BREAK-AWAY FIRE HYDRANT TYPE 8003 Approved for use by President of Factory, JAFAR S.A. Failure to comply with the guidelines and instructions in this Operation and Maintenance Manual releases the manufacturer from all obligations, liability and guarantee. Due to continuous business development, we reserve the right to introduce modifications and structural changes to the presented product.
360 1.2 PURPOSE Break-away fire hydrants TYPE 8003 with double closure are intended for fire protection systems, for chemically neutral pure water, free of impurities and for industrial systems. For use on above-ground installations on pipelines laid horizontally below the freezing zone.
Page 4
thinner bolts. Such a connection enables breakage of hydrant without damaging it and resulting water outflow. Special flanges enable free rotation of the ground part of the hydrant from 0° to 360°. There is a special articulation spindle inside the hydrant, in the connection area of the above ground and underground part of the hydrant.
Page 5
Operation diagram for hydrant TYPE 8003 DN80 CLOSE OPEN OPERATION AND MAINTENANCE MANUAL 12-2015...
Page 6
Operation diagram for hydrant TYPE 8003 DN100 CLOSE OPEN The order of operations during opening and closing of a hydrant type 8003 configured with a shutoff gate valve. - Starting: 1. Open the shutoff gate valve. 2. Open the hydrant.
2.4 MATERIALS DN100 List of basic materials used for the construction of an overground hydrant TYPE 8003 DN100 — see table Item Part name Material Reference standard Cast-iron, EN-GJS 400-15 Main body PN-EN1563: 2012 EN-GJS500-7 Cast-iron, EN-GJS 400-15 Lower body...
2.6 STANDARDS PN-EN 1074-1: 2002 Valves for water supply. Fitness for purpose requirements and appropriate verification tests. General requirements PN-EN 1074-6: 2009 Valves for water supply. Fitness for purpose requirements and appropriate verification tests. Hydrants. PN-89/H-02650 Fittings and pipelines. Pressures and temperatures. PN-EN 19:2005 Industrial valves.
The above-round hydrants are accepted and produced in accordance with: PN-EN 1074-6:2009 (Valves for water supply. Fitness for purpose requirements and appropriate verification tests. Hydrants.) and PN-EN 14384:2009 (Above-ground fire hydrants.) All hydrants (100%) are subject to tightness testing. The tests include external body tightness and closing tightness.
4 ASSEMBLY AND INSTALLATION 4.1 INSTALLATION GUIDELINES Above-ground fire hydrants TYPE 8003 may be installed on underground pipelines in case of horizontal systems. The products described herein are designed for installation using flange on the pipeline acting as medium (water) supply. The hydrant is equipped with special flanges to enable free above-ground part's rotation ο...
4.2 INSTALLATION INSTRUCTIONS Before installing the hydrants, check the technical and commercial documentation, i.e. application for media and operation parameters of the pipeline, in which they are to be installed. Note! If the product is damaged mechanically, do not install it in the pipeline. Any change in the operating conditions must be consulted with the hydrant's manufacturer beforehand.
4.3 OPERATION The outdoor hydrants are designed for drawing fire fighting water. Detailed requirements are given in applicable regulations defining the need for fire fighting water. The diagram above shows an example installation method for an above-ground hydrant, the installation method largely depends on the applied rules based on the local climate and geologic conditions.