ESC PGEN-30 Manual

ESC PGEN-30 Manual

Ecs protector nitrogen generator

Advertisement

Quick Links

For use under U.S. Patents
8,720,591, 9,144,700 and 9,186,533

Ordering Information

Stock Number:
PGEN-30 (PGEN-30E)
Replacement Filters:
PGEN-FKS - Annual Maintenance
Gas Membrane:
PGEN-MS - 20 Year Expected Service Life)

General Description

The ECS Protector Nitrogen Generator is designed for
use in maintaining supervisory gas and facilitating the
Dry Pipe Nitrogen Inerting (DPNI) process for
controlling oxygen corrosion in dry and pre-action fire
sprinkler systems.
The ECS Protector is an on-site
nitrogen generation system that is designed to be
installed inline between the compressed air supply
and the sprinkler system riser in dry or preaction pipe
sprinkler systems. The nitrogen generator utilizes
Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com
ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)
ECS Protector Nitrogen Generator
PGEN-30 (PGEN-30E)

Specifications

Dimensions (cabinet):
Dimensions (incl. bypass): 32.5"(W) x 52.5"(H) x 8.5"(D)
Weight:
Temperature Range:
Power Supply:
Power Consumption:
Gas Connections:
Drain Connection:
membrane gas separation technology that exhausts
oxygen as a waste gas to produce 98%+ nitrogen on
demand with no nitrogen storage necessary for dry or
preaction systems.
The ECS Protector Nitrogen Generator cabinet has an
external bypass valve to allow for nitrogen generator
maintenance or "fast fill" needs, and is designed to
meet the NFPA 13 30-minute fill requirement for dry
pipe or preaction fire protection systems.
1
ECS Protector
Nitrogen Generator
designed for fire sprinkler systems
24.5"(W) x 52.5"(H) x 8.5"(D)
(622mm(W) x 1,334mm(H) x 216mm(D))
(826mm(W) x 1,334mm(H) x 216mm(D))
152 Lbs (69 Kg)
40°F - 105°F (5°C - 40°C)
120v/1 phase/60Hz - Dedicated Circuit
(230v/1 phase/50Hz - Dedicated Circuit)
2 Amps
Air Inlet - ½" NPT Female
Nitrogen Outlet - ½" NPT Female
¼" NPT Female
UL 508A Listed Industrial Control Panel
June 2018 - Rev 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PGEN-30 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ESC PGEN-30

  • Page 1 NFPA 13 30-minute fill requirement for dry sprinkler systems. The nitrogen generator utilizes pipe or preaction fire protection systems. Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com June 2018 - Rev 5 ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)
  • Page 2 3 psig within a 24 hour period, per system. Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) June 2018 - Rev 5...
  • Page 3 The preferred AMD is the Victaulic Series 757. Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) June 2018 - Rev 5...
  • Page 4 Monitoring Output Nitrogen Generator Leak Monitoring Output Nitrogen Generation Power Monitoring Output Monitoring Output Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) June 2018 - Rev 5...
  • Page 5 In some environments it may be necessary to replace filters more frequently. The filter kit for the PGEN-30 (PGEN-30E) is part number PGEN-FKS. When maintained properly the nitrogen separation membrane will provide up to 20 years of service life.
  • Page 6 Step 6: Repeat Step 1 through Step 5 for each additional filter. Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) June 2018 - Rev 5...
  • Page 7 Engineered Corrosion Solutions  11336 Lackland Road  St. Louis, MO 63146  Phone 1-314-432-1377 www.ecscorrosion.com ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) June 2018 - Rev 5...
  • Page 8 Wall Mount Skid Mount Stand Alone w/Separate Air Compressor PGEN-3 PGEN-5 PGEN-10 PGEN-20 PGEN-30 PGEN-40 PGEN-50 PGEN-60 Total System Capacity 675 gal 950 gal 2,000 gal 3,200 gal 6,500 gal 11,000 gal 18,500 gal 22,500 gal Single System Capacity @ 40 psi...

This manual is also suitable for:

Pgen-30e

Table of Contents