Intelligent plug-in temperature sensors

Advertisement

offer maximum performance when tested and maintained in compliance with
NFPA 72.
A.
Test Magnet (p/n M02-04-01 or M02-09-00)
1. Place the optional test magnet against the cover in the magnet test
area, as shown in Figure 3, to activate the test feature.
2. The LEDs should latch on within 10 seconds, indicating alarm and
annunciating the panel.
3. Reset the detector at the system control panel.
B.
Direct Heat Method (Hair dryer of 1000 – 1500 watts)
1. From the side of the detector, direct the heat toward the sensor. Hold
the heat source about 6 inches (15 cm) away to prevent damage to the
cover during testing.
2. The LEDs on the detector should light when the temperature at the
detector reaches the alarm set point. If the LEDs fail to light, check the
power to the detector and the wiring in the detector base.
3. Reset the detector at the system control panel.
Detectors that fail these tests should be cleaned as described under MAIN-
TENANCE and retested. If the detectors still fail these tests, they should be
returned for repair.
Please refer to insert for the Limitations of Fire Alarm Systems
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FL-400-001
FIGURE 3. VIEWS SHOWING POSITION OF TEST MAGNET:
TEST MAGNET
MARKER
LED
MAINTENANCE
NOTE: Before cleaning notify the proper authorities that the system is under-
going maintenance, and therefore the system will temporarily be out of ser-
vice. Disable the loop or system undergoing maintenance to prevent unwanted
alarms.
It is recommended that the sensor be removed from its mounting base for
easier cleaning and that sensors be cleaned at least once a year. Use a vacuum
cleaner to remove dust from the sensing chamber.
FIGURE 4:
FCC STATEMENT
2
TEST
MAGNET
MARKER
LED
I56-3657-002R
©2008 Fire-Lite
C0152-00
C0151-00