MANUFACTURER'S STATEMENT
MANUFACTURER'S STATEMENT
Read this operation manual carefully before use to ensure proper operation of this product.
Failure to read this operation manual may cause improper operation and may result in serious injury or
death of a person.The meanings of the symbols are as follows.
Disregard of warning may cause the improper operation causing death or serious injury of
WARNING
a person.
Disregard of caution may cause the improper operation causing injury of a person or damage to
CAUTION
objects.
NOTE
Special attention is required to the section of this symbol.
It is required to check the operation manual if this symbol is shown on the product.
NOTE
1. This product is a non-contact switch intended for header mount or wall mount for use on an automatic sliding door.
Do not use for any other applications.
2. When setting the sensor's detection area, make sure that there is no traffic around the installation site.
3. Before turning the power ON, check the wiring to prevent damage or malfunction of equipment connected to
the product.
4. Only use the product as specified in the operation manual provided.
5. Be sure to install and adjust the sensor in accordance with the local laws and standards of the country in which
the product is installed.
6. Before leaving the installation site make sure that the product is operating properly and instruct the building
owner/operator on proper operation of the door and the product.
7.The product settings can only be changed by an installer or service engineer. When changed, the
changed settings and the date shall be registered in the maintenance logbook accompanying the door.
WARNING
Do not wash, disassemble, rebuild or repair the sensor, otherwise
it may cause electric shock or breakdown of the equipment.
Danger of electric shock.
NOTE
The following conditions are not suitable for sensor installation.
-Fog or exhaust emission around the door.
-Wet floor.
-Vibrating header or mounting surface.
-Moving objects or objects that emit light near the detection area.
-Highly reflecting floor or highly reflecting objects around the door.
SPECIFICATIONS
Model
: OA-AXIS T
Cover color
: Silver / Black
Mounting height
: 2.0 (6'7") to 3.0m (9'10")
Detection area
: See DETECTION AREA
Detection method
: Active infrared reflection (*1 )
Depth angle
: 1st to 3rd rows / -6 to +6°
adjustment
4th and 5th rows / +26 to +44°
Power supply (*2 )
: 12 to 24VAC ±10% (50 / 60 Hz)
12 to 30VDC ±10%
Power consumption
: < 2.5W (< 4VA at AC)
Operation indicator
: See chart below
Safety input
: Opto coupler
Voltage / 5 to 30VDC
Current / 6mA Max. (30VDC)
Safety output
: When 1st or 2nd row detects.
Opto coupler (NPN)
Voltage / 5 to 50VDC
Current / 100mA Max.
Dark current / 600nA Max.
(Resistance load)
*1 : The 1st and 2nd rows have presence detection function.
*2 : When using this sensor, the sensor has to be connected to a door system which has the SELV circuit.
*3 : Overcurrent protection with less than 2A.
Operation indicator
Status
Operation indicator color
Stand-by (Installation mode)
Stand-by (Operation mode)
1st row detection
Blinking Red
2nd row detection
3rd, 4th or 5th row detection
Setting error
Red & Green Blinking
Signal saturation
Slow Green Blinking
Sensor failure
Fast Green Blinking
NOTE
The specifications herein are subject to change without prior notice due to improvements.
OUTER DIMENSIONS AND PART NAMES
267(10 1/2")
125(4 15/16")
36(1 7/16")
43(1 11/16")
(1)
(2)
1st to 3rd rows
4th and 5th rows
Width
Depth
Depth
9
10
11
12
ON
Disable
Low
Low
L
R
OFF
Enable
High
High
-6
°
6
°
26
°
44
°
1,2
3,4
5,6
7,8
Low
30sec.
Setting 1
5 rows
Narrow
Middle
60sec.
Setting 2
4 rows
35°
13
14
Shallow
Deep
High
180sec.
Setting 3
3 rows
20msec.
N.C.
-3°
2 rows
10msec.
N.O.
Wide
S-High
600sec.
Setting 4
30°
40°
-6°
26°
44°
(3)
(4)
(5)
ENGLISH
Activation output
: When 3rd, 4th or 5th row detects.
Form A relay
50V 0.3A Max. (Resistance load)
Operating temperature
: -20 to +55°C (-4 to 131°F)
Operating humidity
: <80%
Noise level
: <70dBA
Output hold time
: <0.5 sec.
Response time
: <0.3 sec.
IP rate
: IP54
Category
: 2 (EN ISO 13849-1 : 2008)
Performance level
: d (EN ISO 13849-1 : 2008)
ESPE
: Type2
Weight
: 320g (11.2oz )
Accessories
: 1 Operation manual
2 Mounting screws
1 Mounting template
1 Area adjustment tool
1 Cable 3m (9'10")
(8 × 0.22mm² AWG24 ) (*3 )
1sec.
Yellow
Green
Red
Orange
45(1 3/4")
[mm (inch)]
(9)
(1) Connector
(2) Mounting holes
(3) Operation indicator
Width
Function
switch
Function switch
16
After changing the dipswitches
ON
settings,make sure to push the
L
R
Not
(4) Depth angle adjustment screw
function switch for 2 seconds.
OFF
applicable
1 2 3 4
5
6 7 8
9 10 11 12
13
14
15
16
Narrow
(5) Width adjustment screws
Wide
5730870
(6) Function switch
(7) Dipswitches
(8) Detection window
(9) Area adjustment tool
(6)
(7)
(8)
COMPLIED STANDARDS
AND EXTRACT FROM EC DECLARATION OF CONFORMITY
EN 16005:2012 Chapter 4.6.8 and Annex C
EMC Directive 2004/108/EC
EN 61496-3:2001 clause 4. 3. 5 and 5. 4. 7. 3
Notified Body 0044 : TÜV NORD CERT GmbH Langemarckstr. 20 45141 Essen Germany
EC-type examination certificate No. 44 205 13 099205
Technical documentation see manufacture address
DETECTION AREA
A
1st row
Motion / Presence
detection
2nd row
3rd row
Motion detection
4th row
5th row
Emitting area
A
2.00 (6'7")
B
0.13 (5")
C
0.38 (1'3")
D
0.74 (2'5")
E
1.23 (4')
F
1.74 (5'9")
G
1.06 (3'6")
H
1.86 (6'1")
I (*)
2.52 (8'3")
X
0.19 (7")
X is the distance between the 1st row and the mounting surface.
Detection area
To comply with EN 16005, make sure that the detection area is within the values in the chart below.
A
2.00 (6'7")
C
0.23 (9")
G
1.02 (3'4")
I
2.41 (7'11")
The values above are those of the Detection area when tested referring to the test conditions of EN 16005.
(The emitting area is as shown in Emitting area above.)
*: When installed at higher than 2.35m(7'9"), EN 16005 requirements are fulfilled only within the area width "I"
of 3m(9'10").
NOTE
The actual detection area may become smaller depending on the ambient light, the color / material of
the object or the floor as well as the entry speed of the object.
The sensor may not be activated when the entering speed of the object or a person is slower than
50mm / sec. or faster than 1500mm / sec.
INSTALLATION
1
1. Affix the mounting template at the desired mounting position.
(When setting the detection area close to the door, mount the sensor according to the chart below.)
2. Drill two mounting holes of ø3.4mm (ø1/8").
3. To pass the cable through the header, drill a wiring hole of ø8mm (ø5/16").
4. Remove the mounting template.
5. Remove the housing cover. Fix the sensor to the mounting surface with the two mounting screws.
Header
Sensor
Y
X
H
Door
1sec.
Floor
CAUTION
Risk of getting caught.
2
To the connector
of the sensor
WARNING
Danger of electric shock.
3
1.Plug the connector of the sensor.
2.Supply power to the sensor. Adjust the detection area and set the dipswitches. (See ADJUSTMENTS)
NOTE
Make sure to connect the cable correctly to the door controller before turning the power ON.
When turning the power ON or after adjusting the settings, do not enter the detection area for more
than 10 seconds in order to enable the presence detection.
Do not touch the dipswitches before turning the power ON, otherwise an error occurs.
When changing the settings of dipswitch, see ADJUSTMENTS 3 Dipswitch settings.
4
Place the housing cover.
If wiring is to be exposed, break the knockout.
WARNING
Danger of electric shock.
EN 12978:2003 +A1:2009
EN ISO 13849-1:2008
EN 61000-6-2:2005
Charts show the values in the following
G
G
depth angle adjustment settings ;
H
1st to 3rd rows
I
4th and 5th rows : +44°
2.20 (7'3")
2.50 (8'2")
0.14 (6")
0.16 (6")
0.42 (1'5")
0.48 (1'7")
0.82 (2'8")
0.93 (3'1")
1.35 (4'5")
1.54 (5'1")
1.90 (6'3")
2.17 (7'1")
1.33 (4'4")
1.51 (4'11")
2.05 (6'9")
2.32 (7'7")
2.78 (9'1")
3.15 (10'4")
0.21 (8")
0.24 (9")
Test conditions required by EN 16005
2.20 (7'3")
Floor :Grey paper
0.24 (9")
Detection object : EN 16005 CA reference body
1.10 (3'7")
Sensitivity : Middle
2.54 (8'4")
Speed of detection object : 50mm / sec.
H : Height from the floor to the bottom of the header
(The mounting height is "H + Y".)
Y : Distance between the bottom of the header and the sensor
X : Distance between the door and the mounting surface
Maximum mounting distance (Y)
H
X
2.30 (7'7")
2.50 (8'2")
2.00 (6'7")
No limit
0
0.20 (8")
0.05 (2")
0.20 (8")
0.20 (8")
0.10 (4")
0.20 (8")
0.15 (6")
0.13 (5")
0.15 (6")
0.12 (5")
0.20 (8")
-
-
-
0.25 (10")
-
0.30 (12")
-
NOTE
Make sure not to mount the sensor lower than the bottom of header.
Make sure to affix the mounting template as described in the above chart ,
otherwise it can be dangerous since there may be no detection area around
the threshold. Install the sensor as low as possible on the header.
1.White
Power supply
}
2.Brown
12 to 24VAC±10% /12 to 30VDC±10%
3.Green
Activation output
4.Yellow
Form A relay 50V 0.3A Max.
5.Pink (+)
Safety output
6.Blue (-)
Opto coupler(NPN) / Voltage: 5 to 50VDC
7.Red (+)
Safety input
8.Black (-)
Opto coupler / Voltage: 5 to 30VDC
Before starting the procedure, make sure that the power is turned OFF.
When passing the cable through the hole, do not tear the shield.
otherwise it may cause electric shock or breakdown of the sensor.
Do not use the sensor without the cover.
When using the cable knockout, install the sensor indoors or use the rain-cover
(Separately available) otherwise electric shock or breakdown of
the sensor may occur.
Machinery Directive 2006/42/EC
EN ISO 13849-2:2012
EN 61000-6-3:2007 +A1:2011
A. Maekawa
General Manager
OPTEX CO., LTD.
Quality Control Dept.
: Emitting spots
: Emitting spots
(Can be eliminated)
: Detection Area
B
C
D
E
F
: +6°
[m(feet,inch)]
2.70 (8'10")
3.00 (9'10")
0.18 (7")
0.20 (8")
0.52 (1'8")
0.58 (1'11")
1.00 (3'3")
1.10 (3'7")
1.66 (5'5")
1.85 (6'1")
2.34 (7'8")
2.60 (8'6")
1.63 (5'4")
1.81 (5'11")
2.51 (8'3")
2.79 (9'2")
3.40 (11'2")
3.79 (12'5")
0.26 (10")
0.28 (11")
[m (feet,inch)]
3.00 (9'10")
2.80 (9'2")
0.20 (8")
0.20 (8")
0
0.20 (8")
0.20 (8")
0
0.19 (7")
0.20 (8")
0
0.14 (6")
0.15 (6")
0
0.11 (4")
0.12 (5")
0
-
-
-

Advertisement

loading

Summary of Contents for Optex OA-AXIS T

  • Page 1 The sensor may not be activated when the entering speed of the object or a person is slower than 50mm / sec. or faster than 1500mm / sec. SPECIFICATIONS Model : OA-AXIS T INSTALLATION Cover color : Silver / Black Activation output : When 3rd, 4th or 5th row detects.
  • Page 2 European Subsidiary Set dipswitch 9 to "ON" when the sensor operates by itself (Ghosting). OPTEX Co.,LTD. OPTEX Technologies B.V. NOTE When dipswitch 9 is set to "ON", the actual detection area may become smaller. Henricuskade 17, 2497 NB The Hague,The Netherlands 5-8-12 Ogoto Otsu 520-0101, Japan TEL.: +31(0)70-419-4100...