5 x 20 mm
in connection
chamber
5 x 20 mm
in connection
chamber
-
External
5 x 20 mm
in connection
chamber
5 x 20 mm
in connection
chamber
5 x 20 mm
Power board
6.3 x 32 mm
Power board
5 x 20 mm
in connection
chamber
-
External
5 x 20 mm
Power board
6.3 x 32 mm
Power board
5 x 20 mm
in connection
chamber
5 x 20 mm
in connection
chamber
U=115 V U=230 V
16 A; time-lag
6.3 A;
3,15 A; time-
time-lag
lag
40 mA, fast-acting
2 A; time-lag
16 A; time-lag
12.5 A;
10 A; time-
time-lag
lag
40 mA, fast-acting
0.315 A; medium time-
lag
10 A, super fast-acting
2 A; time-lag
35 A fuse
16 A thermal
circuit
breaker
0.315 A;
medium
time-lag
16 A, super
fast-acting
3 x 0.2 A,
medium
time-lag
2 A; time-lag
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pme120-aiLme620-aiEbn853Ebn861

Table of Contents