GardeMatic NanoMatic Installation Instructions Manual

Fountain controller

Advertisement

Quick Links

T H E
F O U N T A I N
C O N T R O L L E R
M A S T E R W I R I N G
M A N U A L
W W W . G A R D E M A T I C . C O M

Advertisement

loading

Summary of Contents for GardeMatic NanoMatic

  • Page 1 T H E F O U N T A I N C O N T R O L L E R M A S T E R W I R I N G M A N U A L W W W . G A R D E M A T I C . C O M...
  • Page 2 OUTPUTS WIND SYS DATA SENSORS A/0\M MASTER 4/8/16/22/30 OUTPUTS OUTPUTS W W W . G A R D E M A T I C . C O M...
  • Page 3: Power Supply

    1. Power supply Connect the stabilized DC 12 V 1,2A power supply as shown on the figure: PWR 12V DC+ PWR 12V DC- DO NOT REMOVE THE RX-TX TWO SHORTCUTS! W W W . G A R D E M A T I C . C O M...
  • Page 4 error refill valve OUTPUTS WIND SYS DATA SENSORS A/0\M MASTER 4/8/16/22/30 OUTPUTS OUTPUTS Transformer 1 24V AC W W W . G A R D E M A T I C . C O M...
  • Page 5 (24 V AC) to the refill output. This output is controlled by the Water level sensors. Connect the other side of the Refill valve to the common collector bus. Visit gardematic.com to reach GardeMatic water level control system: LA-series LB-series All in One series...
  • Page 6 Standby Manual Auto OUTPUTS WIND SYS DATA SENSORS A/0\M MASTER 4/8/16/22/30 OUTPUTS OUTPUTS W W W . G A R D E M A T I C . C O M...
  • Page 7 3. Connect the Auto/Standby/Manual switch Connect the Auto/Standby/Manual three way switch: STANDBY: both the AUTO and MANUAL switches are open, the NanoMagic controller turns in interactive mode. Note: you can ONLY use the menu in Standby mode! AUTO: if the AUTO switch is closed the controller will play the show as specified in the program.
  • Page 8 Wind receiver 1/0 output OUTPUTS SENSORS A/0\M WIND SYS DATA MASTER 4/8/16/22/30 Music line out OUTPUTS OUTPUTS W W W . G A R D E M A T I C . C O M...
  • Page 9 Should it not be enabled on your controller, you can upgrade and enable it with a firmware update. Visit: gardematic.com DO NOT REMOVE THE RX-TX SHORTCUTS! W W W . G A R D E M A T I C . C O M...
  • Page 10 OUTPUTS WIND SYS DATA SENSORS A/0\M MASTER 4/8/16/22/30 OUTPUTS OUTPUTS Transformer n Transformer 1 Transformer 2 24V AC 24V AC 24V AC W W W . G A R D E M A T I C . C O M...
  • Page 11 5. Connect the AC COM’s Connect all 24V AC transformer „N” wire and all inputs marked COM 24V AC to a common collector bus. It is VITAL that you connect all COM 24V AC inputs of the NanoMagic controller to maximize its lifespan! DO NOT CONNECT THE TRANSFORMER GROUNDS DIRECTLY TO THE CONTROLLER!
  • Page 12 24V AC relay OUTPUTS WIND SYS DATA SENSORS A/0\M MASTER 4/8/16/22/30 OUTPUTS OUTPUTS Transformer n Transformer 1 Transformer 2 24V AC 24V AC 24V AC W W W . G A R D E M A T I C . C O M...
  • Page 13: Filtering System

    6. Filtering System Connect the filtering system. Filtering System: connect the controller's FILTER output (normally open) to an 24V AC relay (not included) driving the Filter pump and an UV-C lamp. Connect the relay's primer side to the filter output and to the common collector bus. DO NOT CONNECT ANY HIGH VOLTAGE DEVICE TO THE NANOMAGIC CONTROLLER! DO NOT CONNECT THE TRANSFORMER „N”...
  • Page 14 OUTPUTS SENSORS A/0\M WIND SYS DATA MASTER 4/8/16/22/30 OUTPUTS OUTPUTS Transformer n Transformer 1 Transformer 2 24V AC 24V AC 24V AC W W W . G A R D E M A T I C . C O M...
  • Page 15 7. Connect the programmable outputs 7.1 Connect the WaterSwitch 601 nozzles One WaterSwitch 601 nozzle needs 2 valve outputs (Output). When designing the show, make sure that the 2 outputs for the same WaterSwitch 601 nozzle are inverted: Example: when one is ON(Nozzle), the other is OFF(Exhaust) DO NOT REMOVE THE RX-TX SHORTCUTS!
  • Page 16 solenoid valve OUTPUTS SENSORS A/0\M WIND SYS DATA MASTER 4/8/16/22/30 OUTPUTS OUTPUTS Transformer n Transformer 1 Transformer 2 24V AC 24V AC 24V AC W W W . G A R D E M A T I C . C O M...
  • Page 17 7. Connect the programmable outputs 7.2 Connect any solenoid valves or other 24VAC devices You can connect any 24VAC devices up to 2A (48W) DO NOT REMOVE THE RX-TX SHORTCUTS! W W W . G A R D E M A T I C . C O M...
  • Page 18 24V AC relay OUTPUTS WIND SYS DATA SENSORS A/0\M MASTER 4/8/16/22/30 OUTPUTS OUTPUTS Transformer 1 Transformer 2 Transformer n 24V AC 24V AC 24V AC W W W . G A R D E M A T I C . C O M...
  • Page 19 7. Connect the programmable outputs 7.3 Connecting high voltage devices High voltage devices (eg. pumps) MUST BE electrically detached from the NanoMagic controllers by using 24VAC relays. Instead of controlling the high voltage devices directly, the NanoMagic controller will controll the relays, which in turn control the high voltage devices.
  • Page 20 OUTPUTS SYS DATA OUTPUTS SYS DATA SENSORS A/0\M WIND OUTPUTS MASTER 4/8/16/22/30 SLAVE 40 OUTPUTS OUTPUTS OUTPUTS OUTPUTS SYS DATA OUTPUTS SYS DATA OUTPUTS OUTPUTS OUTPUTS SLAVE 40 SLAVE 40 OUTPUTS OUTPUTS OUTPUTS OUTPUTS W W W . G A R D E M A T I C . C O M...
  • Page 21 8. Optionally connect the Slave controllers You can increase the number of controlled outputs by attaching Slave devices to the Master. You can connect up to 100 Slaves. The communication happens on the RX-/RX+/TX-/TX+ connectors, called the . When connecting the Slaves, you MUST use twisted pair cables for the RX-/RX+ and TX-/TX+ cables respectively.
  • Page 22 N O T E S W W W . G A R D E M A T I C . C O M...
  • Page 23 N O T E S W W W . G A R D E M A T I C . C O M...
  • Page 24 N A N O M A G I C . G A R D E M A T I C . C O M GardeMatic Ltd. H-1163 Budapest, Gordonka u. 8. HUNGARY Phone: + 36 1 403 2634 E-mail: sales@gardematic.com TradeMark & Copyright 2013 GardeMatic Ltd. All rights reserved.