ACURT2 and ACURT4 Information Packet Description: Device Name: Polling Address: Serial Port Number: Dial-Up Phone Number: IP Address: IP Router Address: This information packet is for reference only. See the TOPAZ Hardware Installation Guide for complete instructions. UTC Fire & Security 9 Farm Springs Road, Farmington, CT 06034-4065 (888) 437-3287...
DIP Switch SW1 Settings Note: See page 11 for switch location. Switch ON Position = Terminated – OFF Position = Not Terminated Host TX Line Terminated Host RX Line Terminated Expansion Module Port TX Line Terminated Expansion Module Port RX Line Terminated Current Switch Setting SW 1 Circle the current setting...
ACURT2 and ACURT4 Information Packet DIP Switch SW2 Settings Note: See page 11 for switch location. Switch Switch Setting Function Host Communication Baud Rate OFF OFF 19200 OFF OFF 38400 57600 1200 115200 through 2400 4800 9600 Host Encryption disabled Host Encryption enabled Dial-up Host Communications Dedicated Host Communications...
Page 7
Current Switch Setting SW 2 Circle the current settings...
ACURT2 and ACURT4 Information Packet DIP Switch SW3 Settings Note: See page 11 for switch location Switch Description OFF = LAN Disabled ON = LAN Enabled OFF = Do Not Allow LAN IP Parameters to be Updated ON = Allow LAN IP Parameters to be Updated OFF = Do Not Use LAN default IP Parameters ON = Set IP Address To 192.168.0.132 OFF = Triple DES Disabled...
Rotary Switch SW4 Setting Note: See page 11 for switch location Function - Sets the ACURT polling (rotary) address Current Setting 0 - F Address 0-F DIP Switch SW5 Settings Note: See page 11 for switch location ON POSITION = terminated – No Input Device Off Position = Not Terminated –...
ACURT2 and ACURT4 Information Packet DIP Switch SW6 (ACURT4 Only) Note: See page 11 for switch location ON POSITION = terminated – No Input Device Current Off Position = Not Terminated – Zone In Use Setting Terminates Zone Input Reader 2 Zone 0 Terminates Zone Input Reader 2 Zone 1 Terminates Zone Input Reader 2 Zone 2 Terminates Zone Input Reader 3 Zone 0...
Clearing the Memory on the ACURT CAUTION: Before clearing memory you should record all switch settings. This will assist you in setting them back to their original locations after clearing the memory. Note: See page 11 for switch and LED locations. To clear memory: 1.
ACURT2 and ACURT4 Information Packet Power-Up Self-Test The Controller should always be tested after installing any module. The power-up self-test indicators are LEDs on the printed circuit board assembly. At power up, all of the LEDs will light, then all turn off. The LEDs will light as follows (at power- up): all ON at hardware reset, then all OFF.
Note: See page 11 for LED locations Description ON if zone monitor voltage reference is ever out of range LED 4 (indicates board or power supply failure). On-Line LED Definitions LAN Status LEDs Description ON When transmitting. ON When receiving. ON When collision occurs.
ACURT2 and ACURT4 Information Packet Battery Replacement Replace RAM back-up battery every five years using 3 AAA Nickel-Cadmium. Replace the clock/calendar battery every five years with 1 CR2023 Lithium or the equivalent. Replace the UPS batteries as needed. Always replace both batteries: 12 volt, 1.2 amp hour (Ah) Gel Cell.
ACURT2 and ACURT4 Component Layout Attach to Grounding Stud in Panel LAN Status Optional dial-up LEDs Modem Card LAN Port TB10 POWER SWITCH LINK EXP. MODULE COMMUNICATION TRANSMIT DATA LED +5VDC LEDS +3.3VDC HOST PORT LED1 TB11 RECEIVE DATA LED +12VDC LED3 AC ON...