Checking The Flue Integrity; Flue Gas Analysis; Heat Exchanger; To Clean The Burner - Worcester Greenstar FS 30CDi Installation, Commissioning And Servicing Instructions

Floor standing rsf gas fired condensing regular boiler for sealed or open vent central heating systems
Hide thumbs Also See for Greenstar FS 30CDi:
Table of Contents

Advertisement

6.5

Checking the flue integrity

The appliance combustion cover must be fitted whilst
this test is being performed.
Refit the test point caps after the test has been
performed.
The integrity of the flue system and performance of the appliance can be
checked via the sample points at the top left hand side of the combustion
chamber, refer to figure 44.
With the combustion cover fitted and the appliance running at
maximum output, remove the cap from the air inlet sample point [1]
Insert the analyser probe into the sample point
Allow the readings to stabilise and check that:
– O
is equal to or greater than 20.6%
2
– CO
is less than 0.2%
2
If the readings are outside these limits, then this indicates that there
could be a problem with the flue system or combustion circuit.
6.6

Flue gas analysis

Ensure that the gas inlet pressure is correct before
continuing, refer to section 5.5.1
Combustion test:
Remove cap on the flue gas sample point [2], as shown below and
connect a flue gas combustion analyser. Replace the cap after use.
Press the Service engineer button for more than 10 seconds
Turn the temperature control to maximum and the boiler will go to
maximum output
Run the boiler at maximum output for at least 10 minutes
After 10 minutes, check the maximum CO/CO
information in table 13 on page 35
Turn the temperature control down to minimum and allow the boiler
to stabilise for 10 minutes
After 10 minutes, check the minimum CO/CO
information in table 13 on page 35
2
Fig. 44 Flue integrity test
[1]
Air inlet sample point
[2]
Flue gas sample point
If the boiler fails the combustion test, check the following possible
causes:
Refer to section 5.5.1 and check the gas inlet pressure
Confirm the correct fan pressure.
Air intake for restrictions.
ErP
Greenstar FS CDi
6720818079 (2016/04)
Check the diaphragm in the fan for damage, replace if damaged.
Check the diaphragm for correct operation, the diaphragm opens
towards the fan.
Cleanliness of the heat cell, plus blockages in the condensate
disposal.
6.7
6.7.1
Check that the boiler is completely isolated from the gas supply.
Disconnect the mixing chamber from the fan.
Remove the connector and earth wire from the fan.
Remove the clips [1], castellated nuts[2a] and springs [2b] from the
studs [2].
Remove the rear nut [4a] from the rear stud [4].
Remove the burner cover plate [5] and fan [7] from the top of the

heat exchanger.

Remove the burner [6] and clean the components.
Do not use a wire brush.
readings against the
2
readings against the
2
1
Fig. 45 Burner removal
6.7.2
Refer to section 6.9.3 on page 36 for access to the fan intake.
Carefully withdraw the flap valve from fan intake tube and check for
soiling and splits, clean or replace as required.
Take care when refitting the flap valve, the flaps must open upwards
into the fan intake tube.
After re-assembly check CO/CO
"Setting the air/gas ratio" on page 34.
Heat exchanger

To clean the burner

WARNING: Burner
Do not remove the burner unless a new burner head
gasket is available for re-assembly.
7
2a
2b
2

To check the flap valve in the fan intake

2
SERVICING AND SPARES
1
4a
5
6
4
8
levels as described in the section
31