TTL UBT plus User Manual

Control and automation panel for ttl air curtain

Advertisement

Quick Links

UBT
plus
Control and automation panel
for
TTL air curtain systems
User manual
Translated English version

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UBT plus and is the answer not in the manual?

Questions and answers

Summary of Contents for TTL UBT plus

  • Page 1 Control and automation panel TTL air curtain systems User manual Translated English version...
  • Page 2: Table Of Contents

    TTL air curtain systems - Control and automation panel UBT plus Content 1. Safety information 2. Fixing 3. Technical data 3.1 Technical data of control and automation panel UBT plus 3.2 Technical data of internal connecting board (PCB) 4. Quick start guide 5.
  • Page 3 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operating settings 9.1 Display of operating modes 9.2 Main menu 9.3 Menu 1 - Information menu 9.4 Menu 2 - Statistics 9.5 Menu 3 - Basic settings 9.6 Menu 4 - Analog input...
  • Page 4: Safety Information

    Original replacement parts and accessories approved by the manufacturer are designed for safety. When using other parts or in the event of failure to observe the TTL documentation, we decline all liability. In the event of any ambiguities regarding technology, handling or use, we expressly recommend checking with the manufacturer or his representative, citing the model designation.
  • Page 5: Fixing

    TTL air curtain systems - Control and automation panel UBT plus 2. Fixing The electronic control and automation panel UBT is made for wall mounting. The case is designed two- plus piece with a basic plate and an upper section with integrated electronic equipment.
  • Page 6: Technical Data

    TTL air curtain systems - Control and automation panel UBT plus 3. Technical data 3.1 Technical data control and automation panel UBT plus Electrical connection data line, factory ready-made with plugs in several lengths, 6-wire, lengths 6, 10, 20, 30, 50 m...
  • Page 7: Quick Start Guide

    TTL air curtain systems - Control and automation panel UBT plus 4. Qick start guide Connect the control lines resp. check them air curtain unit — control and automation panel UBT plus air curtain unit — infrared sensor (IR sensor) If necesarry.
  • Page 8: Application Possibilities - Basics

    TTL air curtain devices of all types and construction lengths. The used CAN bus technology affords the possibility to connect several units. Single units or groups of units can be adressed by coding.
  • Page 9: Operating Modes

    TTL air curtain systems - Control and automation panel UBT plus 6. Operating modes 6.1 OFF mode In the OFF mode the air curtain system is switched off, but in serviceability and can be activated for operation by actuation of the buttons MANUAL/HAND mode or AUTOMATIC mode...
  • Page 10: Automatic Mode

    TTL air curtain systems - Control and automation panel UBT plus 6. Operating modes (cont.) 6.3 AUTOMATIC mode 6.3.1 AUTOMATIC mode with inactive controller(s) In AUTOMATIC mode the air curtain unit will be switched-on or switched-off by an external conductor (door...
  • Page 11: Automatic Mode With Activated Controller(S)

    TTL air curtain systems - Control and automation panel UBT plus 6. Operating modes (cont.) 6.3.2 AUTOMATIC mode with activated controller(s) With adaquate installed acessories (motoric valve or motoric mixer, infrared sensor or room sensor) and sensor) one or both controllers can be activated in AUTOMATIC mode.
  • Page 12: Summer/Winter Mode

    TTL air curtain systems - Control and automation panel UBT plus 6. Operating modes (cont.) 6.4 SUMMER/WINTER mode The SUMMER/WINTER key switchover between an operation with activated heating battery (WINTER mode) or an operation without heating (SUMMER mode) manually. For using this function a selenoid valve or electrothermal valve have to be installed.
  • Page 13: Energy Saving Modes

    TTL air curtain systems - Control and automation panel UBT plus 6. Operating modes (cont.) 6.5 Energy saving functions For an especially and energy saving operation of air curtain system(s) ca be activated special functions: Temperature setback mode With activated blow-out controller the air blow-out temperature will be adjusted normally at a programm- of outside temperature or the heating up of inside a mall area.
  • Page 14: Image - Menu Illustrations - Used Symbols

    TTL air curtain systems - Control and automation panel UBT plus 7. Image - menu illustrations - used symbols 7.1 Overview operating elements 1 LCD display 2 MANUAL mode key 3 AUTOMATIC mode key 4 SUMMER/WINTER mode key 5 OFF(0) key 6 Display „Safe EEPROM“...
  • Page 15: Display Symbols

    TTL air curtain systems - Control and automation panel UBT plus 7.3 Display symbols OFF mode MANUAL AUTOMATIC mode mode (active air outlet symbol) controller activated Power indicator stepless, AUTOMATIC mode Power stepped, AUTOMATIC mode (in assoc. with AC fans)
  • Page 16: Menu Guidance -Menu Tree

    TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree The menu tree is showing a general listing of all functions and menu points available by controller .These documentation will expound every menu point.
  • Page 17: Setting Of Parameters

    TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree (cont.) 8.3 Setting of parameters Parameter value to change Press the „SELECT“ key to jump into the changing menu Quit submenu DDC enable GLOBAL...
  • Page 18 TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree (cont.) Main menu point Submenu Function Parameter / Default 1 Info menu Info Per unit adress display of: I/O status insertion status jumper at PCB...
  • Page 19 TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree (cont.) Main menu point Submenu Function Parameter / Default 2 Statistics for AC fans (statistics-history of notable switching occurences resp. faults) Per dialet internal connecting board (PCB) display of:...
  • Page 20 TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree (cont.) Main menu point Submenu Function Parameter / Default 3 Basic settings(cont.) Operation mess. active Switch over for operation message 0=NO / 1=YES „Ready for operation“...
  • Page 21 TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree (cont.) Main menu point Submenu Function Parameter / Default 0=NO / 1=YES for WINTER mode 0=NO / 1=YES for SUMMER mode Temperature WINTER Temperature setting WINTER mode 10-50 (°C)
  • Page 22: Displays And Basic Operating Settings

    TTL air curtain systems - Control and automation panel UBT plus 8. Menu guidance - menu tree (cont.) Main menu point Submenu Function Parameter / Default 9 Key lock Key lock -time Timing to start key lock 0=OFF / 1-30 (min) 0 Key lock -code Set code resp.
  • Page 23 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings 9.1 Display of operating modes 1 OFF mode Display of actual temperatures (if activated - see menu 3.15) T-nom: 21.0° EXT: 22.7° T-act = actual temperature, AIR = blowout temp. (not activ.) T-act: 20.5°...
  • Page 24 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.1 Display of operating modes (cont.) 5 AUTOMATIC mode, stepless, with timer Display of topical temperatures (controllers active) (T-nom = nominal value IR sensor, EXT = outside sensor, T-nom: 21.0°...
  • Page 25: Main Menu

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.2 Main menu 1 Info menu Main menu with 12 menu points 2 Statistics Selection of desired menu point with navigation cursor...
  • Page 26 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.3 Menu 1 - Information menu (cont.) 1 Information menu 3 Info -motors Information about status of motors/fans Info -motors 3 SELECT PARAMETER Submenu 3.1...
  • Page 27: Menu 2 - Statistics

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.4 Menu 2 - Statistics Statistics 2 Statistics menu 1 for EC fans Motor fault Statistics for: Frost alert Filter change :...
  • Page 28: Menu 3 - Basic Settings

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.5 Menu 3 - Basic settings 3 Basic settings menu 1 0180 Overrun time Time of overrun within the AUTOMATIC mode operation...
  • Page 29 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.5 Menu 3 - Basic settings (cont.) 3 Basic settings menu 7 Monitoring PCB‘s Determination of the number of PCB‘s in the bus group to...
  • Page 30 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.5 Menu 3 - Basic settings (cont.) 3 Basic settings menu 13 AUTO contact inverted Automatic contakt inverses, that means it react not as an Auto cont.
  • Page 31: Menu 4 - Analog Input

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.6 Menu 4 - Analogue input 4 Analogue input menu 1 Activation of air volume control via external control VOL via ext. 0-10V 0=OFF 1=GLO.
  • Page 32: Menu 5 - Blowout Temperature Controller Air

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.7 Menu 5 - Blowout temperature controller AIR 5 Blowout temperature controller (AIR) menu 1 WATER nominal standby WATER nom. standby 20-80...
  • Page 33 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.7 Menu 5 - Blowout temperature controller AIR (cont.) 5 Blowout temperature controller (AIR) menu 7 Setback -WINTER ON Setback -WINTER ON...
  • Page 34 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) enu 1 Activation of air volume controller for WINTER mode VOL WINTER ON 0=NO 1=YES 1 SELECT PARAMETER enu 2 Activation of air volume controller for SUMMER mode...
  • Page 35 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) enu 6 Reference value for SUMMER mode for units or groups of unit SUMMER Reference value with several sen sors, thereby the referenece is possible to: - min.
  • Page 36: Menu 7 - Sensor Adjustment

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.9 Menu 7 - Sensor correction 7 Sensor correction menu 1 EXTERN sensor correction - AIR Correction value for blow-out temperature controllers sensor EXTERN sensor corr.
  • Page 37: Menu 8 - Clock

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.10 Menu 8 - Clock 8 Clock menu 1 Timer Effect of timer for operating modes -only AUTOMATIC mode Timer 0=OFF 1: AUTO...
  • Page 38 TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.10 Menu 8 - Clock (cont.) 8 Clock menu 4 Timer adjust Using the „SELECT“ key opens the submenu for timer Timer adjust...
  • Page 39: Menu 9 - Key Lock

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.11 Menu 9 - Key lock 9 Key lock menu 1 Key lock -time Default time until automatic activation of key lock...
  • Page 40: Menu 10 - Lcd (Display Settings)

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.12 Menu 10 - LCD (display settings) 10 LCD menu 1 LCD -brillinace Changing display contrast LCD -brilliance 30-60 1 SELECT PARAMETER...
  • Page 41: Menu 11 - Language

    TTL air curtain systems - Control and automation panel UBT plus 9. Displays and basic operation settings (cont.) 9.13 Menu 11 - Language English 11 Language menu 1 Language Choose of display language Language 1 SELECT PARAMETER English Submenu 1.1...
  • Page 42: Connecting Device - Start Up

    TTL air curtain systems - Control and automation panel UBT plus 10. Connecting device - start up 10.1 Internal connecting board (PCB) The internal connecting board is implemented inside of the air curtain unit. External control contacts like e.g. DDC enable, door contact etc. will be connected at these internal connecting board.
  • Page 43: Connecting Control Panel

    OFF(0) button and to restart renewed. The motor fault will be collect statisti- cally and is accessible by menu 2.1 (Statistics). In case of recurring motor faults pleas contact the TTL service immidiately. Shut-up after frost alert (only with a implemented frost alert thermostat) - a restart after frost alert Aut.start after frost).
  • Page 44: Grouping - Adressing

    TTL air curtain systems - Control and automation panel UBT plus 11. Grouping - adressing by programming. The adresses are free selectable up 1 to 9 and will be determined at the internal connecting board. All recognised air curtain units will be listed by its internal connectiong boards in the respective menus and shown by their adress.
  • Page 45: Malfunctions

    TTL air curtain systems - Control and automation panel UBT plus 12. Malfunctions 12.1 Fault visualization Display safe EEPROM nent illuminated the memory is defective. In this case please contact the manufacturer of the air curtain unit by CAN bus failure The databus fault (CAN bus fault) is signalized via a yellow LED below the symbol „CAN bus fault“.
  • Page 46: Fault Clearance

    (common fault message). In case of a fan/motor fault please contact your service company or the TTL service. Remedy the cause of the error and unlock via the OFF(0) key. To avoid a demage don‘t set the air curtain system in operation without consultation of the manufacturer TTL.
  • Page 47: Eu Declaration Of Conformity

    In the event of any questions, please contact the manufacturer at the address above. TTL GmbH reserves the right to undertake any change or improvement to parts or their acces- sories without the obligation to update earlier products and existing documentation.
  • Page 48: Manufacturer, Contact, Service Adress

    TTL Torluftschleier GmbH Fabrikstraße 3 • 73650 Winterbach Fon +49 (0) 71 81 / 40 09 - 0 Fax +49 (0) 71 81 / 40 09 - 10 info@luftschleier.de • www.luftschleier.de...