Thorn security TYCO T1216W-C Installation And Commissioning Manual

Marine fire detection/alarm control panel and repeater

Advertisement

Marine Fire Detection/Alarm Control Panel and Repeater
© 2012 Thorn Security Ltd
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
TYCO T1216W-C
Installation and Commissioning Manual
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
T1216W-C
MARINEW-P-I
1
11/12
PAGE 1 of 39

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TYCO T1216W-C and is the answer not in the manual?

Questions and answers

юрій
July 4, 2025

інструкція на украінській мові є?

Summary of Contents for Thorn security TYCO T1216W-C

  • Page 1 ISSUE No. & DATE: TYCO T1216W-C Marine Fire Detection/Alarm Control Panel and Repeater Installation and Commissioning Manual © 2012 Thorn Security Ltd PAGE 1 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 2: Table Of Contents

    T1216W-C MARINEW-P-I 11/12 List of Contents 1. L ........... 3 7.8.1 C1630 O IST OF IGURES UTPUT NTERFACE ........24 ONFIGURATION 2. L ............ 3 IST OF ABLES 7.8.2 C1634 8 WAY VOLT FREE RELAY OUTPUT 3. I ............4 NTRODUCTION ......
  • Page 3: List Of Figures

    OTHERBOARD ....37 EPEATER IRING IAGRAM 20 – W .. 38 IGURE ATERMIST ANEL IRING IAGRAM © 2012 Thorn Security Ltd PAGE 3 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 4: Introduction

    T1216W-C MARINEW-P-I 11/12 4. Commission the panel 3. Introduction Refer to section 6. Commissioning. This manual contains all the information necessary for the installation, commissioning and maintenance 5. Installation of the T1216W panel. The control panel must be installed by suitably NOTE: It is important to read this manual fully qualified technicians familiar with the installation of before commencing installation.
  • Page 5 Exhausted batteries must be recycled. Return them battery manufacturer or take them to your Council waste disposal site appropriate disposal. © 2012 Thorn Security Ltd PAGE 5 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 6: Installation Instructions

    T1216W-C MARINEW-P-I 11/12 Table 1 – Content of Spares Bag Quantity Description Type Mains Fuse T5AH250V 20mm Battery Fuse T8AH250V 20mm End-of-Line resistors for zone circuits 10k 0.25W End-of-Line resistors for alarm circuits 3k9 0.25W End-of-Line resistors for monitored outputs 3k9 0.25W Key Ref - 801 Access Control key...
  • Page 7 20. Reinstallation of the chassis is the reverse of removal. Ensure that all keyholes on the © 2012 Thorn Security Ltd PAGE 7 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 8: Power Supply

    T1216W-C MARINEW-P-I 11/12 chassis are fully mounted onto the posts in the washers [supplied with the fixing kit], one back-box. fitted between the panel and the bulkhead and the other fitted between the panel and 21. Reconnect all earth wires and ensure none are the steel washer inside the panel.
  • Page 9: Panel Psu

    2Vdc. Use three cores of the RS485 screened data cable. © 2012 Thorn Security Ltd PAGE 9 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 10 T1216W-C MARINEW-P-I 11/12 Figure 2 – Battery clamp details PAGE 10 of 39...
  • Page 11: C1665 Musteri

    Panel 1 Repeater Panel Wiring Optional Repeater Muster Interface[s] Figure 4 – Muster Interface Wiring Diagram © 2012 Thorn Security Ltd PAGE 11 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 12: Modifications To Thew

    T1216W-C MARINEW-P-I 11/12 5.3.2 Modification 2 [System Operated]: Modifications to the Water Mist Relay Control Panel Refer to Figure 6 for details. Replace the 6k8 monitoring resistor connected Three modifications to the Water Mist Relay Control between wires 315 and 316 with a 10k 0.25W. Panel [WMRCP] are necessary to provide the correct interface.
  • Page 13: T1216W And 5.5 Replacing The Display

     All necessary permits to work are in place. modified under section 5.3.1]. Connect 2 cores © 2012 Thorn Security Ltd PAGE 13 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 14: To Change The Inserts

    T1216W-C MARINEW-P-I 11/12 to the appropriate terminals. Record the core 5.5.1 To change the inserts identification reference and circuit use. Isolate the mains supply to the panel. 9. In the WMRCP, identify the additional fault Disconnect the batteries at the battery box. interface relay described in section 5.3.3.
  • Page 15 Note – Over tightening the nut may cause the stud to break away from the door. Figure 8 – Display Insert Replacement © 2012 Thorn Security Ltd PAGE 15 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 16: T Ofit The Optional

    T1216W-C MARINEW-P-I 11/12 6. Offer the door stay door mounting bracket up to 5.5.2 To Fit the Optional Door Stay the studs on the display frame as shown in Figure 9 and fit one M6 washer and Nyloc nut 1. A door stay is available as an option for the [supplied] to each stud.
  • Page 17: Commissioning

    3. Connect a wire link as the end-of-line device on each of the fire detection zones and sounder © 2012 Thorn Security Ltd PAGE 17 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 18: Powering Up

    T1216W-C MARINEW-P-I 11/12 circuits. At the panel end, measure the detector/MCP discrimination; all devices will resistance across the positive & negative ends raise a detector fire indication. of the cables for each of the circuits; ensuring Intrinsically Safe alarm devices [sounders] may be the value does not exceed 20.
  • Page 19: Configuration

    Close the panel door to allow access to the © 2012 Thorn Security Ltd PAGE 19 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 20: Engineer S Zone /Output Process

    T1216W-C MARINEW-P-I 11/12 buttons on the display. IMPORTANT NOTE: WHILE THE PANEL IS ENGINEER’S ZONAL/OUTPUT 2. Select a zone or output to be configured: CONFIGURATION MODE, ZONAL o On the panel display, press the Select On/Off INPUTS ARE IN PERMANENT RESET AND switch to enable the Cursor Select Mode.
  • Page 21: List Of Configuration

    [Not EN54 compliant function]. will restart the delay timer.  SW 2/4 to 2/5 – Not Used © 2012 Thorn Security Ltd PAGE 21 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 22 T1216W-C MARINEW-P-I 11/12  SW 2/6 - Enable Zonal Alarms, SW 2/7- Pulse  Sounder circuits 3 & 4 on the control board and any output board sounder Non Alarm Zones: circuits are always delayed by 2-minutes. MODE SW 2/6 SW 2/7 ...
  • Page 23: List Of Linkc

    Link fitted Earth Fault Lower right hand corner of monitoring C1627 motherboard E/F monitoring disabled Link removed © 2012 Thorn Security Ltd PAGE 23 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 24: C1630 Output Interface

    T1216W-C MARINEW-P-I 11/12 Table 4 – Setting Quantity and Type of O/P DIL switch settings on the Modules on the C1630 Repeater Interface Board: DIL switch SW1 on the C1631 Repeater Interface C1630 Qty of PCB is used to set the quantity of repeaters and the board Type of board DIL Switch...
  • Page 25: Commissioning Procedure

    Remove the circuit faults, restoring the circuit o Press the Silence Alarms and the Reset © 2012 Thorn Security Ltd PAGE 25 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 26: Class Change Input

    T1216W-C MARINEW-P-I 11/12 buttons after each device test and check the 3. Initiate a fire condition on a zone to operate the alarm clears (Manual Call Points must be output. Check that the fire signal operates the manually reset before resetting the panel). interface relay adjacent to the fire protection equipment.
  • Page 27: Power Supply Unit

    24hrs to achieve a fully charged condition. long conductors or looms which might be prone to © 2012 Thorn Security Ltd PAGE 27 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 28 T1216W-C MARINEW-P-I 11/12 damage due to vibration of the panel enclosure. Check that all cables are firmly held in the terminal blocks & Earth bars. Check that the Earth Bars are SLEEVING firmly fixed to the enclosure. Check that all Earth RESISTOR ON LEAD leads are correctly &...
  • Page 29 Flashes when zone is in a fault condition. Illuminates Yellow Text steady when zone is disabled or in test. © 2012 Thorn Security Ltd PAGE 29 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 30: Ser Controls

    T1216W-C MARINEW-P-I 11/12 9. User Controls POWER SUPPLY ON MUSTER TEST DISPLAY FIRE ALARM FIRE OUTPUT ACTIVE SILENCE/ GENERAL FAULT RESOUND ENABLE ALARMS POWER SUPPLY FAULT SYSTEM FAULT RESET DISABLE EARTH FAULT FUSE FAILED SILENCE TEST BUZZER REPEATER FAULT SOUNDER FAULT/DISABLED DELAY SOUNDER TEST OVERRIDE...
  • Page 31: Pcb Layouts

    10. PCB Layouts Note: “Evacuate” or “Evac” = Manual Fire Alarm Figure 10 – C1627 Motherboard Layout © 2012 Thorn Security Ltd PAGE 31 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 32 T1216W-C MARINEW-P-I 11/12 Evacuate/Muster configuration Link: Buzzer Upper position: Evacuate mode Connector (manual fire alarm) Lower position: Muster mode Link removed: Evacuate & Muster modes disabled Keyswitch Connector Buzzer 9V Battery Connector Keyswitch Connector Motherboard Ribbon Cable Connector Figure 11 – Rear Right Hand Side of Display PCB SW1Config switch J3 Comms J2 Comms...
  • Page 33 S OUT - Silence signal out GND - Common 0V Figure 15 – C1665 Muster Interface Board © 2012 Thorn Security Ltd PAGE 33 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 34: Nstallation Details

    T1216W-C MARINEW-P-I 11/12 11. Installation Details Figure 16 – T1216W-C Installation Drawing PAGE 34 of 39...
  • Page 35: Wiring Diagrams

    Connections to Power Auxiliary 24Vdc Terminals Supply Unit Figure 17 – Mains AC Change-Over Unit Electrical Installation Diagram © 2012 Thorn Security Ltd PAGE 35 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 36 T1216W-C MARINEW-P-I 11/12 Figure 18 – T1216W-C Internal Layout Diagram PAGE 36 of 39...
  • Page 37 PUBLICATION: 11/12 ISSUE No. & DATE: Figure 19 – T1216W-C Motherboard, PSU & Repeater Wiring Diagram © 2012 Thorn Security Ltd PAGE 37 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...
  • Page 38 T1216W-C MARINEW-P-I 11/12 Figure 20 – Watermist Panel Wiring Diagram PAGE 38 of 39...
  • Page 39: Wiring Diagram Notes

     Buzzer Active Maximum current sink: 50mA @ 30Vdc Use 24V AUX DC output to power equipment. © 2012 Thorn Security Ltd PAGE 39 of 39 Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE...