CONTENTS PAGE WARNING Do not throw or slam the remote controller. PRECAUTIONS..................1 ACCESSORIES (INDOOR UNIT).............. 2 Operate the remote controller within the receiving scope of the INSTALLATING INDOOR UNIT ...............2 indoor unit, and direct the transmitting part of the remote control- ler to the receiver of the indoor unit.
3. INSTALLATING INDOOR UNIT Installing the equipment in any of the following places may lead to faults of the equipment (if that is inevitable, consult the supplier): UNIT FEATURES The site contains mineral oils such as cutting lubricant. HORIZONTAL OR VERTICAL--All models are designed for either application and can be installed in either position as supplied from the Seaside where the air contains much salt.
Page 4
3.2 Install 10 or bigger Pendant Bolts Or D. Steel beam and girder structure Set and use supportive angle steel. Ground Bolts Pendant bolt hole Suspended bolt 4-12×25 Air inlet side Supportive Pendant bolt angle steel Fig.3-8 3.3 Suspending The Indoor Unit Fig.3-3 Use a hoisting device to hoist the indoor unit, align it with the installation screw, adjust the horizontality and then tighten it.
3.5 Install the condensate drainpipe 3.6 Dimension Unit:mm 1. Install the indoor unit drainpipe MVA-90CWN1-V MVA-120CWN1-V Two drain couplings are provided on alll models.select either one for condensate outlet and plug the other. consult local codes or ordinances for specific requirement regarding condensate drain.
Page 6
4. INSTALLATING OUTDOOR UNIT Air outlet 4.1 Important: Construction Checkpoints Installation Check the model and name to avoid mistaken installation. Air intlet Air inlet Refrigerant pipe The refrigerant pipes must have the specified diameter. Nitrogen of a certain pressure must be filled into the refrigerant pipe before welding.
Page 7
4.4 Installing The Outdoor Unit As shown in Fig.4-4, leave an interval of 100mm between the outdoor units. 200 mm 200 mm M12 foundation bolt 4 screws for 1 unit Fig.4-4 The distance of the foundation bolt is shown in Fig.4-5. steel Fig.4-7 (Unit:mm)
Page 8
MVA-90CWN1-V Table.4-2 Allowed value Gas-side connective Max. actual length of pipe (L) pipe of system Outdoor Height difference (upper) between indoor unit and outdoor Outdoor unit (H) (lower) Liquid-side connective pipe of system 4.7 Airtight Test MVA-120CWN1-V Fig.4-10 After the pipes between the indoor unit and the outdoor unit are connected, replenish compressed nitrogen to perform airtight test.
b. Leakage detection alarm device linked 5.3 Heat Insulation Of The Refrigerant Pipe with the mechanical ventilation device Please use heat-resistant materials as heat insulation materials Indoor unit of the air-side pipe. (e.g., EPT) Cover heat insulation materials separately at the liquid side and the air side.
Page 10
6.3 PRECAUTIONS DURING BRAZING SERVICE VALVE 10. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system. Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Fig.
Procedure of using stop valve Open the spool until it touches the stop block. Do not attempt to open further. Use a spanner or a similar tool to tighten the bonnet. The bonnet tightening torque is shown in aboveTable “Tightening torque”. Fig.6-3 Use refrigerant tank to expel air (see Fig.6-2 and Fig.6-3 ) Upon completion of installation, open all valves before trial run.
Inspection panel Drain pipe Inspection panel Table 8-1 Indoor unit Outdoor unit MOV-90CN1-D MVA-90CWN1-V Model MVA-120CWN1-V MOV-120CN1-D Bush Bush (inspection and sweep orifice) Power 220V 3N~ 60Hz 208-230V 3N~ 60Hz (inspection and sweep orifice) Main drain pipe Switch capacity of the main...
9. TRIAL RUN Outdoor unit Please conduct in accordance with “Trial Run Tenor Nameplate” Check whether any vibration or abnormal sound occurs during on the electric control box. the operation. Check whether the air, noise and condensate generated by the CAUTION unit affect the neighbors.
MAINTENANCE FAN BELT ALIGNMENT AND ADJUSTMENT Place belt on the groove of the fan pulley and motor sheave to obtain the approximate alignment and belt tension. Regular maintenance Remove the belt and align the fan pulley and motor sheave Some regular maintenance have been carried on by user, using a straight edge,refer to figure.
Page 15
3) When the unit is not running and heating system is not run-time in For required to deflection the winter, the water must be drained out the coil (system) or add the appropriate concentration antifreeze, otherwise the coil will be Belt section Small pulley Newton(N)
Page 16
Re-install the air filter Condenser coil Unfiltered air circulates through the unit's condenser coil can cause the coil's surface to become clogged with dust, etc. Clean the coil, vertically (i.e., with the fins), and stroke the coil surface with a soft brush. Be sure to keep all vegetation away from the condenser coil area.