Operation and Maintenance
Manual
 
 
 
GDS‐48 Remote Bridge Sensor for Combustible Gases, VOCs and CO2
 
 
 
 
 
GDS Corp. 
1245 Butler Road       League City, TX    77573 
409‐927‐2980     409‐927‐4180 (Fax)     www.gdscorp.com 
 

Advertisement

Table of Contents
loading

Summary of Contents for GDS Corp GDS-48

  • Page 1       Operation and Maintenance Manual       GDS‐48 Remote Bridge Sensor for Combustible Gases, VOCs and CO2           GDS Corp.  1245 Butler Road       League City, TX    77573  409‐927‐2980     409‐927‐4180 (Fax)     www.gdscorp.com   ...
  • Page 2 GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0       CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING OR SERVICING. ATTENTION: POUR DES RAISONS DE SÉCURITÉ, CET ÉQUIPEMENT DOIT ÊTRE UTILISÉ, ENTRETENU ET RÉPARÉ...
  • Page 3: Table Of Contents

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   CONTENTS      SAFETY INFORMATION .............................  4     GENERAL INFORMATION ............................  5    ..............................  5 ATALYTIC BEAD SENSORS     .................................  5 NFRARED  ENSORS    .................................  5  SENSORS     SPECIFICATIONS  ................................  6  ...
  • Page 4: Safety Information

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 1 SAFETY INFORMATION    Important – Read Before Installation  Users should have a detailed understanding of GDS‐48 operating and maintenance instructions.  Use the GDS‐48  only as specified in this manual or detection of gases and the resulting protection provided may be impaired.  Read  the following WARNINGS prior to use.  WARNINGS   The GDS‐48 sensor transmitter described in this manual must be installed, operated and maintained in  accordance with information contained herein. Installation in any hazardous area must comply with all  applicable restrictions, requirements and guidelines for said hazardous areas. It is the end user customer’s  final decision to ensure that the GDS‐48 is suitable for the intended use.    The GDS‐48 is designed and constructed to measure the level of certain gases in ambient air. Accuracy in  atmospheres containing steam or inert gases cannot be guaranteed.   Always mount the sensor head vertically with the sensor head facing down.    Do not paint sensor assembly.    Do not operate the GDS‐48 if its enclosure is damaged or cracked or has missing components. Make sure  the cover, internal PCB’s and field wiring are securely in place before applying power.   Do not expose the GDS‐48 to electrical shock or continuous severe mechanical shock. Protect the GDS‐48  and related sensor assemblies from dripping liquids and high power sprays.   Calibrate with known target gas at start‐up and check on a regular schedule, at least every 90 days.  More  frequent inspections are encouraged to spot problems such as dirt, oil, paint, grease or other foreign  materials on the sensor head. ...
  • Page 5: General Information

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   2 GENERAL INFORMATION    The GDS‐48 Remote Bridge Sensor is designed to support remote sensors with bridge‐style output signals that are  suitable for transmission over long distances.  The GDS‐48 is ideally suited for installation where reliability and cost  are critically important and where a local display is not required.    Three‐wire bridge‐style output compatible with GDS Corp controllers.   Certified for use in Class I Division 1, Groups B, C & D hazardous areas   Easily‐replaceable sensor element   Fault indication for sensor fail or missing sensor (at controller)   Constructed of 316 stainless steel   Reliable catalytic bead , infrared or photoionization sensor technology    CATALYTIC BEAD SENSORS  are the most cost effective solution for the detection of combustible gases.  Catalytic bead sensors are comprised of two independent ‘beads’ that are wrapped with a special wire that varies  in resistance based on changes in temperature. One bead is coated with a material (“catalyst”) that promotes the  burning of any combustible gas that may be present. During operation, an excitation voltage applied to the sensor  raises the temperature of both beads to a pre‐specified value. When gas is present, the temperature of the bead  with the catalyst coating increases. This changes the ratio of resistance between the two beads and indicates the  presence of gas. To operate properly, catalytic bead sensors must be installed and balanced for zero when no gas is  present.    ...
  • Page 6: Specifications

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 3 SPECIFICATIONS    Model:  GDS Corp Remote Bridge Sensor for Combustible Gases and Carbon Dioxide  Power Input:  Excitation voltage, dependent on sensor Display:  None  Input:  Direct connect bridge sensors for combustible and CO gases. Accuracy:  +/‐ 5% of full scale (typical) Calibration:  Output is factory adjusted but is not calibrated. Receiving device must provide zero  and span (two‐point) calibration. The GDS‐48 is compatible with all GDS Corp  controllers with bridge‐style inputs that provide two‐point calibration capability.   Output:  Millivolt bridge‐style outputs Response Time:  Determined by sensor type and range Temperature:  See individual sensor temperature specifications Fault Indication:  Provided by controller or receiver Housing:  Junction box epoxy‐coated aluminum, sensor head 316 stainless steel.    Approvals:   CSA Class 1, Division 1, Groups B, C and D Explosion Proof with flame arrestor;...
  • Page 7: Figure 3-1: Recommended Sensor Temperature Ranges And Excitation

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0       Sensor  Range Temperature Excitation Voltage*  50  Methane  0‐100 % LEL ‐20°C to + 50°C 4.5 VDC @ 80 mA  51  Propane  0‐100% LEL ‐20°C to + 50°C 4.5 VDC @ 80 mA  52  Methane  0‐100% v/v ‐20°C to + 50°C 4.5 VDC @ 80 mA  53  Carbon Dioxide  Multiple ‐20°C to + 50°C 4.5 VDC @ 80 mA  57  Ethylene Oxide  0‐100% LEL ‐20°C to + 50°C...
  • Page 8: Installation

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 4 INSTALLATION    CHOOSING A LOCATION  Factors such as air movement, gas density, emission sources and environmental variables affect sensor location.   Air movement by fans, prevailing winds and convection should be carefully evaluated to determine if a leak is more  likely to raise gas levels in certain areas within the facility.  Vapor density of a gas determines if it will rise or fall in  air when there are no significant currents.  Lighter than air gases should have the monitors mounted 12 – 18 inches  (30 – 45 cm) above the potential gas leak and heavier than air gases should be this distance below.  Even though  the GDS‐48 sensor transmitter is designed for rugged service, it should be protected from environmental damage  from water, snow, shock, vibration and dirt.  The GDS‐48 should always be mounted with the sensor head opening facing down. If necessary, a Splash Guard  (p/n 10‐0205) should be attached if there is any chance that water or liquid spray could enter the sensor opening  from below.  Be sure to leave sufficient room (~ 12”) below the sensor head to allow easy access for attachment of  a Calibration Cup and / or removal of the sensor head cover for sensor replacement.     Gray Enclosure  Yellow Enclosure    S—R—C  R—C—A  TB1   USE R‐C‐A for COMBUSTIBLE, CO2 or PID SENSOR  USE S‐R‐C for OXYGEN or TOXIC GAS SENSOR      Figure 4-1: GDS-48 Remote Bridge Sensor...
  • Page 9: Electrical Connections

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   ELECTRICAL CONNECTIONS  The GDS‐48 is a three‐wire bridge‐type sensor that requires excitation voltage and outputs a millivolt‐level signal  to the remote controller or receiver. Incorrect wiring can result in sensor damage or sensor failure.     S—R—C  R—C—A  USE R‐C‐A for COMBUSTIBLE, CO2  or  PID  SENSOR  USE S‐R‐C for OXYGEN or TOXIC GAS  SEN‐ SOR  Three‐wire connection  “R”  “C”  to remote receiver or  “A”  controller      Figure 4-2: GDS-48 Wiring Connections (Gray Enclosure)  ...
  • Page 10 GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 Shielded cable is always recommended.  Wiring should be installed in metal conduit with no other cabling in the  same conduit. When power is initially applied to the GDS‐48 the output may momentarily indicate a temporary off‐ scale low (FAULT) or off‐scale high (OVERRANGE) value before settling down. All GDS Corp controllers provide a  ‘warm up’ interval during which the sensor input is ignored. This keeps the controller from indicating an alarm due  to sensor warm‐up characteristics.   Total warm‐up time is dependent on the type of sensor and range selected. GDS Corp recommends a four to eight  hour interval between initial power‐on and first calibration. If the sensor has been powered up, and has only been  offline for a few hours, the warm‐up time will be shorter.     GDS Corp Page 10 info@gdscorp.com...
  • Page 11: Calibration

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   5 CALIBRATION     CALIBRATION OVERVIEW  The GDS‐48 does not have the capability to perform zero and span calibration. Final zero and span calibration must  be performed by the controller or receiving device.   Follow these GDS‐48 calibration guidelines:   Calibration accuracy is only as good as the calibration gas accuracy.  GDS Corp calibration gases are  traceable to NIST (National Institute of Standards and Technology).   Never use calibration gas that has passed its expiration date.    Always use a GDS Corp calibration cup that completely surrounds the sensor head.    Be sure to use ZERO AIR, a mixture of 21% oxygen and 79% nitrogen, as a zero reference unless you are  certain that no target gas exists in the area. Ambient gas may result in an ‘elevated zero’ condition that  will cause a FAULT to occur once the ambient gas is no longer present.    GDS Corp recommends using a span gas that is between 25% and 75% of full scale. GDS Corp does not  recommend using full scale as the span set point.   Always calibrate a new sensor before depending on the device for personnel or equipment safety   Calibrate on a regular schedule. GDS Corp recommends a full calibration every 3 months, with periodic  ‘bump tests’ on a more frequent basis to ensure that the sensor has not been affected by temperature  extremes or the presence of incompatible gases.     In general, calibration involves applying a zero reference gas and telling the receiving device to accept that output ...
  • Page 12: Figure 5-1: Applying Calibration Gas To Gds-48

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 response factors for common volatile organic compounds, contact GDS Corp for a list of available gases and  response factors.   The actual steps involved in calibration vary depending on the receiving device, but can be generalized as follows:  1. Select the appropriate channel on the controller or receiver and enable Calibration Mode.  This should  disable alarms during the calibration process.  Make sure that the controller’s Cal Span value matches the  cylinder of calibration gas.   2. Apply zero air to the sensor as shown in Fig. 6‐1 or confirm the absence of any target gas.  3. At the controller or receiver, press the “Set Zero” button to confirm that the current reading is ‘zero’.   4. Apply span gas to the sensor as shown in Fig 6‐1.   5. At the controller or receiver, monitor the output until it stabilizes. When stable, press the “Set Span”  button to confirm that the current reading corresponds to the Span value.   6. Turn off the regulator and remote the calibration cup from the sensor head.   7. At the controller or receiver, exit Cal Mode and resume normal operation.     Fixed Flow Regulator  Cylinder of Calibration Gas Calibration Cup      Figure 5-1: Applying Calibration Gas to GDS-48...
  • Page 13: Operation And Maintenance

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   6 OPERATION AND MAINTENANCE    In the normal operating mode, the millivolt‐level output corresponds to the detected gas concentration.  In the  event of a significant gas release, the GDS‐48 will indicate an overrange condition if the sensor’s output continues  to increase beyond the full scale value.   In the event that the sensor output drops below zero due to interference  gases or sensor failure, the output will drop to zero, indicating a FAULT condition to the remote receiver or  controller. If the sensor is removed, the output will also drop to zero.     The GDS‐48 should be checked regularly for damage, water ingress or flame arrestor clogging due to excessive dust  or dirt. If the flame arrestor has become contaminated by dust, dirt or moisture, remove the sensor head cover  (after first making sure to declassify the area) and carefully clean with compressed air. Use of solvent is  discouraged as remnants of the solvent material may affect the sensor. There are no user‐serviceable components  and maintenance is limited to cleaning and/or sensor replacement.     Some GDS Corp controllers and gas detectors monitor ‘sensor life’ by calculating a value between 0 and 100%  based on the current response to calibration gas as compared to the initial response when the sensor was first  installed. To ensure that the calculations are accurate, please make certain to follow the ‘new sensor’ installation  instructions in the appropriate device manual.     SENSOR REPLACEMENT  If a sensor shows FAULT, does not respond to gas or can no longer be calibrated, it should be replaced. GDS‐48  sensor transmitters use GDS Corp type 10‐95XX sensors, where the XX is the gas type shown in Section 3. The  range value should also be specified when ordering replacement sensors. For example, a replacement SmartIR  infrared for combustible gas, 0‐100% LEL would be “10‐9550‐R0100”.     To replace a sensor, review Fig. 6‐1 and follow these steps:  1. Declassify the area or remove power to the GDS‐48.  ...
  • Page 14: Figure 6-1: Sensor Replacement

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 CAUTION WHEN REINSTALLING THE SENSOR HEAD COVER.       Figure 6-1: Sensor Replacement GDS Corp Page 14 info@gdscorp.com...
  • Page 15: Spare Parts

    GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   7 SPARE PARTS     GRAY ENCLOSURE  5.5”  Enclosure + Sensor Head (No sensor):  3.5”  20‐0126  Full assembly less sensor (gray)  Enclosure / Junction Box Only:  20‐0099  Gray junction box enclosure w/ PCB  3.5”  Sensor Head Only: 10‐0247  Remote bridge‐style sensor (Type 1‐4)    Note: Does not include sensor  8.0”  Sensor: 10‐95xx  GDS Corp bridge sensor      YELLOW ENCLOSURE    Enclosure + Sensor Head (No sensor):  20‐0153 ...
  • Page 16 GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0 Sensor Head Splash Guard 10‐0198  Splash Guard (Fits all sensor heads)  Sensor Head Flow Cell 10‐0205  Flow Cell (1/8” NPT compression fittings)  20‐0205S  Other (specify)    Splash Guard  Flow Cell        GDS Corp Page 16 info@gdscorp.com...
  • Page 17 GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0   8 DRAWINGS AND DIMENSIONS      5.0”  7.75”    Figure 8-1: GDS-48 Yellow Enclosure   GDS Corp Page 17 info@gdscorp.com...
  • Page 18 GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0     5.5” 3.5” 3.5”  8.0”        Figure 8-2: GDS-48 (Gray Enclosure)       GDS Corp Page 18 info@gdscorp.com...