Powers HydroGuard T/P e705 Technical Instructions

Combination mixing valve

Advertisement

Quick Links

Technical Instructions
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use
information can result in death, serious personal
injury, property damage, or damage to the
equipment.
Keep this Manual for future reference.

Description

n
The Series e700 HydroGuard T/P automatically mixes hot and
cold water to deliver blended water within a specified range.
Using an advanced thermal actuator, the Series e700 quickly
compensates for temperature fluctuations induced by water
temperature and pressure changes. In the event of cold
water failure, the thermostatic motor virtually shuts off the
flow of hot water. HydroGuard T/P meets the most stringest
performance criteria for temperature and pressure changes,
defined by ASSE 1016 (Type T/P).
Featuring heavy, cast-brass construction and an adjustable
brass to brass high limit temperature stop, self-contained

Specifications

n
Valve Construction: Combination mixing valve, with heavy cast bronze body and brass stem. Concealed adjustable high
temperature limit stop. Available with ADA-compliant ABS or metal lever handle.
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/2" Sweat Inlet/Outlet
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 gpm
Maximum Hot Water Supply Temperature . . . . . . . . . . . . . . . . . . . . . . . 190°F(88°C)
Minimum Hot Water Supply Temperature (Approach Temperature) . . . . . . . . 10°F (5.5°C) above set point
Maximum Operating Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 psig (862 kPa)
Temperature Ranges (for +/- 3°F performance) . . . . . . . . . . . . . . . . . . . . . ASSE 1016 Type T/P: 90 - 110°F (32 - 43°C)
High Temperature Limit Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjustable (factory set at 110°F [43°C])
Maximum Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 psig (862kPa)
Minimum Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0 gpm (3.781 L/min)
Approved Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CSA B125.1, ASME 112.18.1 ASSE 1016 T/P
Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1016, IAPMO cUPC
Shipping Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 lbs. (1.6 kg)
All HydroGuard T/P Series e700 combination mixing valves
meet above performance specifications based on typical
operating conditions as stated in ASSE 1016 (45 psi pressure
differential, hot water supply between 140°-180°F (60°-82°C),
cold water supply less than 70°F (21°C).
e705
cartridge, corrosion resistant internal component, integral
checks, and back to back shallow wall installation capabil-
ity. All parts of the e700 Series valve are accessible from
the front of the valve. All Series e700 valves open in the cold
water position to ensure maximum bather safety and comfort.
The accuracy, reliability and water economy of the Series
e700 HydroGuard T/P make it preferable for applications that
require precise, consistent water
control: showers, baths, hospital hydrotherapy and
residential areas. All e700 valves meet the Americans with
Disabilities Act (ADA).
ASSE 1016 Type T: 80 - 120°F (27 - 49°C)
If your operating conditions vary from those stated in the
standard, performance may vary as well. Consult your local
sales representative or a Powers factory engineer to discuss
your specific application. All Powers thermostatic mixing
valves perform to the requirements of standards ASSE 1016
and CSA B125.
IS-P-e700
HydroGuard
T/P
®
Series e700
e707
e710

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HydroGuard T/P e705 and is the answer not in the manual?

Questions and answers

Summary of Contents for Powers HydroGuard T/P e705

  • Page 1 Consult your local operating conditions as stated in ASSE 1016 (45 psi pressure sales representative or a Powers factory engineer to discuss differential, hot water supply between 140°-180°F (60°-82°C), your specific application. All Powers thermostatic mixing cold water supply less than 70°F (21°C).
  • Page 2 Operation Hot and cold water enter respective ports in the valve and mix in a chamber containing an advanced thermal actuator (refer to cutaway view). This actuator controls the position of the plunger and temperature. Rotating the adjustment handle repositions the plunger in the cartridge assembly to produce the desired temperature.
  • Page 3 Safety Requirement - All Models WARNING CAUTION Need for Periodic Inspection: Periodic inspection by a licensed The high temperature limit stop setting must be adjusted to limit contractor is recommended. Corrosive water conditions, tempera- the distance the user can rotate the handle towards the full hot tures over 200°F, unauthorized adjustments or repair could render water position.
  • Page 4 A Watts Water Technologies Company USA: Tel: (800) 669-5430 • Fax: (847) 229-0526 • PowersControls.com Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • PowersControls.ca Latin America: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • PowersControls.com IS-P-e700 1515 EDP# 6512256 © 2015 Powers...