Zennio KLIC-TS User Manual

Knx – ab gateway for toshiba ac units

Advertisement

Quick Links

KLIC-TS
KNX – AB Gateway for
Toshiba AC Units
ZCL-TS
Application program version: [1.0]
User manual edition: [1.0]_a
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio KLIC-TS

  • Page 1 ➢ KLIC-TS KNX – AB Gateway for Toshiba AC Units ZCL-TS Application program version: [1.0] User manual edition: [1.0]_a www.zennio.com...
  • Page 2: Table Of Contents

    KLIC-TS CONTENTS Contents ............................2 Introduction .......................... 3 1.1 KLIC-TS ..........................3 1.2 Installation ........................4 1.3 Start-Up and Power Loss ....................5 Configuration......................... 6 2.1 General ..........................6 2.2 Inputs ..........................8 2.2.1 Binary Input ......................8 2.2.2 Temperature Probe ....................8 2.2.3...
  • Page 3: Introduction

    KLIC-TS 1 INTRODUCTION 1.1 KLIC-TS KLIC-TS from Zennio is a gateway that provides full-duplex communication between the KNX home automation system and Toshiba air-conditioning systems through connection wires provided by the latter. Because of this bidirectional communication, the air conditioning system can be controlled from the home automation system in the same manner as it is through its own controls.
  • Page 4: Installation

    5. KNX connector Figure 1. Element scheme. KLIC-TS connects to the KNX bus via the corresponding built-in terminal (5). Once the device is provided with power from the KNX bus, both the physical address and the KLIC- TS application program can be downloaded.
  • Page 5: Start-Up And Power Loss

    Important: if intending to control the A/C unit both through its incorporated wired remote control and through KLIC-TS, it must be taken into account that orders sent from the wired control will have a higher priority than those sent through KLIC-TS. In addition, certain parameterisations made in the device can be ignored.
  • Page 6: Configuration

    Logic functions: see section 2.3 A/C gateway: see section 2.4. The latter entails all functions specific to KLIC-TS, i.e., all the functions related to interfacing with the A/C unit and to the management of the climate control system. ETS PARAMETERISATION...
  • Page 7 KLIC-TS Heartbeat (Periodical Alive Notification): this parameter lets the integrator incorporate a 1-Bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically with value “1” to notify that the device is still working (still alive).
  • Page 8: Inputs

    All inputs are disabled by default. Depending on the function selected for each input, additional tabs will be included in the menu on the left. 2.2.1 BINARY INPUT Please refer to the “Binary Inputs” user manual, available in the KLIC-TS product section, at the Zennio website (www.zennio.com). 2.2.2 TEMPERATURE PROBE Please refer to the “Temperature Probe”...
  • Page 9: Motion Detector

    It is possible to connect motion detectors (models ZN1IO-DETEC-P and ZN1IO-DETEC- X from Zennio) to the input ports of KLIC-TS. Please refer to the “Motion Detector” user manual, available in the KLIC-TS product section, at the Zennio website (www.zennio.com). Notes: The ZN1IO-DETEC-P motion detector is compatible with a variety of Zennio devices.
  • Page 10: Logic Functions

    KNX bus, and to send the results through other communication objects specifically enabled for this purpose. KLIC-TS can implement up to 10 different and independent functions, each of them entirely customisable and consisting in up to 4 consecutive operations each.
  • Page 11: A/C Gateway

    KLIC-TS allows controlling and monitoring an air-conditioning unit in the same way it would be through the wired remote control it is provided with. Through the KNX bus, KLIC-TS can be sent orders to control the following basic functions of the air conditioning unit: On/Off switch of the air-conditioning unit.
  • Page 12 These functionalities imply changes in the state of the A/C unit, which therefore notifies KLIC-TS periodically about the current state. When KLIC-TS is notified about a change, it updates the status objects and sends them to the KNX bus. In addition, KLIC-TS provides an error management function (see section 2.4.4), which allows sending messages to the KNX bus in case the A/C unit reports any errors.
  • Page 13 KLIC-TS OPERATION MODES Figure 7. A/C Gateway. Configuration. Operation modes. KLIC-TS allows controlling the A/C unit operating mode through the following objects, available by default: “[AC] Mode”: 1-Byte object which allows selecting the A/C unit operation mode. There will be only taken in account values that are appropriated with some of available modes in Toshiba units, which are represented in Table 1 “[AA] Mode (status)”: 1-Byte object which allows knowing the A/C unit...
  • Page 14 Figure 8. A/C Gateway. Configuration. Flaps The Flaps function allows sending the A/C unit orders to switch the position of the flaps (or vanes) that direct the air flow outwards. To that end, KLIC-TS provides a percentage control. Flaps: allows the percentage control type which will be applied in flaps. Flaps position can be controlled through the 1-Byte object “[AC] Flaps: Percentage...
  • Page 15 ➢ Swing Object Polarity: sets the polarity of the above objects: “0 = Swing Off; 1 = Swing On” or “0 = Swing On; 1 = Swing Off”. Besides, KLIC-TS allows activating the standby function in case of being available in the unit: Standby Object: sets whether the A/C unit incorporates the standby function.
  • Page 16 3 (maximum) Table 3. Fan speed (three levels). In addition, KLIC-TS allows activating the automatic fan speed mode, in case fan mode is not active. The value 0% of the "[AC] Fan: Percentage Control” and "[AC] Fan: Percentage Control (Status)" objects, will be reserved for triggering such function and reporting whether it is currently active, respectively.
  • Page 17 Auto modes), provided that the limits are still within the predefined limits of the A/C unit. When KLIC-TS receives an order to send the A/C unit a setpoint, which is greater (or lower) than the configured limits, it will actually send the limit value.
  • Page 18 If during 3 minutes, no temperature values are received, values of the internal probe will be recuperated again to execute temperature control, in the same way as it will be controlled if KLIC-TS was configured disabling this option. If a new external temperature value is received, the control will be again executed by using this external value.
  • Page 19 KLIC-TS that the filter needs to be cleaned. Once the filter is cleaned, the alarm has to be reset through the object “[AC] Filter: Reset” sending the value “0” or “1”. OPERATING TIME Figure 13. A/C Gateway. Configuration. Operating time.
  • Page 20 ➢ Automatic Off Object Polarity: sets the polarity of the above object: “0 = Activate; 1 = Deactivate” o “0 = Deactivate; 1 = Activate”. ➢ Automatic Off Delay: sets the time, in seconds, KLIC-TS waits before switching the AC machine off. Any switch-off order received during the delay will abort the time count.
  • Page 21: Initial Configuration

    Initial Configuration: allows setting the desired initial state that KLIC-TS will send the A/C unit after programming or restarting the device: ➢ “Default”: the initial state will be the last one KLIC-TS is aware of. ➢ “Custom”: see section 2.4.2.
  • Page 22: Scenes

    2.4.3 SCENES The Scenes function allows defining a set of statuses (in terms of On/Off, mode, fan speed, etc.) that KLIC-TS will send to the A/C unit whenever it receives the corresponding scene values from the KNX bus. ETS PARAMETRISATION After enabling this function (see section 2.4.1), a new tab named Scenes will be...
  • Page 23 KLIC-TS Figure 18. A/C Gateway. Scenes. For every enabled scene, the particular parameters that should be configured are: Scene Number: sets the scene number (1-64) that, upon reception through the Scenes object (decreased by one), will trigger the corresponding orders, as defined next.
  • Page 24: Error Handling

    A/C unit and the configuration has been done, no response has been received by the A/C unit during a time. Errors in the A/C unit: errors reported by the A/C unit itself. KLIC-TS can notify the KNX bus about the reported error code, although referring to the specific documentation of the A/C unit is advisable in order to obtain further information.
  • Page 25 KLIC-TS Errors in the A/C unit: ➢ “[AC] AC Unit Error: Active Error”: 1-Bit object which indicates there is an error in A/C unit. ➢ “[AC] AC Unit Error: Error Code”: 14-Byte object which provides error code. In case the A/C unit reports an error, the former object will send a value of “1”, while the latter will report the corresponding error code.
  • Page 26: Annex I. Communication Objects

    KLIC-TS ANNEX I. COMMUNICATION OBJECTS “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 27 KLIC-TS 0xA (Inc. by 50%) 0xB (Inc. by 25%) 0xC (Inc. by 12%) 0xD (Inc. by 6%) 0xE (Inc. by 3%) 0xF (Inc. by 1%) 0x0 (Stop) 0x1 (Dec. by 100%) … 0x7 (Dec. by 1%) 4 Bit C T - - -...
  • Page 28 KLIC-TS 1 Bit C T - - - DPT_Switch [Ix] [Long Press] 1 Sending of 1 1 Bit C T - W - DPT_Switch [Ix] [Long Press] 0/1 Switching Switching 0/1 1 Bit C T - - - DPT_UpDown [Ix] [Long Press] Move Up Shutter...
  • Page 29 KLIC-TS -671088.64 - 2 Bytes C T - - - 9.xxx [Ix] [Long Press] Constant Value (Float) Float Value 670760.96 [Ix] [Long Press] Constant Value 2 Bytes C T - - - DPT_Value_2_Ucount 0 - 65535 0 - 65535 (Integer)
  • Page 30 KLIC-TS 45, 74, 103 1 Bit C - - W - DPT_Switch [Ix] Presence: Day/Night According to parameters 46, 75, 104 1 Bit C T R - - DPT_Occupancy [Ix] Presence: Occupancy State 0 = Not Occupied; 1 = Occupied 0 = Nothing;...
  • Page 31 KLIC-TS 0 = Auto 1 = Heat 0 = Automatic; 1 = Heating; 3 = 1 Byte C - - W - DPT_HVACContrMode 3 = Cool [AC] Mode Cooling; 9 = Fan; 14 = Dry 9 = Fan 14 = Dry...
  • Page 32 KLIC-TS 1 Bit C T R - - DPT_Switch [AC] Flaps: Swing (Status) 0 = Swing Off; 1 = Swing On 1 Bit C T R - - DPT_Switch [AC] Flaps: Swing (Status) 0 = Swing On; 1 = Swing Off...
  • Page 33 Join and send us your inquiries about Zennio devices: http://support.zennio.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. www.zennio.com info@zennio.com...