SCC TS Series Installation Instructions Manual

Protocol converter for use with lmv3..., lmv5.., rwf... and ts series controls
Hide thumbs Also See for TS Series:
Table of Contents

Advertisement

Quick Links

SCC Inc.
TS Series
TS... Priticil Cinverter
fir use with LMV3..., LMV5.., RWF... and TS Series Cintrils
Standard
Descriptin
Installatin Instructins
TS... series protocol converters provide feeible
communicaton interface optons to the building
management system (BMS) to provide streamlined data
collecton and monitoring.
Document No. TS-6100
February 18, 2019 (Rev. 19C1)
With Ethernet Switch
SCC Inc.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for SCC TS Series

  • Page 1 SCC Inc. Document No. TS-6100 February 18, 2019 (Rev. 19C1) TS Series TS… Priticil Cinverter fir use with LMV3..., LMV5.., RWF… and TS Series Cintrils Standard With Ethernet Switch TS… series protocol converters provide feeible Descriptin communicaton interface optons to the building management system (BMS) to provide streamlined data collecton and monitoring.
  • Page 2: Table Of Contents

    Interface..........................19 Changing the Protocol......................20 Adding a Device........................20 Adding a TS Series Lead/Lag Master via HOST, FIELD, R1 or R2 Port........24 Adding a TS Series Lead/Lag Master via ETHERNET or ETH Port.........26 Adding Boiler Objects to TS Series Lead/Lag Master............27 Adding a TS Series Deaerator/Surge Tank Panel via TS Series Lead/Lag Master....28 Adding a TS Series Deaerator/Surge Tank Panel..............29...
  • Page 3 BACnet/Metasys N2 – Mapping....................57 LMV5…..........................57 LMV3…..........................61 LME7…..........................63 RWF10..........................65 RWF55..........................66 TS Series Deaerator/Surge Tank...................68 TS Series Touchscreen Kit.....................71 TS Series Lead/Lag Master (Global System Data)..............80 TS Series Lead/Lag Master (Boiler Data)................83 Ethernet/IP – Mapping......................87 LMV5…..........................87 LMV3…..........................91 LME7…..........................93 RWF10..........................95 RWF55..........................96 TS Series Deaerator/Surge Tank...................98 TS Series Touchscreen Kit....................101...
  • Page 4 TS Series Document No. TS-6100 LMV3…..........................120 LME7…..........................122 RWF10..........................124 RWF55..........................125 TS Series Deaerator/Surge Tank..................127 TS Series Touchscreen Kit....................130 TS Series Lead/Lag Master (Global System Data)...............138 TS Series Lead/Lag Master (Boiler Data)................141 Modbus – Mapping.........................145 LMV5…..........................145 LMV3…..........................154 LME7…..........................160 RWF10..........................162 RWF55..........................163 TS Series..........................165 Mapping Notes........................166...
  • Page 5: Certifcatons

    TS Series Installaton Instructons Document No. TS-6100 Certifcatins BTL Mark – BACnet Testnn Labiratiry • The BTL® Mark is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which veriifes that the product correctly implements the BACnet®...
  • Page 6: Compatble Controls And Protocols

    Document No. TS-6100 Cimpatble Cintrils and Priticils The TS Series Protocol Converter can connect any combinaton or quantty of supported controls and convert the data into one of the supported protocols. A web-based conifguraton utlity is used to make conifguraton changes.
  • Page 7: Available Ports

    TS Series Installaton Instructons Document No. TS-6100 Available Pirts TS-PX4 This model has the following ports: HOST port (RS-485) • FIELD port (RS-485) • • ETHERNET port TS-PL4 This model has the following ports: HOST port (RS-485) • • FIELD port (L...
  • Page 8 (conifgured for RS-232 by DIP switch) to connect directly to the AZL… if speciifed as an opton. If the TS-P... is ordered as part of a TS Series Lead/Lag Master, TS Series Deaerator/Surge Tank Master or TS Series Touchscreen Kit, it will come installed as part of that assembly.
  • Page 9: Protocol Selecton

    TS Series Installaton Instructons Document No. TS-6100 Priticil Selectin Models TS-PX4, TS-PX2 and TS-PW can be conifgured for any of the following protocols: BACnet/IP • • BACnet MS/TP • Modbus/RTU to Modbus TCP/IP Modbus TCP/IP to Modbus/RTU • Metasys N2 •...
  • Page 10 LME7... (via OCI417.10) Modbus/RTU RS-485 RWF10 (with Modbus) Modbus/RTU RS-485 RWF55 Modbus/RTU RS-485 TS Series Deaerator/Surge Tank Master Modbus TCP/IP Ethernet TS Series Touchscreen Kit Modbus TCP/IP Ethernet TS Series Lead/Lag Master Modbus/RTU RS-485 Each connected device must have a unique Modbus address assigned between 1 and 255. All serial devices connected must have matching baud rates, data bits, stop bits and parity setngs.
  • Page 11: Physical Connectons

    TS Series Installaton Instructons Document No. TS-6100 Physical Cinnectins (cintnued) TS-PL… and TS-PX... The protocol converter has three ports, labeled HOST, FIELD and ETHERNET. The physical medium of the HOST and FIELD port depends upon the model of the device.
  • Page 12: Dip Switches

    Installaton Instructons TS Series Document No. TS-6100 DIP Switches Model TS-PW has DIP switches for each serial port to add terminaton, biasing as well as changing the physical connecton for port R1 from RS-232 to RS-485. • TERM: Applies 120-ohm terminaton between the RS-485+ and RS-485- connectons.
  • Page 13: Diagnostc Leds

    TS Series Installaton Instructons Document No. TS-6100 Diannistc LEDs TS-PL… and TS-PX... The protocol converter has sie LEDs that indicate the current status. • SPL: Indicates that the protocol converter is ofine (not programmed). • RUN: Begins fashing 20 seconds ater power to indicate normal operaton.
  • Page 14: Ts-Pw

    Installaton Instructons TS Series Document No. TS-6100 Diannistc LEDs (cintnued) TS-PW The protocol converter has three LEDs that indicate the current status. • SS: Begins fashing 20 seconds ater power to indicate normal operaton. ERR: Indicates that there is a system error present. Use the web-based conifguraton •...
  • Page 15: Web-Based Conifguraton Utlity

    • Default Gateway: 192.168.1.1 Model TS-PW also allows a wireless connecton. Enable DHCP to set a compatble IP address automatcally. The default network setngs for the wireless connecton are: SSID (Netwirk Name): SCC Inc. Protocol Converter • Passwird: start9876 •...
  • Page 16: Changing Ip Address (Windows)

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Changing IP Address (Windows) 1. (Windows 7) Click the Windows logo to open the start menu, then type 'cmd.eee' in the Search fles and folders teet boe and then press Enter.
  • Page 17 TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) 4. Right-click on the network adapter that is connected to the protocol converter and then click Pripertes. 5. Click 'Internet Protocol Version 4 (TCP/IPv4)' and then click Pripertes. SCC Inc.
  • Page 18 Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) 6. Click 'Use the following IP address:'. Enter the IP address and subnet mask desired. Using the values shown below is recommended if the protocol converter has the default IP address.
  • Page 19: Interface

    TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Interface Open a web browser. Navigate to http://192.168.1.70 http://192.168.50.1 if using model TS- PW with a wireless connecton. Note that these addresses can be changed and may be diferent.
  • Page 20: Changing The Protocol

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Changing the Protocol To change the protocol, enter the desired number in the priticil_select parameter and then click Submit. To apply the new protocol, click System Restart at the botom of the screen.
  • Page 21 Biiler via LLM (Ethernet) ti <priticil>: Connect to TS Series Lead/Lag Master boiler object via ETHERNET or ETH port Biiler via LLM (Serial) ti <priticil>: Connect to TS Series Lead/Lag Master boiler object • via either the HOST, FIELD, R1 or R2 serial port •...
  • Page 22 Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Once the device is selected, enter the Modbus address in the Nide ID ifeld. This must be a unique address. For devices connected to the ETHERNET or ETH port, enter any number that has not been used.
  • Page 23 TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) The communicaton setngs for the ports speciifed in the protocol parameters as the HOST port and FIELD port may need to be changed to match the connected equipment. All equipment connected to a port must have matching setngs.
  • Page 24: Adding A Ts Series Lead/Lag Master Via Host, Field, R1 Or R2 Port

    Surge Tank Panels. These objects are created individually. Enter 1 for the node ID. This is the default Modbus address of the TS Series Lead/Lag Master. Enter the device instance (if applicable), and the appropriate port for the HOST and FIELD port as speciifed in the protocol parameters (R1 or R2).
  • Page 25 The other communicaton setngs for the ports speciifed in the protocol parameters as the HOST port and FIELD port need to be changed to match the TS Series Lead/Lag Master. The required setngs are 38400 baud, no parity, 8 data bits and 1 stop bit. Edit each of these parameters individually and click Submit.
  • Page 26: Adding A Ts Series Lead/Lag Master Via Ethernet Or Eth Port

    Enter a unique number for the node ID (such as 200). Enter the device instance (if applicable). Click Submit. The IP address for TS Series Lead/Lag Master must be checked to conifrm it matches the IP address of the port it is connected to. The default is 192.168.2.69 for connecton to ETHERNET2 on the TS Series Lead/Lag Master touchscreen.
  • Page 27: Adding Boiler Objects To Ts Series Lead/Lag Master

    TS Series Lead/Lag Master. Make sure that the node ID and port selected (for serial) match that of the TS Series Lead/Lag Master and that the device instance selected is not duplicated. Repeat for each boiler object needed. biiler_id indicates the boiler designaton (Boiler 1, Boiler 2, Boiler 3, …, Boiler 8).
  • Page 28: Adding A Ts Series Deaerator/Surge Tank Panel Via Ts Series Lead/Lag Master

    <priticil> that matches the method used to connect the TS Series Lead/Lag Master. Note that the x will be 1 or 2 depending upon if DA1 or DA2 is being connected. Make sure that the node ID matches that of the TS Series Lead/Lag Master and that the device instance selected is not duplicated.
  • Page 29: Adding A Ts Series Deaerator/Surge Tank Panel

    Add. In the drop-down menu, select the device name DA/ST ti <priticil>. Enter a unique number for the node ID (such as 200). Enter the device instance (if applicable) and the IP address. The default IP address for a TS Series Deaerator/Surge Tank Panel is 192.168.1.58. SCC Inc.
  • Page 30: Adding A Ts Series Touchscreen Kit

    Web-Based Cinifnuratin Utlity (cintnued) Adding a TS Series Touchscreen Kit Direct connecton to a TS Series Touchscreen Kit is possible. Scroll down to the botom of the screen and click Add. In the drop-down menu, select the device name Tiuchscreen Kit ti <priticil>.
  • Page 31: Protocol Conifguraton Parameters - Bacnet/Ip

    This sets the Modbus/RTU stop bits for the port speciifed as the FIELD port (1 or 2). ip_master: Sets the IP address of the TS Series Lead/Lag Master. The default address is • 192.168.2.69 (the default address of the ETHERNET2 port on the HMI).
  • Page 32: Protocol Conifguraton Parameters - Bacnet Ms/Tp

    This sets the Modbus/RTU stop bits for the port speciifed as the HOST port (1 or 2). ip_master: Sets the IP address of the TS Series Lead/Lag Master. The default address is • 192.168.2.69 (the default address of the ETHERNET2 port on the HMI).
  • Page 33: Protocol Conifguraton Parameters - Metasys N2

    (1 or 2). • ip_master: Sets the IP address of the TS Series Lead/Lag Master. The default address is 192.168.2.69 (the default address of the ETHERNET2 port on the HMI). watchdin_tme: Remote command required refresh tme, default is 60 seconds (0-999).
  • Page 34: Protocol Conifguraton Parameters - Ethernet/Ip

    This sets the Modbus/RTU stop bits for the port speciifed as the FIELD port (1 or 2). ip_master: Sets the IP address of the TS Series Lead/Lag Master. The default address is • 192.168.2.69 (the default address of the ETHERNET2 port on the HMI).
  • Page 35: Protocol Conifguraton Parameters - Modbus/Rtu To Modbus Tcp/Ip

    TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Protocol Conifguraton Parameters – Modbus/RTU to Modbus TCP/IP Parameters that apply to all proifles or are general to the protocol are set here. The setng in bold is the default. Ater changing a value, click Submit to apply the change. A restart is required ater all desired setngs have been changed.
  • Page 36: Protocol Conifguraton Parameters - Modbus Tcp/Ip To Modbus/Rtu

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Protocol Conifguraton Parameters – Modbus TCP/IP to Modbus/RTU Parameters that apply to all proifles or are general to the protocol are set here. The setng in bold is the default. Ater changing a value, click Submit to apply the change. A restart is required ater all desired setngs have been changed.
  • Page 37: Protocol Conifguraton Parameters - Lonworks

    This sets the Modbus/RTU stop bits for the HOST port (1 or 2). • ip_master: Sets the IP address of the TS Series Lead/Lag Master. The default address is • 192.168.2.69 (the default address of the ETHERNET2 port on the HMI).
  • Page 38: Clearing All Proifles From Memory

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Clearing All Proifles From Memory All conifgured proifles can be cleared from the protocol converter by clicking Clear Proifles and Restart from the conifguraton screen. Alternatvely, each proifle can also be individually removed by clicking Remove under Actve priifles.
  • Page 39: Changing Network Setngs

    TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Changing Network Setngs From the conifguraton screen, click Network Setngs to view or edit the network setngs. Before changing the IP address of the protocol converter or any connected devices, make sure that the communicaton between the devices will not be afected.
  • Page 40: Diagnostcs And Debugging

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Diagnostcs and Debugging From the conifguraton screen, click Diannistcs & Debunninn to display the diagnostc home screen. Use the navigaton pane on the let to view the four diagnostc and debugging sectons.
  • Page 41: Setup - Loading Updates

    TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Setup – Loading Updates Allows uploading and downloading of system ifles. To load supplied updates or other conifguraton ifles (such as BACnet BBMD mapping ifle bdt.ini) choose the General tab, then click Chiise Files. Navigate to the ifle to load then click Submit.
  • Page 42: Setup - Wifi Client

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Setup – WiFi Client Allows a connecton via WiFi to an eeistng wireless network (model TS-PW only). Depending upon the locaton of the protocol converter, it may require that an eeternal antenna is mounted to receive a sufcient signal.
  • Page 43: Setup - Wifi Access Point

    TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Setup – WiFi Access Point Allows a wireless access point to be established via WiFi (model TS-PW only). Depending upon the locaton of the protocol converter, it may require that an eeternal antenna is mounted to receive a sufcient signal.
  • Page 44: View

    Installaton Instructons TS Series Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) View The status of connectons (protocol statstcs), data arrays (internal data), nodes (individual device statstcs) and map descriptors (data statstcs) can be viewed to determine if conifguraton is successful.
  • Page 45 TS Series Installaton Instructons Document No. TS-6100 Web-Based Cinifnuratin Utlity (cintnued) Nodes shows the Te (transmit) and Re (receive) trafc for each device. This shows that data is passing through the protocol converter. If Te and Re do not increment in unison that may indicate a communicaton problem.
  • Page 46: Bacnet Additonal Informaton

    Installaton Instructons TS Series Document No. TS-6100 BACnet Additinal Infirmatin Models TS-PX... and TS-PW support both BACnet/IP and BACnet MS/TP. BACnet/IP BACnet/IP uses Ethernet as the physical medium and communicates using the UDP transport layer on port 47808 (BAC0 in heeadecimal) by default. The protocol converter can be conifgured as a BACnet/IP Broadcast Management Device.
  • Page 47: Metasys N2 Additonal Informaton

    TS Series Installaton Instructons Document No. TS-6100 Metasys N2 Additinal Infirmatin Models TS-PX… and TS-PW support Metasys N2. Metasys N2 uses RS-485 as the physical medium. The maeimum number of devices that can be installed on a single network varies depending upon the model of controller. The only supported baud rate is 9600.
  • Page 48: Ethernet/Ip Additonal Informaton

    Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP Additinal Infirmatin Models TS-PX... and TS-PW support Ethernet/IP. The protocol converter is conifgured to be a server to the system. Message instructons are used to query data as needed. Tested Applicatons The following Rockwell Automaton sotware platforms have been tested: •...
  • Page 49: User-Deifned Data Types

    TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP Additinal Infirmatin (cintnued) User-Deifned Data Types Open Studio 5000 or RSLogie 5000. Create a new project using the appropriate controller. In the Cintriller Ornaniier window, right-click User-Deifned under Data Types and choose Impirt Data Type….
  • Page 50: Controller Tags

    Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP Additinal Infirmatin (cintnued) Controller Tags In the Cintriller Ornaniier window, double-click Cintriller Tans and click the Edit tab. Choose a name for the device data to be connected (such as Biiler_1) and then click the buton to choose the data type.
  • Page 51 TS Series DA/ST (standalone) REAL[90] INT[2] TS Series Touchscreen Kit REAL[265] INT[18] REAL[265] INT[265] TS Series Lead/Lag Master REAL[57] INT[5] REAL[57] INT[57] TS Series LL Master (boiler) REAL[92] INT[7] TS Series LL Master (DA/ST) REAL[90] INT[2] SCC Inc. Page 51...
  • Page 52: Logic

    Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP Additinal Infirmatin (cintnued) Logic Open the logic routne (such as MainRiutne) where the message instructons should be placed. Place SCC_Messane_Sequence (found under Add-On tab) at the end of a rung. Edit the input tag Qty_Messanes to match the total number of message instructons that will be used (maeimum of 32 using this add-on instructon).
  • Page 53: Setng Up Messaging Instructons

    TS Series LL Master (boiler, y = 1-8) LLM_By_Read_e LLM_By_Status_e LLM_By_Write_e LLM_By_Trigger_e TS Series LL Master (DA/ST, y = 1 or 2) DSCy_Read_e DSCy_Status_e Click on each message instructon to set up the speciifc message. For the Read and Status message instructons, choose the message type CIP Data Table Read.
  • Page 54: Testng Operaton

    Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP Additinal Infirmatin (cintnued) For the Write and Trinner message instructons, choose the message type CIP Data Table Write. Select the source element from the device tag and select the sub-element to match the type of data (Write or Trinner). Select the number of elements and destnaton element name from the table above –...
  • Page 55: Modbus Additonal Informaton

    TS Series Installaton Instructons Document No. TS-6100 Midbus Additinal Infirmatin Supported baud rates for Modbus/RTU are 9600, 19200, 38400, 57600, 76800 and 115000. Conversion from Modbus/RTU to Modbus TCP/IP requires that the node ID parameter is used. This is oten not used or set to '255' by default, following the assumpton that there would only be one node per IP address.
  • Page 56: Lonworks Additonal Informaton

    Installaton Instructons TS Series Document No. TS-6100 Additinal Infirmatin ORKS Models TS-PL... support the LonWorks protocol via the FIELD port. L uses the FTT-10A ORKS transceiver. The L network is polarity insensitve and supports free topology wiring ORKS (star, bus or daisy-chain wiring are all acceptable). When using L...
  • Page 57: Bacnet/Metasys N2 - Mapping

    AI 20001 for node 200. Addresses 100 and above work in the same manner. Address AI 101 would be AI 1101 for node 1 and AI 200101 for node 200. For the TS Series Lead/Lag Master, the global variables will be AI/AV/BI/BV 1-99, boiler 1 variables will be AI/AV/BI/BV 101-199, contnuing through boiler 8 variables which will be AI/AV/BI/BV 801-899.
  • Page 58 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 LMV5... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n20 LMV PRESSURE UNIT no units 0=metric,1=standard AI n21 LMV SENSOR SELECTION no units see Mappinn Nites – Nite 2...
  • Page 59 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 LMV5... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n68 LMV AZL5 PARAMETER SET VER no units AI n69 LMV AZL5 ID DATE YEAR 2-DIGIT no units...
  • Page 60 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 LMV5... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n116 LMV ERROR OUTPUT CURRENT percent see Mappinn Nites – Nite 1 AI n117 LMV ERROR STARTUPS CURRENT...
  • Page 61: Lmv3

    TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – LMV3… BACnet/Metasys N2 LMV3... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n1 LMV PHASE no units see LMV Phases AI n2 LMV FUEL ACTUATOR...
  • Page 62 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 LMV3... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n45 LMV REVERT TO PILOT CYCLES no units AI n46 LMV OPERATION FUEL 0 NEW no units see Mappinn Nites –...
  • Page 63: Lme7

    TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – LME7… BACnet/Metasys N2 LME7... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n1 PHASE no units see LME7 Phases AI n2 FLAME INTENSITY...
  • Page 64 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 LME7... Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n45 HISTORY 6 ERROR PHASE no units see LME7 Phases AI n46 HISTORY 6 ERROR LOAD percent...
  • Page 65: Rwf10

    TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – RWF10 BACnet/Metasys N2 RWF10 Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n1 PROCESS VARIABLE <pv unit> AI n2 STATUS WORD no units...
  • Page 66: Rwf55

    Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – RWF55 BACnet/Metasys N2 RWF55 Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n1 INPUT 1 X1 <pv unit> AI n2 INPUT 2 X2...
  • Page 67 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 RWF55 Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AV/AO n45 OFF HYSTERESIS TOP HYS3 <pv unit> AV/AO n46 ON HYST COOLING HYS4 <pv unit> AV/AO n47 OFF HYST BTM COOLING HYS5 <pv unit>...
  • Page 68: Ts Series Deaerator/Surge Tank

    – TS Series Deaerator/Surge Tank This mapping applies to either standalone applicatons or as part of a TS Series Lead/Lag Master. BACnet/Metasys N2 TS Series Deaeratir/Surne Tank Mappinn MS/TP addressinn inly: n = nide ID fir standaline, 9 when DA/ST-1 via LLM, 10 when DA/ST-2 via LLM...
  • Page 69 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Deaeratir/Surne Tank Mappinn MS/TP addressinn inly: n = nide ID fir standaline, 9 when DA/ST-1 via LLM, 10 when DA/ST-2 via LLM ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n44 ANALOG INPUT 8...
  • Page 70 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Deaeratir/Surne Tank Mappinn MS/TP addressinn inly: n = nide ID fir standaline, 9 when DA/ST-1 via LLM, 10 when DA/ST-2 via LLM ADDRESS DESCRIPTION UNITS/TEXT NOTES BI n2 DA HIGH WATER...
  • Page 71: Ts Series Touchscreen Kit

    TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – TS Series Touchscreen Kit BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n1 LMV PHASE no units...
  • Page 72 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AV/AO n45* LMV SETPOINT W1 <pv unit> AV/AO n46* LMV SETPOINT W2 <pv unit> AI n47...
  • Page 73 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n93 LMV ADAPTION STATE no units AV/AO n94 LMV START ADAPTION no units 0=reset,1=start,2=abort...
  • Page 74 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AV/AO n141 RWF LC SP1 <pv unit> AV/AO n142 RWF LC SP2 <pv unit> AV/AO n143 RWF LC AL ALARM SP <pv unit>...
  • Page 75 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n189 RWF EX2 AL ALARM SP no units AI n190 RWF EX2 HYS1 <pv unit>...
  • Page 76 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES AI n237 VSD OUTPUT VOLTAGE volts AI n238 VSD DC BUS VOLTAGE volts AI n239...
  • Page 77 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES BI n20 LMV FUEL VALVE V1 OIL actve/inactve BI n21 LMV FUEL VALVE V2 OIL...
  • Page 78 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES BI n68 RWF EX1 K6 ACTIVE actve/inactve BI n69 RWF EX2 INPUT 1 FAULT actve/inactve...
  • Page 79 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Tiuchscreen Kit Mappinn MS/TP addressinn inly: n = nide ID ADDRESS DESCRIPTION UNITS/TEXT NOTES BI n116 EA ALARM INPUT 10 actve/inactve BI n117 EA ALARM INPUT 11 actve/inactve BI n118...
  • Page 80: Ts Series Lead/Lag Master (Global System Data)

    Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – TS Series Lead/Lag Master (Global System Data) BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Glibal System Data) ADDRESS DESCRIPTION UNITS/TEXT NOTES AV/AO 1 LLM REMOTE SETPOINT <pv unit>...
  • Page 81 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Glibal System Data) ADDRESS DESCRIPTION UNITS/TEXT NOTES AV/AO 46 LLM LOOP D VALUE no units AV/AO 47 LLM LOOP ALT SETPOINT no units AI 48 LLM LOOP ALT ELAPSED...
  • Page 82 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Glibal System Data) ADDRESS DESCRIPTION UNITS/TEXT NOTES BI 40 LLM LOOP PUMP 1 RUN actve/inactve BI 41 LLM LOOP PUMP 2 RUN actve/inactve BI 42 LLM LOOP PUMP 1 ALARM...
  • Page 83: Ts Series Lead/Lag Master (Boiler Data)

    Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 Mappinn (cintnued) – TS Series Lead/Lag Master (Boiler Data) BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) MS/TP addressinn inly: x = biiler desinnatin ADDRESS DESCRIPTION UNITS/TEXT NOTES...
  • Page 84 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) MS/TP addressinn inly: x = biiler desinnatin ADDRESS DESCRIPTION UNITS/TEXT NOTES AI x45 Be DRAFT SENSOR inches water AI x46...
  • Page 85 TS Series Installaton Instructons Document No. TS-6100 BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) MS/TP addressinn inly: x = biiler desinnatin ADDRESS DESCRIPTION UNITS/TEXT NOTES BI x3 Be BOILER PUMP RUNNING actve/inactve BI x4...
  • Page 86 Installaton Instructons TS Series Document No. TS-6100 BACnet/Metasys N2 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) MS/TP addressinn inly: x = biiler desinnatin ADDRESS DESCRIPTION UNITS/TEXT NOTES BI x51 Be EA INPUT 8 actve/inactve BI x52...
  • Page 87: Ethernet/Ip - Mapping

    TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP Mappinn – There are four arrays provided for each device (Read, Status, Write and Trigger). To write a writable point, write the desired value to the indee of the Write array and then set the corresponding indee of the Trigger array to 1.
  • Page 88 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP LMV5... Mappinn Variable = LMV_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV COMBUSTION EFFICIENCY Read LMV INPUT WORD Read word of bits LMV OUTPUT WORD Read word of bits LMV PROGRAM STOP Read, Write see Mappinn Nites –...
  • Page 89 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP LMV5... Mappinn Variable = LMV_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV SOFTWARE VERSION AZL Read read in heeadecimal LMV SW VER BURNER CONTROL Read read in heeadecimal LMV SW VER LOAD CONTROL...
  • Page 90 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP LMV5... Mappinn Variable = LMV_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES 0.11 LMV GAS PRESS SW MAX Status 0.13 LMV AIR PRESSURE SW Status 0.14 LMV START RELEASE OIL Status 0.15...
  • Page 91: Lmv3

    TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – LMV3… Ethernet/IP LMV3... Mappinn Variable = LMV_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV PHASE Read see LMV Phases LMV FUEL ACTUATOR Read LMV AIR ACTUATOR Read LMV VSD OUTPUT...
  • Page 92 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP LMV3... Mappinn Variable = LMV_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV REVERT TO PILOT CYCLES Read LMV OPERATION FUEL 0 NEW Read see Mappinn Nites – Nite 7 LMV OPERATION FUEL 1 NEW Read see Mappinn Nites –...
  • Page 93: Lme7

    TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – LME7… Ethernet/IP LME7... Mappinn Variable = LME7_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES PHASE Read see LME7 Phases FLAME INTENSITY Read MAINS VOLTAGE Read STARTUPS RESETTABLE Read STARTUPS TOTAL...
  • Page 94 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP LME7... Mappinn Variable = LME7_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES HISTORY 6 ERROR PHASE Read see LME7 Phases HISTORY 6 ERROR LOAD Read HISTORY 7 ERROR CODE Read see LME7 Errir Cides...
  • Page 95: Rwf10

    TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – RWF10 Ethernet/IP RWF10 Mappinn Variable = RWF10_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES PROCESS VARIABLE Read STATUS WORD Read ANALOG OUTPUT Read CURRENT SETPOINT Read, Write SETPOINT ALARM 1...
  • Page 96: Rwf55

    Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – RWF55 Ethernet/IP RWF55 Mappinn Variable = RWF55_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES INPUT 1 X1 Read INPUT 2 X2 Read INPUT 3 X3 Read CURRENT SETPOINT WR...
  • Page 97 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP RWF55 Mappinn Variable = RWF55_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES OFF HYSTERESIS TOP HYS3 Read, Write ON HYST COOLING HYS4 Read, Write OFF HYST BTM COOLING HYS5 Read, Write OFF HYST TOP COOLING HYS6...
  • Page 98: Ts Series Deaerator/Surge Tank

    Mappinn (cintnued) – TS Series Deaerator/Surge Tank This mapping applies to either standalone applicatons or as part of a TS Series Lead/Lag Master. Ethernet/IP TS Series Deaeratir/Surne Tank Mappinn Variable (standalone) = DSC_<ARRAY NAME>_<Node ID> Variable (TS Series Lead/Lag Master as DA1) = DSC1_<ARRAY NAME>_<Node ID>...
  • Page 99 Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Deaeratir/Surne Tank Mappinn Variable (standalone) = DSC_<ARRAY NAME>_<Node ID> Variable (TS Series Lead/Lag Master as DA1) = DSC1_<ARRAY NAME>_<Node ID> Variable (TS Series Lead/Lag Master as DA1) = DSC2_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION...
  • Page 100 TS Series Document No. TS-6100 Ethernet/IP TS Series Deaeratir/Surne Tank Mappinn Variable (standalone) = DSC_<ARRAY NAME>_<Node ID> Variable (TS Series Lead/Lag Master as DA1) = DSC1_<ARRAY NAME>_<Node ID> Variable (TS Series Lead/Lag Master as DA1) = DSC2_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION...
  • Page 101: Ts Series Touchscreen Kit

    TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – TS Series Touchscreen Kit Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV PHASE Read see LMV Phases LMV FUEL ACTUATOR...
  • Page 102 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV SETPOINT W1 Read, Write LMV SETPOINT W2 Read, Write LMV WEEKDAY Read 0=Sun,1=Mon,…,6=Sat LMV YEAR 2-DIGIT...
  • Page 103 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV ADAPTION STATE Read LMV START ADAPTION Read, Write 0=reset,1=start,2=abort LMV ADAPTION OUTPUT Read, Write LMV P-VALUE...
  • Page 104 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES RWF LC SP1 Read, Write RWF LC SP2 Read, Write RWF LC AL ALARM SP Read, Write...
  • Page 105 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES RWF EX2 AL ALARM SP Read RWF EX2 HYS1 Read RWF EX2 HYS3 Read RWF EX2 Y OUTPUT...
  • Page 106 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES VSD OUTPUT VOLTAGE Read VSD DC BUS VOLTAGE Read VSD STATUS WORD Read VSD OUTPUT RPM Read...
  • Page 107 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LMV FUEL VALVE V1 OIL Status 1.10 LMV FUEL VALVE V2 OIL Status 1.11 LMV FUEL VALVE V3 OIL Status 1.12...
  • Page 108 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES RWF EX1 K6 ACTIVE Status 9.12 RWF EX2 INPUT 1 FAULT Status 9.13 RWF EX2 INPUT 2 FAULT Status 9.14...
  • Page 109 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Tiuchscreen Kit Mappinn Variable = TSK_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES 13.9 EA ALARM INPUT 10 Status 13.10 EA ALARM INPUT 11 Status 13.11 EA ALARM INPUT 12 Status 13.12...
  • Page 110: Ts Series Lead/Lag Master (Global System Data)

    Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – TS Series Lead/Lag Master (Global System Data) Ethernet/IP TS Series Lead/Lan Master Mappinn (Glibal System Data) Variable = LLM_Mst_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LLM REMOTE ENABLE...
  • Page 111 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Lead/Lan Master Mappinn (Glibal System Data) Variable = LLM_Mst_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LLM LOOP OUTPUT Read LLM LOOP P VALUE Read, Write LLM LOOP I VALUE...
  • Page 112 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Lead/Lan Master Mappinn (Glibal System Data) Variable = LLM_Mst_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES LLM LOOP OUTPUT 1 Status LLM LOOP OUTPUT 2 Status LLM LOOP PUMP 1 RUN...
  • Page 113: Ts Series Lead/Lag Master (Boiler Data)

    Installaton Instructons Document No. TS-6100 Ethernet/IP Mappinn (cintnued) – TS Series Lead/Lag Master (Boiler Data) Ethernet/IP TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) Variable = LLM_Be_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES Be LMV PHASE...
  • Page 114 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) Variable = LLM_Be_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES Be FW WR CURRENT SP Read Be FW SP1 Read Be DRAFT SENSOR...
  • Page 115 TS Series Installaton Instructons Document No. TS-6100 Ethernet/IP TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) Variable = LLM_Be_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES Be BOILER AUTO Status Be BOILER AVAILABLE Status Be BOILER PUMP RUNNING...
  • Page 116 Installaton Instructons TS Series Document No. TS-6100 Ethernet/IP TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) Variable = LLM_Be_<ARRAY NAME>_<Node ID> INDEX DESCRIPTION ARRAY NAME(S) NOTES Be EA INPUT 8 actve/inactve Be EA INPUT 9 actve/inactve Be EA INPUT 10 actve/inactve 5.10...
  • Page 117: Lonworks - Mapping

    TS Series Installaton Instructons Document No. TS-6100 Mappinn ORKS – SNVT names beginning with nvi are read-only. SNVT names beginning with nvi are used to write data. When writng, monitor the corresponding nvi SNVT to verify the write. x in the SNVT name represents the Nide ID as entered when conifguring the proifle using the web- based conifguraton utlity.
  • Page 118 Installaton Instructons TS Series Document No. TS-6100 LMV5... Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LMV MODBUS WATCHDOG (nvo/nvi)eLmvMWdog* SNVT_tme_sec LMV MODBUS OPERATING MODE (nvo/nvi)eLmvMOpMode SNVT_count_inc_f 0=auto,1=on,2=of LMV MODBUS SETPOINT W3 (nvo/nvi)eLmvMSpW3 SNVT_count_inc_f LMV MODBUS OUTPUT (nvo/nvi)eLmvMOutput SNVT_lev_percent see Mappinn Nites – Nite 1...
  • Page 119 TS Series Installaton Instructons Document No. TS-6100 LMV5... Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LMV D-VALUE (nvo/nvi)eLmvD-Value* SNVT_tme_sec LMV LOCKOUT ERROR CODE CURRENT (nvo)eLmvLoEcCur SNVT_count_inc_f see LMV5 Lickiut/Errir Cides LMV LOCKOUT DIAG CODE CURRENT (nvo)eLmvLoDcCur SNVT_count_inc_f see LMV5 Lickiut/Errir Cides...
  • Page 120: Lmv3

    Installaton Instructons TS Series Document No. TS-6100 Mappinn (cintnued) ORKS – LMV3… LMV3... Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LMV PHASE (nvo)eLmvPhase SNVT_count_inc_f see LMV Phases LMV FUEL ACTUATOR (nvo)eLmvFuelAct SNVT_angle_deg LMV AIR ACTUATOR (nvo)eLmvAirAct SNVT_angle_deg LMV VSD OUTPUT...
  • Page 121 TS Series Installaton Instructons Document No. TS-6100 LMV3... Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LMV OPERATION FUEL 0 NEW (nvo)eLmvOpF0N SNVT_count_inc_f see Mappinn Nites – Nite 7 LMV OPERATION FUEL 1 NEW (nvo)eLmvOpF1N SNVT_count_inc_f see Mappinn Nites – Nite 7...
  • Page 122: Lme7

    Installaton Instructons TS Series Document No. TS-6100 Mappinn (cintnued) ORKS – LME7… LME7... Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES PHASE (nvo)ePhase SNVT_count_inc_f see LME7 Phases FLAME INTENSITY (nvo)eFlamePer SNVT_lev_percent MAINS VOLTAGE (nvo)eMainsVol SNVT_volt_ac STARTUPS RESETTABLE (nvo)eSURst SNVT_count_inc_f STARTUPS TOTAL...
  • Page 123 TS Series Installaton Instructons Document No. TS-6100 LME7... Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES HISTORY 6 ERROR LOAD (nvo)eH6ErrLd SNVT_lev_percent HISTORY 7 ERROR CODE (nvo)eH7ErrCd SNVT_count_inc_f see LME7 Errir Cides HISTORY 7 ERROR STARTUPS (nvo)eH7ErrSU SNVT_count_inc_f HISTORY 7 ERROR PHASE...
  • Page 124: Rwf10

    Installaton Instructons TS Series Document No. TS-6100 Mappinn (cintnued) ORKS – RWF10 RWF10 Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES PROCESS VARIABLE (nvo)eProcessVar SNVT_count_inc_f STATUS WORD (nvo)eStatusWord SNVT_count_inc_f ANALOG OUTPUT (nvo)eAnaOutput SNVT_lev_percent CURRENT SETPOINT (nvo,nvi)eCurrentSp SNVT_count_inc_f SETPOINT ALARM 1...
  • Page 125: Rwf55

    TS Series Installaton Instructons Document No. TS-6100 Mappinn (cintnued) ORKS – RWF55 RWF55 Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES INPUT 1 X1 (nvo)eIn1X1 SNVT_count_inc_f INPUT 2 X2 (nvo)eIn2X2 SNVT_count_inc_f INPUT 3 X3 (nvo)eIn3X3 SNVT_count_inc_f CURRENT SETPOINT WR (nvo)eCurSpWr...
  • Page 126 Installaton Instructons TS Series Document No. TS-6100 RWF55 Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES ON HYST COOLING HYS4 (nvo/nvi)eHysClgHys4 SNVT_count_inc_f OFF HYST BTM COOLING HYS5 (nvo/nvi)eHystBtHys5 SNVT_count_inc_f OFF HYST TOP COOLING HYS6 (nvo/nvi)eHystTpHys6 SNVT_count_inc_f REACTION THRESHOLD q (nvo/nvi)eThresholdQ...
  • Page 127: Ts Series Deaerator/Surge Tank

    Mappinn (cintnued) ORKS – TS Series Deaerator/Surge Tank This mapping applies to either standalone applicatons or as part of a TS Series Lead/Lag Master. TS Series Deaeratir/Surne Tank Mappinn ORKS e = 9 for DA/ST-1 or 10 for DA/ST-2 when connected via TS Series Lead/Lag Master...
  • Page 128 Installaton Instructons TS Series Document No. TS-6100 TS Series Deaeratir/Surne Tank Mappinn ORKS e = 9 for DA/ST-1 or 10 for DA/ST-2 when connected via TS Series Lead/Lag Master SNVT NAME DESCRIPTION SNVT TYPE NOTES ANALOG INPUT 8 (nvo)eAnaInput8 SNVT_count_inc_f...
  • Page 129 TS Series Installaton Instructons Document No. TS-6100 TS Series Deaeratir/Surne Tank Mappinn ORKS e = 9 for DA/ST-1 or 10 for DA/ST-2 when connected via TS Series Lead/Lag Master SNVT NAME DESCRIPTION SNVT TYPE NOTES DA HIGH WATER (nvo)eDaHighWtr SNVT_switch (State)
  • Page 130: Ts Series Touchscreen Kit

    Installaton Instructons TS Series Document No. TS-6100 Mappinn (cintnued) ORKS – TS Series Touchscreen Kit TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LMV PHASE (nvo)eLmvPhase SNVT_count_inc_f see LMV Phases LMV FUEL ACTUATOR (nvo)eLmvFuelAct SNVT_angle_deg LMV GAS ACTUATOR...
  • Page 131 TS Series Installaton Instructons Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LMV SETPOINT W2 (nvo/nvi)eLmvSpW2* SNVT_count_inc_f LMV WEEKDAY (nvo)eLmvWeekday SNVT_date_day 0=Sun,1=Mon,…,6=Sat LMV DATE (nvo)eLmvDt SNVT_tme_stamp LMV HOURS RUN GAS RESET (nvo/nvi)eLmvHrGsRst* SNVT_count_inc_f...
  • Page 132 Installaton Instructons TS Series Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LOW RANGE TRIM FUEL 1 (nvo)eLowTrFuel1 SNVT_lev_percent HIGH RANGE TRIM FUEL 1 (nvo)eHighTrFuel1 SNVT_lev_percent ANALOG INPUT TRIM (nvo)eAnaInTr SNVT_lev_percent CURRENT TRIM CORRECTION...
  • Page 133 TS Series Installaton Instructons Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES RWF FW INPUT WORD (nvo)eRwfFwIn SNVT_count_inc_f RWF FW OUTPUT WORD (nvo)eRwfFwOut SNVT_count_inc_f RWF FW LEVEL PERCENT (nvo)eRwfFwLvPct SNVT_count_inc_f RWF FW SETPOINT PERCENT...
  • Page 134 Installaton Instructons TS Series Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES EA ECONOMIZER STACK OUT (nvo)eEaEcSOut SNVT_count_inc_f EA DRAFT FEEDBACK (nvo)eEaDratFB SNVT_lev_percent EA DRAFT ALARM (nvo)eEaDratAlm SNVT_switch (State) EA DRAFT ALARM CODE...
  • Page 135 TS Series Installaton Instructons Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES USER VALUE 7 (nvo)eUserVal7 SNVT_count_inc_f USER VALUE 8 (nvo)eUserVal8 SNVT_count_inc_f USER VALUE 9 (nvo)eUserVal9 SNVT_count_inc_f USER VALUE 10 (nvo)eUserVal10 SNVT_count_inc_f USER VALUE 11...
  • Page 136 Installaton Instructons TS Series Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES RWF LC MANUAL OPERATION (nvo)eRwfLcManOp SNVT_switch (State) RWF LC BINARY INPUT 1 (nvo)eRwfLcBIn1 SNVT_switch (State) RWF LC BINARY INPUT 2 (nvo)eRwfLcBIn2...
  • Page 137 TS Series Installaton Instructons Document No. TS-6100 TS Series Tiuchscreen Kit Mappinn ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES EA INPUT 10 (nvo)eEaInput10 SNVT_switch (State) EA INPUT 11 (nvo)eEaInput11 SNVT_switch (State) EA INPUT 12 (nvo)eEaInput12 SNVT_switch (State) EA INPUT 13...
  • Page 138: Ts Series Lead/Lag Master (Global System Data)

    Installaton Instructons TS Series Document No. TS-6100 Mappinn (cintnued) ORKS – TS Series Lead/Lag Master (Global System Data) TS Series Lead/Lan Master Mappinn (Glibal System Data) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LLM REMOTE SETPOINT (nvo/nvi)MstRemoteSp SNVT_count_inc_f LLM LEAD BOILER...
  • Page 139 TS Series Installaton Instructons Document No. TS-6100 TS Series Lead/Lan Master Mappinn (Glibal System Data) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LLM LOOP D VALUE (nvo/nvi)MstLoopD SNVT_count_inc_f LLM LOOP ALT SETPOINT (nvo/nvi)MstLoopAlt SNVT_count_inc_f LLM LOOP ALT ELAPSED (nvo)MstLoopElap SNVT_count_inc_f...
  • Page 140 Installaton Instructons TS Series Document No. TS-6100 TS Series Lead/Lan Master Mappinn (Glibal System Data) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES LLM LOOP PUMP 1 RUN nvoMstLoopP1Run SNVT_switch (State) LLM LOOP PUMP 2 RUN nvoMstLoopP2Run SNVT_switch (State) LLM LOOP PUMP 1 ALARM...
  • Page 141: Ts Series Lead/Lag Master (Boiler Data)

    TS Series Installaton Instructons Document No. TS-6100 Mappinn (cintnued) ORKS – TS Series Lead/Lag Master (Boiler Data) TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES Be LMV PHASE (nvo)eLmvPhase SNVT_count_inc_f...
  • Page 142 Installaton Instructons TS Series Document No. TS-6100 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES Be USER VALUE 2 (nvo)eUserVal2 SNVT_count_inc_f Be USER VALUE 3 (nvo)eUserVal3 SNVT_count_inc_f Be USER VALUE 4...
  • Page 143 TS Series Installaton Instructons Document No. TS-6100 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES Be LMV FAN CONTACTOR (nvo)eLmvFanCont SNVT_switch (State) Be LMV OIL SELECTED (nvo)eLmvOilSel SNVT_switch (State) Be LMV GAS SELECTED...
  • Page 144 Installaton Instructons TS Series Document No. TS-6100 TS Series Lead/Lan Master Mappinn (Biiler Data, x = biiler desinnatin) ORKS SNVT NAME DESCRIPTION SNVT TYPE NOTES Be EA INPUT 13 (nvo)eEAIn13 SNVT_switch (State) Be EA ALARM 1 (nvo)eEAAlarm1 SNVT_switch (State) Be EA ALARM 2...
  • Page 145: Modbus - Mapping

    TS Series Installaton Instructons Document No. TS-6100 Midbus – Mappinn When using either Modbus conversion, the Modbus points are the same as the natve mapping. Using the node ID as part of the Modbus TCP/IP message is required to direct the message to the proper device.
  • Page 146 Installaton Instructons TS Series Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV CURRENT EXCESS AIR Unsigned Int 16 LMV INPUT WORD Unsigned Int 16 word of bits 35 bit 0 LMV CONTROLLER SWITCH Boolean 35 bit 1...
  • Page 147 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV HOURS RUN OIL S2 RESET Unsigned Int 32 LMV HOURS RUN OIL S3 RESET Unsigned Int 32 LMV HOURS RUN TOTAL RESET Unsigned Int 32...
  • Page 148 Installaton Instructons TS Series Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV LOCKOUT ERR PHASE CURRENT Unsigned Int 16 see LMV Phases LMV LOCKOUT FUEL CURRENT Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV LOCKOUT OUTPUT CURRENT Unsigned Int 16 e10, see Mappinn Nites –...
  • Page 149 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV LOCKOUT MINUTE -3 Unsigned Int 16 LMV LOCKOUT SECOND -3 Unsigned Int 16 LMV LOCKOUT STARTUPS -3 Unsigned Int 32 LMV LOCKOUT HOURS -3...
  • Page 150 Installaton Instructons TS Series Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV LOCKOUT ERROR PHASE -7 Unsigned Int 16 see LMV Phases LMV LOCKOUT FUEL -7 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV LOCKOUT OUTPUT -7 Unsigned Int 16 e10, see Mappinn Nites –...
  • Page 151 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR ERROR PHASE -3 Unsigned Int 16 see LMV Phases LMV ERROR FUEL -3 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -3 Unsigned Int 16 e10, see Mappinn Nites –...
  • Page 152 Installaton Instructons TS Series Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR ERROR PHASE -10 Unsigned Int 16 see LMV Phases LMV ERROR FUEL -10 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -10 Unsigned Int 16 e10, see Mappinn Nites –...
  • Page 153 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV5… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR ERROR PHASE -17 Unsigned Int 16 see LMV Phases LMV ERROR FUEL -17 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -17 Unsigned Int 16 e10, see Mappinn Nites –...
  • Page 154: Lmv3

    Installaton Instructons TS Series Document No. TS-6100 Midbus – Mappinn (cintnued) LMV3… There is a read limit of 20 words per message. If a message is invalid, the LMV3… will not respond with an eecepton. Messages must begin and end on a valid register. Mult-register formats such as 32-bit or string data must be read entrely to be a valid message.
  • Page 155 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV3… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV TOTAL VOLUME FUEL 1 Unsigned Int 32 LMV NUMBER OF LOCKOUTS Unsigned Int 16 LMV PRESELECT OUTPUT FUEL 0 Unsigned Int 16 LMV PRESELECT OUTPUT FUEL 1...
  • Page 156 Installaton Instructons TS Series Document No. TS-6100 Midbus LMV3… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR FUEL -2 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -2 Unsigned Int 16 e10, see Mappinn Nites – Nite 1 LMV ERROR STARTUPS -2...
  • Page 157 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV3… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR FUEL -9 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -9 Unsigned Int 16 e10, see Mappinn Nites – Nite 1 LMV ERROR STARTUPS -9...
  • Page 158 Installaton Instructons TS Series Document No. TS-6100 Midbus LMV3… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR FUEL -16 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -16 Unsigned Int 16 e10, see Mappinn Nites – Nite 1 LMV ERROR STARTUPS -16...
  • Page 159 TS Series Installaton Instructons Document No. TS-6100 Midbus LMV3… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES LMV ERROR FUEL -23 Unsigned Int 16 0=gas/fuel0,1=oil/fuel LMV ERROR OUTPUT -23 Unsigned Int 16 e10, see Mappinn Nites – Nite 1 LMV ERROR STARTUPS -23...
  • Page 160: Lme7

    Installaton Instructons TS Series Document No. TS-6100 Midbus – Mappinn (cintnued) LME7… Midbus LME7… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES PHASE Unsigned Int 16 see LME7 Phases FLAME INTENSITY Unsigned Int 16 MAINS VOLTAGE Unsigned Int 16 STARTUPS RESETTABLE Unsigned Int 32...
  • Page 161 TS Series Installaton Instructons Document No. TS-6100 Midbus LME7… Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES PME PRODUCT ID String (10 words) OCI PRODUCT ID String (10 words) writable data area CURRENT ERROR CODE Unsigned Int 16 see LME7 Errir Cides...
  • Page 162: Rwf10

    Installaton Instructons TS Series Document No. TS-6100 Midbus – Mappinn (cintnued) RWF10 Midbus RWF10 Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES 8192 PROCESS VARIABLE Unsigned Int 16 8193 STATUS WORD Unsigned Int 16 8192 bit 12 OUTPUT ALARM 1 BURNER Boolean...
  • Page 163: Rwf55

    TS Series Installaton Instructons Document No. TS-6100 Midbus – Mappinn (cintnued) RWF55 Midbus RWF55 Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES INPUT 1 X1 Float INPUT 2 X2 Float INPUT 3 X3 Float CURRENT SETPOINT WR Float FIRST SETPOINT SP1 Float...
  • Page 164 Installaton Instructons TS Series Document No. TS-6100 Midbus RWF55 Mappinn ADDRESS ACCESS DESCRIPTION FORMAT NOTES 4215 FILTER INPUT 1 dF1 Float 4217 FILTER INPUT 2 dF2 Float 4219 FILTER INPUT 3 dF3 Float 4221 ACTUAL VALUE LIMIT LOW oLLo Float...
  • Page 165: Ts Series

    Document No. TS-6100 Midbus – Mappinn (cintnued) TS Series See the corresponding documentaton for each device to ifnd the natve Modbus mapping: TS Series Tiuchscreen Kit (standaline): Document No. TS-1100 • TS Series Lead/Lan Master: Document No. TS-2100 • •...
  • Page 166: Mapping Notes

    Document No. TS-6100 Mappinn Nites TS Series Lead/Lag Master Remote Control Strategies A remote setpoint can be sent to LLM REMOTE SETPOINT. The value sent will be displayed on the SETPOINTS screen. In order for this setpoint to be used, the System Local-Of-Remote switch must be in 'Remote' and at least one boiler must be available.
  • Page 167 TS Series Installaton Instructons Document No. TS-6100 Mappinn Nites (cintnued) Note 4 – LMV5 operatng mode. 0: eeternal load control X5-03 • • 1: internal load control • 2: internal load control bus 3: internal load control X62 • 4: eeternal load control X62 •...
  • Page 168 Installaton Instructons TS Series Document No. TS-6100 Mappinn Nites (cintnued) Nite 7 – LMV3 fuel train. Mide Fuel Train Fuel-Air Rati Cintril Innitin Fuel Act. Air Act. Minitired VSD G mod modulatng electronic direct spark Gp1 mod modulatng electronic pilot between V1/V2...
  • Page 169: Lmv Phases

    TS Series Installaton Instructons Document No. TS-6100 LMV Phases NUMBER DESCRIPTION LOCKOUT PHASE SAFETY PHASE SAFETY PHASE HOME RUN POSITION STANDBY STATIONARY SAFETY RELAY ON RELEASE OF STARTUP FAN MOTOR ON DRIVE TO PURGE PREPURGE PREPURGE FGR PREPURGE VSD DRIVE TO IGNITION...
  • Page 170: Lmv5 Lockout/Error Codes

    Installaton Instructons TS Series Document No. TS-6100 LMV5 Lickiut/Errir Cides LMV5 Lickiut/Errir Cides CODE DECIMAL CODE HEX DESCRIPTION NO ERROR ROM ERROR RAM ERROR INTERNAL COMMUNICATION ERROR UNSUCCESSFUL SYNC OF 2uCs FAULT DURING FLAME AMP TEST FAULT INTERNAL HARDWARE TEST...
  • Page 171 TS Series Installaton Instructons Document No. TS-6100 LMV5 Lickiut/Errir Cides CODE DECIMAL CODE HEX DESCRIPTION WRONG CONTACT POSITION OF IGNITION WRONG CONTACT POSITION OF FUEL RELAY PLAUSIBILITY CHECK FAULT FAULT AT DEACTIVATED INPUTS SHUTDOWN VIA SAFETY LIMIT TEST PROGRAM STOP ACTIVATED...
  • Page 172 Installaton Instructons TS Series Document No. TS-6100 LMV5 Lickiut/Errir Cides CODE DECIMAL CODE HEX DESCRIPTION GAS ACTUATOR DETECTED A FAULT OIL ACTUATOR DETECTED A FAULT AUX1 ACTUATOR DETECTED A FAULT AUX2 ACTUATOR DETECTED A FAULT LOAD CONTROL DETECTED A FAULT...
  • Page 173: Lmv3 Error Codes

    TS Series Installaton Instructons Document No. TS-6100 LMV3 Errir Cides LMV3 Errir Cides CODE DESCRIPTION NO FLAME AT END OF SAFETY TIME AIR PRESSURE FAILURE EXTRANEOUS LIGHT LOSS OF FLAME VALVE PROVING PROOF OF CLOSURE AIR PRESSURE SWITCH SPEED DEPENDENT COMBUSTION PRESSURE POC PRESSURE SWITCH –...
  • Page 174 Installaton Instructons TS Series Document No. TS-6100 LMV3 Errir Cides CODE DESCRIPTION INTERNAL ERROR – CONTACT REQUEST INTERNAL ERROR – CONTACT REQUEST INTERNAL ERROR – CONTACT REQUEST INTERNAL ERROR – VOLTAGE MONITOR TEST POWER FAILURE MAINS VOLTAGE RECOVERY INTERNAL ERROR – MAINS VOLTAGE INTERNAL ERROR –...
  • Page 175 TS Series Installaton Instructons Document No. TS-6100 LMV3 Errir Cides CODE DESCRIPTION INTERNAL ERROR INTERNAL ERROR SELECTED MODE NOT RELEASED FOR BASIC UNIT INTERNAL ERROR INVALID PARAMETERIZATION INTERNAL ERROR INTERNAL ERROR SCC Inc. Page 175...
  • Page 176: Lme7 Phases

    Installaton Instructons TS Series Document No. TS-6100 LME7 Phases NUMBER DESCRIPTION LOCKOUT PHASE UNDERVOLTAGE OVERVOLTAGE START PREVENTION SAFETY LOOP START PREVENTION EXTRANEOUS LIGHT TEST HOME RUN STANDBY START RELEASE FAN ON DRIVE TO PREPURGE PREPURGE 1 PREPURGE 2 PREPURGE 3...
  • Page 177: Lme7 Error Codes

    TS Series Installaton Instructons Document No. TS-6100 LME7 Errir Cides CODE DESCRIPTION NO ERROR NO FLAME AT END OF SAFETY TIME TSA1 AIR PRESSURE FAILURE OFF EXTRANEOUS LIGHT ON BURNER START AIR PRESSURE FAILURE ON ACTUATOR FAILURE LOSS OF FLAME...
  • Page 178: Ts Series Conifguraton For Modbus

    255.255.255.0. TS Series Touchscreen Kit The default IP address for the TS Series Touchscreen Kit is 192.168.1.60 with a subnet mask of 255.255.255.0 and a boiler number of 1. If multple TS Series Touchscreen Kits are connected to the network, each must be assigned a unique IP address and boiler designaton.
  • Page 179: Lmv5 Conifguraton For Modbus

    TS Series Installaton Instructons Document No. TS-6100 LMV5 Cinifnuratin fir Midbus The LMV5... controller must be properly conifgured for Modbus operaton. Use the Select < and Select > butons to navigate up and down the screen and the Enter buton when the desired opton is selected with the cursor.
  • Page 180: Lmv3 Conifguraton For Modbus

    Installaton Instructons TS Series Document No. TS-6100 LMV3 Cinifnuratin fir Midbus The LMV3.. controller must have a compatble OCI opton installed (OCI412.10 or OCI413.20) in order to communicate with the system via Modbus. The service (heatng engineer) password must be entered for these parameters to be accessed.
  • Page 181: Lme7 Conifguraton For Modbus

    TS Series Installaton Instructons Document No. TS-6100 LME7 Cinifnuratin fir Midbus The LME7.. controller must have an OCI417.10 connected in order to communicate with the system via Modbus. Modbus/RTU protocol selecton and addressing is done using the PC tool OCI417 Cinifnuratin Utlity (download from htp://www.scccombuston.com, sorted under Products →...
  • Page 182: Rwf10 Conifguraton For Modbus

    Installaton Instructons TS Series Document No. TS-6100 RWF10 Cinifnuratin fir Midbus The RWF10 must have the Modbus opton in order to communicate with the system. This is an opton card that is inserted into the controller when required. To conifgure the RWF10 controller to communicate using Modbus, use the following procedure: 1.
  • Page 183: Rwf55 Conifguraton For Modbus

    TS Series Installaton Instructons Document No. TS-6100 RWF55 Cinifnuratin fir Midbus The RWF55 must be properly conifgured for Modbus operaton. Use the up and down arrow butons to navigate through the menus and the Enter buton when the desired menu is selected. Use Esc to go back to the previous menu. When a parameter needs to be changed, the up and down arrow butons allow the value to be changed and Enter conifrms the change.
  • Page 184: Change Log

    Installaton Instructons TS Series Document No. TS-6100 Channe Lin Revision 18D1 • New Modbus points for LMV3 sotware V3.70 and higher were added. • LME7 via OCI417.10 protocol conversion available in all protocols. • Ethernet/IP conversion available for all devices.