Table of Contents

Advertisement

1.
Abbreviations and Terms ...................................................................................................... 3
2.
Description ............................................................................................................................. 5
2.1
The Specification ................................................................................................................. 5
2.2
Compatibility ........................................................................................................................ 5
2.3
Communication.................................................................................................................... 5
2.4
Distributed Control ............................................................................................................... 5
2.5
The Building......................................................................................................................... 6
2.6
Design.................................................................................................................................. 7
3.
Parameters Overview ............................................................................................................. 8
3.1
Basic Properties................................................................................................................... 8
3.2
Operational Conditions......................................................................................................... 9
3.3
Basic Parameters................................................................................................................. 9
4.
Central Unit............................................................................................................................10
4.1
Basic Parts and Parameters................................................................................................10
4.2
User Accessible Memories ..................................................................................................10
4.3
Analog Outputs ...................................................................................................................12
4.4
Serial Communication Channels .........................................................................................13
4.4.1 Serial Communication Channel 1 (CH1).......................................................................13
4.4.2 Serial Communication Channel 2 (CH2).......................................................................16
4.4.3 Serial Communication Channel 3 (CH3).......................................................................16
4.5
Setting of CPU Parameters .................................................................................................17
4.5.2 Management of the user program source memory .......................................................20
5.
Input and Output Unit ...........................................................................................................21
5.1
Basic Functions...................................................................................................................21
5.1.1 Binary Inputs ................................................................................................................21
5.1.2 Binary Transistor Outputs.............................................................................................22
5.1.3 Binary Relay Outputs ...................................................................................................23
5.1.4 Analog Inputs of TC605, TC606, TC625, TC626 Modules ............................................24
5.1.5 Analog Inputs of the TC634 Module .............................................................................25
5.2
Special Functions................................................................................................................29
5.2.1 Interrupt Inputs.............................................................................................................29
5.2.2 Counter of Type 3 ........................................................................................................29
5.2.3 Admeasurement of Position by the Incremental Encoder..............................................30
5.2.4 Measurement of the Signals Period and Phase Shift ....................................................31
6.
Packaging ..............................................................................................................................32
7.
Transport ...............................................................................................................................32
8.
Storage ..................................................................................................................................32
9.
Installation.............................................................................................................................32
9.1
Principles of Proper Installation ...........................................................................................32
9.2
Ensuring of the Required Operational Temperature.............................................................33
9.3
The Mounting ......................................................................................................................34
9.4
Arrangement of Connecting of Terminal Boards..................................................................36
9.5
Connection of the PLC Inputs and Outputs..........................................................................45
9.5.1 Connection of the Protective Connector .......................................................................45
9.5.2 PLC Power Supply .......................................................................................................45
9.5.3 Connection of Binary Inputs .........................................................................................46
9.5.4 Connection of Binary Transistor Outputs ......................................................................47
9.5.5 Connection of Binary Relay Outputs.............................................................................48
9.5.7 Connection of TC634 Analog Inputs .............................................................................49
9.5.8 Connection of Analog Outputs......................................................................................51
9.5.9 Connection of the CH1 Interface ..................................................................................52
9.5.10 Connection of the CH2 Interface ..................................................................................54
9.5.11 Connection of the CH3 Interface ..................................................................................56
9.5.12 Connection of Interrupt Inputs ......................................................................................56
9.5.13 Connection of the Type 3 Counter ................................................................................56
9.5.14 Incremental Encoder Connection..................................................................................57
Technical equipment of TC600 PLC
Contents
1
TXV 138 08.02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TC600 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tecomat TC600 Series

  • Page 1: Table Of Contents

    Technical equipment of TC600 PLC Contents Abbreviations and Terms ...................... 3 Description ..........................5 The Specification ......................... 5 Compatibility ........................5 Communication........................5 Distributed Control ....................... 5 The Building......................... 6 Design..........................7 Parameters Overview ......................8 Basic Properties........................8 Operational Conditions......................9 Basic Parameters.........................
  • Page 2 Tecomat TC600 9.5.15 Connection of Inputs for Measurement of the Period and Phase Shift ......57 Attendance ..........................58 10.1 Instructions for Safe Attendance..................58 10.2 Putting into Operation ......................58 10.3 PLC Initialization .........................58 10.4 Operational Modes......................59 10.4.1 Change of Operational Modes..................59 10.4.2 Activities Performed at Changing of the PLC Mode on the Standard Basis....59 10.4.3 Optionally Performed Activities at Change of the PLC Mode........60...
  • Page 3: Abbreviations And Terms

    Tecomat programmable logic controllers are described in detail in the Handbook of the Tecomat PLC programmer, TXV 001 09.02 and Instruction set of the Tecomat PLC, TXV 001 05.02 . Detailed descrip- tion of modes of serial communication channels is given in the handbook Serial communication of Tecomat programmable logic controllers, TXV 001 06.02.
  • Page 4 Tecomat TC600 User Program set of all user processes designed for control of the given application Multiprogramming set of rules according to which individual user processes are activated Program Cycle set of user processes which are activated cyclically ac- cording to rules of multiprogramming...
  • Page 5: Description

    U strip. 2.2 Compatibility Although PLC's of the TC600 series are designed for the smallest appli- cations, use properties of large Tecomat PLC's remain retained. Significant property is uniformness of technical and program means for creation and...
  • Page 6: The Building

    Tecomat TC600 2.5 The Building The smallest fully functional PLC unit of the TC600 series is formed by the basic module (BM). It is produced in six designs which differ in the num- ber and type of inputs and outputs.
  • Page 7: Design

    TXN 061 84 Design Modules of PLC's of the TC600 series are designed as devices to be                    EN 50022 (idt EN 50022:1977). Metal jacket of the modules and mechanical arrange- ment guarantees higher resistance against interferences.
  • Page 8: Parameters Overview

    Tecomat TC600 3. Parameters Overview 3.1 Basic Properties Number of inputs and TC601 TC602 TC603 TC604 TC605 TC606 TC607 outputs of PLC TC600 TC621 TC622 TC623 TC624 TC625 TC626 series Binary inputs Total number of inputs Arrangement 1x8, 2x8, 1x8,...
  • Page 9: Operational Conditions

    Technical equipment of TC600 PLC 3.2 Operational Conditions       33 2000-3 Class of environment effect (mod IEC 364-3:1993) Range of operational tempera- 0 °C to +55 °C tures Average temperature during 24 max. +50 °C hours Allowed transportation tem- -25 °C to +70 °C perature Relative air humidity 50 % to 95 % without condensation...
  • Page 10: Central Unit

    4.1 Basic Parts and Parameters Central unit ensures the majority of PLC control functions. Due to its properties, it is ranked among Tecomat CPU D series. It contains especially the supply voltage converter, microcontroller, memories RAM and EEPROM, RTC circuit, lithium battery to supply voltage to the RAM mem-...
  • Page 11 Technical equipment of TC600 PLC Memory of CPU Memory of CPU parameters is power-independent memory designed for parameters storage of parameters that can be set in the PLC SET mode. Contents of the memory remain retained even when the PLC power supply is turned off or if the battery is discharged.
  • Page 12: Analog Outputs

    Tecomat TC600 4.3 Analog Outputs Analog outputs are used for control of voltage-control action elements of the controlled object. They are arranged in a group with a common terminal of the analog ground. Analog outputs are galvanically connected with the CPU control circuits.
  • Page 13: Serial Communication Channels

    Technical equipment of TC600 PLC 4.4 Serial Communication Channels Standard design of all PLC's of the TC600 series is equipped with two communication channels. Third communication channel is added per order (see Article 2.5). 4.4.1 Serial Communication Channel 1 (CH1) To program the PLC, CH1 is designed for connection of the PLC to a superior system.
  • Page 14 For the communication, PLC's of the TC600 series use binding circuits of signals TxD (Transmit Data), RxD (Receive Data). Signal RTS (Request To Send) is used internally for control of the transmitter activation.
  • Page 15 For the communication, PLC's of the TC600 series use only binding cir- cuits of signals TxD (Transmit Data) and RxD (Receive Data) of the RS-422 interface.
  • Page 16: Serial Communication Channel 2 (Ch2)

    Setting of the required mode is given in Article 4.5, detailed description of the modes is given in the handbook Serial Communication of Tecomat Programmable Logic Controllers, TXV 001 06.02. CH2 interface is optional (see Article 2.5). Parameters of the interface are given under item 4.4.1.
  • Page 17: Setting Of Cpu Parameters

    Technical equipment of TC600 PLC 4.5 Setting of CPU Parameters Mode SET CPU parameters are set in the setting mode (mode SET). To set and display parameters, the PLC front board is equipped with buttons SET and MODE and a one-place seven-segment LED display. Displaying of In the SET mode, all data are displayed in the rotational way, that is, parameters...
  • Page 18 Tecomat TC600 - channel is off (no other channel parameter is set) - connection of a superior system (a PC or an active operation board) - interconnection with other PLC's or regulators in the EPSNET mul- timaster network with fast data exchange...
  • Page 19 Technical equipment of TC600 PLC Tab. 4.2 List of available transmission speeds of CH1, CH2 and CH3 in various modes Speed Channel mode Speed Channel mode 0.3 kb/s PC,MAS 28.8 kb/s PC,PLC,MAS 0.6 kb/s PC,MAS 38.4 kb/s PC,PLC,MAS 1.2 kb/s PC,MAS 57.6 kb/s PC,PLC,MAS...
  • Page 20: Management Of The User Program Source Memory

    Tecomat TC600 Detection of the CTS signal may be either off or on. By pressing the SET button we change the setting, by pressing the MODE button we save the set value and move to setting of another parameter. When detection of the CTS signal is on, before transmission of the reply the PLC tests state of the CTS signal after setting the RTS signal.
  • Page 21: Input And Output Unit

    Technical equipment of TC600 PLC 5. Input and Output Unit 5.1 Basic Functions The majority of input and output circuits of the PLC is realized on the in- put and output unit. Individual types of the series differ in the type of the used input and output unit or in modification of the unit fitting with circuits of binary and analog inputs and binary transistor and relay outputs.
  • Page 22: Binary Transistor Outputs

    Tecomat TC600 5.1.2 Binary Transistor Outputs Binary transistor outputs serve for control of two-state action and signal- ling elements, which require high count and el. closing speed. To increase functional reliability, every output is galvanically separated by an optical ele- ment from internal circuits and is protected against short circuit, overvoltage and reversing of polarity.
  • Page 23: Binary Relay Outputs

    Technical equipment of TC600 PLC 5.1.3 Binary Relay Outputs Binary relay outputs serve for control of two-state action and signalling elements of the controlled object, supplied by alternating voltage or voltage higher than the allowed range of closed voltage of transistor outputs. Out- puts are realized by the closing voltage-free contact relay led out independ- ently or in a group with one common connector.
  • Page 24: Analog Inputs Of Tc605, Tc606, Tc625, Tc626 Modules

    Tecomat TC600 5.1.4 Analog Inputs of TC605, TC606, TC625, TC626 Modules Analog inputs serve for connection of up to four analog signals of the controlled object to the PLC. They are intended especially for processing of analog signals with normalized current or voltage level. Input circuits are galvanically connected with internal PLC control circuits.
  • Page 25: Analog Inputs Of The Tc634 Module

    Technical equipment of TC600 PLC 5.1.5 Analog Inputs of the TC634 Module Analog inputs serve for connection of up to eight analog signals of the controlled object to the PLC. They are intended especially for measurement of temperatures using passive resistance temperature scanners, and for processing of analog signals with normalized current or voltage level.
  • Page 26 Tecomat TC600 Parameters of inputs Scanner type Pt100 W = 1.385 for TC634 resistance (can be selected by a program) Pt100 W = 1.391 temperature scanners Ni1000 W = 1.617 Ni1000 W = 1.500 general 0 to 630  general 0 to 2520  Measurement range see table 5.1a...
  • Page 27 Format PID In the PID format, value of the input variable is passed, converted to the format compatible with PID instructions of Tecomat programmable logic controllers. The value can be interpreted as percentage expression of the full measurement range. Exceeding of the range is signalled by the value $7FFF.
  • Page 28 Tecomat TC600 Resolution of input Resolution means the smallest detectable change of the input variable data expressed in technical units. It represents the value of the least significant bit of input data (LSB). Tab. 5.2a. Resolution of input data of TC634 resistance temperature scan-...
  • Page 29: Special Functions

    Technical equipment of TC600 PLC 5.2 Special Functions Basic BM functions of TC603 to TC607 can be extended by special functions. Special functions use standard-fitted inputs, or possibly PLC outputs, but their attendance requires more complex shell algorithms or complementa- tion of the basic technical equipment of the input and output unit.
  • Page 30: Admeasurement Of Position By The Incremental Encoder

    Tecomat TC600 Parameters of the TC601, TC602 TC603 to TC607 type 3 counter Number of counters Nominal voltage 24 V- Voltage for log. 0 max. 14 V- (opening of the circuit) Voltage for log. 1 min. 18.5 V- (closing of the circuit) max.
  • Page 31: Measurement Of The Signals Period And Phase Shift

    Technical equipment of TC600 PLC 5.2.4 Measurement of the Signals Period and Phase Shift The function allows for measurement of the signal period at the BM input Properties of the DI0 or measurement of the phase shift of two signals at BM inputs DI0 and function DI1.
  • Page 32: Packaging

    9. Installation 9.1 Principles of Proper Installation Tecomat PLC's of the TC600 series are built-in devices designed for being mounted in closed cases. From the viewpoint of correct function of the system, it is necessary to choose the size and design of the case so that by the construction arrangement, it is possible to limit as much as possible the effect of especially power parts of the device on the PLC.
  • Page 33: Ensuring Of The Required Operational Temperature

    Design Tecomat Programmable Logic Controllers, TXV 001 08.01. 9.2 Ensuring of the Required Operational Temperature In cases without forced inside air circulation, the PLC must be placed in such a way so that the distance between the bottom and top side of the PLC and inside sides of the case is at least 100 mm.
  • Page 34: The Mounting

    (idt EN 50022:1977). Outside proportions of the PLC BM, EM and EM/2 are apparent from Figs. 9.1, 9.2 and 9.3. Fig. 9.1 Mechanic proportions of PLC BM of the TC600 series Fig. 9.2 Mechanic proportions of PLC EM of the TC600 series Fig.
  • Page 35 Technical equipment of TC600 PLC EM and EM/2 are placed always on the right side from the BM. EM (EM/2) are connected mutually as well as with the BM by a band cable which is part of the EM (EM/2). Cable socket is connected into a socket plug on the right side of the BM (EM/2).
  • Page 36: Arrangement Of Connecting Of Terminal Boards

    Tecomat TC600 9.4 Arrangement of Connecting of Terminal Boards terminal boards A, B of binary inputs terminal board D of binary transistor outputs terminal board P of optional analog outputs or CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232...
  • Page 37 Technical equipment of TC600 PLC terminal boards A, B, C of binary inputs terminal boards D, E of binary transistor outputs terminal board P of optional analog outputs or CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232 terminal board N of optional CH2 interface terminal board M of the PLC power supply socket plug R for connection of the EM...
  • Page 38 Tecomat TC600 terminal boards A, B of binary inputs terminal board D of binary transistor outputs terminal board E of binary relay outputs terminal board P of optional analog outputs or CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232...
  • Page 39 Technical equipment of TC600 PLC terminal boards A, B of binary inputs terminal boards E, F, G, H of binary relay outputs terminal board P of optional analog outputs or CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232 terminal board N of optional CH2 interface terminal board M of the PLC power supply socket plug R for connection of the EM...
  • Page 40 Tecomat TC600 terminal boards A, B of binary inputs terminal board C of analog inputs terminal boards E, F of binary relay outputs terminal board P of optional analog outputs or CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232...
  • Page 41 Technical equipment of TC600 PLC terminal boards A, B of binary inputs terminal board C of analog inputs terminal board D of binary transistor outputs terminal boards E, F, G, H of binary relay outputs terminal board P of optional analog outputs of CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232 terminal board N of optional CH2 interface...
  • Page 42 Tecomat TC600 terminal boards A, B, C of binary inputs terminal boards D, E, F of binary transistor outputs terminal board P of optional analog outputs or CH3 terminal board K of optional CH1 interface socket L of CH1 interface RS-232...
  • Page 43 Technical equipment of TC600 PLC terminal boards A, B of binary inputs terminal board C of binary transistor outputs socket for connection to the BM socket plug for connection of the EM or EM/2 connector for connection of the protective conductor Fig.
  • Page 44 Tecomat TC600 terminal boards A, B, C, D of binary inputs socket for connection to the BM socket plug for connection of the EM or EM/2 connector for connection of the protective conductor Fig. 9.17 Arrangement of Connection Terminal Boards of TC633 EM/2...
  • Page 45: Connection Of The Plc Inputs And Outputs

    Technical equipment of TC600 PLC 9.5 Connection of the PLC Inputs and Outputs With the exception of the protective grounding connector and the CH1 RS-232 interface, PLC inputs and outputs are connected using removable terminal boards which are inserted into the appropriate socket plugs of in- puts and outputs.
  • Page 46: Connection Of Binary Inputs

    TC607 (TC621 to TC626) is indicated. Fig. 9.17 Example of connection of switches to binary inputs of the PLC of the TC600 series Supply voltage of a group of switches may be connected in arbitrary po- larity, within the group individual inputs must be poled identically.
  • Page 47: Connection Of Binary Transistor Outputs

    Fig. 9.18 Example of connection of loads to binary transistor outputs of the PLC of the TC600 series For fitting and marking of terminal boards of binary transistor outputs of individual PLC types see Article 9.4.
  • Page 48: Connection Of Binary Relay Outputs

    Fig. 9.19 Example of connection of loads to binary relay outputs of the PLC of TC600 series For fitting and marking of terminal boards of binary relay outputs of indi- vidual PLC types see Article 9.4.
  • Page 49: Connection Of Analog Inputs Of Tc605, Tc606, Tc625, Tc626

    C6 connector. Examples of the installation realization in the distribution board are contained in the handbook Design of Tecomat Programmable Logic Controllers, TXV 001 08.01. For fitting of terminal boards of analog inputs of individual PLC types see Article 9.4.
  • Page 50 Tecomat TC600 Configuration jumpers Fig. 9.21 Example of connection of current and voltage signals to the TC634 analog inputs Fig. 9.22 Example of connection of resistance temperature scanners to the TC634 analog inputs Type of the analog Every input must be set individually by the jumper for the direct-current voltage or current signal supply.
  • Page 51: Connection Of Analog Outputs

    Technical equipment of TC600 PLC 9.5.8 Connection of Analog Outputs Optionally fitted BM analog outputs of TC601 to TC607 are led out to connectors P1 to P10 of the terminal board marked as OPTIONAL I/O. Lead out of analog Connector Signal Note outputs of the OT-13...
  • Page 52: Connection Of The Ch1 Interface

    Fig. 9.24 Connection of loads to the OT-14 piggyback analog outputs Examples of the installation realization in the distribution board are con- tained in the handbook Design of Tecomat Programmable Logic Controllers, TXV 001 08.02. For fitting of terminal boards of analog outputs of individual PLC types see Article 9.4.
  • Page 53 Marginal network equipment Internal network equipment Fig. 9.25 Interconnection of two CH1 interfaces RS-485 of the PLC of TC600 series Optional CH1 RS-422 Binding circuits of the interface are led out to connectors K1 to K6 of the interface terminal board marked as SERIAL CHANNEL 1.
  • Page 54: Connection Of The Ch2 Interface

    Use of the signal is described in the handbook Serial Communication of Tecomat Programmable Logic Controllers, TXV 001 06.02 . Still level of the signal corresponds with the value of logical 1. In Fig. 9.27, five-conductor interconnection with the possibility of CTS signal detection is shown.
  • Page 55 Interface of the connected device Fig. 9.28 Three-conductor interconnection of the CH2 interface RS-232 of the PLC of TC600 series Optional CH2 RS-485 Binding circuits of the interface are led out to connectors N1 to N6 of the interface terminal board marked as SERIAL CHANNEL 2.
  • Page 56: Connection Of The Ch3 Interface

    (DI1) in the way illustrated in the scheme in Fig. 9.29. In the case that the RESET input is not used, it must be serviced by connection to voltage cor- responding with log. 1. Fig. 9.29 Connection of the type 3 counter of the PLC of TC600 series TXV 138 08.02...
  • Page 57: Incremental Encoder Connection

    Fig. 9.30 Connection of the incremental encoder with outputs with the open PNP collector (on the left) and NPN collector (on the right) to the PLC of TC600 series 9.5.15 Connection of Inputs for Measurement of the Period and Phase...
  • Page 58: Attendance

    Tecomat TC600 10. Attendance 10.1 Instructions for Safe Attendance When the power supply is on, it is not allowed to disconnect and connect supplying terminal boards neither to connect and disconnect individual con- ductors of the terminal boards. When programming controlling PLC algorithms, the possibility of an error...
  • Page 59: Operational Modes

    Transfer between RUN and HALT modes controlled by the attendance persons is possible only using the superior system equipped with an inte- grated development environment for programming of the Tecomat PLC's or with a monitoring and controlling program. Transfer between the modes has practical foundation only in the phase of debugging of the user program.
  • Page 60: Optionally Performed Activities At Change Of The Plc Mode

    Tecomat TC600 If a critical error occurs in the course of activities performed at transfer between the modes, the PLC sets the HALT mode, shows on the display the error code, and expects removal of the error cause. Do not in any case replace stopping of control using the HALT mode by function of the button CENTRAL STOP.
  • Page 61: Programming And Debugging Of The Plc Program

    10.5 Programming and Debugging of the PLC Program PLC programming Programming of control algorithms and testing of correctness of the written programs for TECOMAT PLC's is performed using computers of the PC standard. For connection with the PLC, the serial channel of these com- puters is used.
  • Page 62: Configuration Constants In The User Program

    Tecomat TC600 10.5.1 Configuration Constants in the User Program Configuration of Configuration constants are automatically generated during compilation constants for setting of the user program, and they form its non-separable part. They carry infor- mation on the required PLC mode and its use. Constants can be set using...
  • Page 63: Software Configuration

    In the xPRO program, sw configuration is entered using the directive #unit . Structure of the directive is identical with other Tecomat PLC direc- tives. Some parameters intended for description of more extensive system, have the character of a constant in the TC600 series.
  • Page 64 Tecomat TC600 - address of the table containing the initialization data INITAB Parameter is entered symbolically, for example IniCH2, or absolutely, for example T0 (names used in the following ex- amples of declarations are not mandatory). Entering of the parameter for CH2, CH3, analog inputs and some special functions (see further) is mandatory.
  • Page 65: Servicing Of Binary Inputs

    Technical equipment of TC600 PLC 10.5.3 Servicing of Binary Inputs BM binary inputs are assigned to the scratchpad memory together with Declaration of BM binary outputs by the directive #unit with general structure according to binary inputs 10.5.2. #unit 0, 0, Digit_600, 2, 1, X0, Y0, On Example of declaration ;...
  • Page 66: Servicing Of Binary Outputs

    For structure of the physical address see item 10.5.12. Checking of overload PLC's of the TC600 series allows for program-checking of outputs over- of binary outputs load. This state is signalled at bit S35.1: S35.1 = 0 - outputs are in correct state S35.1 = 1...
  • Page 67 Technical equipment of TC600 PLC #unit 0, 0, Analog_600_, 8, 0, X2, 0, On, IniAI Example of ; analog inputs declaration for BM of TC605 and TC606 #unit 0, 2, Analog_600_, 8, 0, X2, 0, On, IniAI Example of declaration ;...
  • Page 68 Tecomat TC600 Servicing of TC634 TC634 analog inputs occupy 16 bytes in the inputs image in the scratch- analog inputs pad (parameter of the directive #unit POC_IN = 16). Binary representa- tion of the inputs state is overwritten in the cycle loop into the scratchpad zone with the initial address defined by the parameter Z_IN of directive #unit.
  • Page 69 Technical equipment of TC600 PLC Valid values of the The following table gives allowed values of the CONT control word with TC634 control word the corresponding selections: CONT Input type Scanner/range type Format of input data $8020 Resistance Pt100, W100 = 1.385 0 to 65535 $8120 temperature...
  • Page 70: Servicing Of Analog Outputs

    Tecomat TC600 10.5.6 Servicing of Analog Outputs Declaration of optional In the case of fitting the optional piggyback OT-13 or OT-14, the sw con- analog outputs figuration of BM standard-fitted inputs and outputs is complemented in the way which depends on the BM type.
  • Page 71: Servicing Of Interrupt Inputs

    PC, channels CH2 and CH3 have selectable modes (see Article 4.4 and 4.5). Detailed description of the modes including the servicing table is given in the handbook Serial Communication of Tecomat Programmable Logic Controllers, TXV 001 06.02 .
  • Page 72 Time between two user program cycles following one after an- other. Lasting time of the cycle loop depends on the PLC set con- figuration. - max. 4 ms for the TC600 series - cycle lasting time Lasting time of the user program cycle depends on the task extent and structure of the user program.
  • Page 73 Technical equipment of TC600 PLC - output delay Closing time or opening time of the output switch - typ. 4 ms for relay outputs - max. 400 s for transistor outputs - time of the program response (see further text) - time of the programmable controller response (see further text) Programmable Time diagram in Fig.
  • Page 74 Tecomat TC600 Response of the Time diagram in Fig. 10.2 gives prolongation of the response time of the programmable programmable controller to change of the signal at the interrupt input at synchronization of the response with the user program cycle. In the P42...
  • Page 75 Technical equipment of TC600 PLC Interrupt period To determine the IRQ period, that it, the interval between two IRQ's from the signal at one interrupt input, it is necessary to realize that the IRQ from signals at individual interrupt inputs are asynchronous towards the program cycle, and at the same time they may be asynchronous towards one an- other.
  • Page 76: Servicing Of The Type 3 Counter

    Tecomat TC600 10.5.9 Servicing of the Type 3 Counter Declaration of the Declaration of the counter is performed by the directive with the #unit type 3 counter general structure according to item 10.5.2. Parameter of directive is INITAB mandatory. The initialization table serves for identification of the counter type.
  • Page 77 Technical equipment of TC600 PLC CONT.0 - blocking of the counter 0 = blocking of the counter 1 = counter running CONT.4 - resetting of the counter Change of the bit state from 0 to 1 performs reset of the counter and setting to zero of all bits of the STAT state word (while in state 1, the counter is not reset).
  • Page 78 Tecomat TC600 Time diagrams of the counter modes counter Fig. 10.6 Time diagram of the freely running counter counter Fig.10.7 Time diagram of the self-filling counter with pre-selection TXV 138 08.02...
  • Page 79: Incremental Encoder Servicing

    Technical equipment of TC600 PLC 10.5.10 Incremental Encoder Servicing Declaration of Declaration of admeasuring is performed by the directive with #unit admeasuring general structure according to item 10.5.2. Declaration example #unit 0, 0, IRC_600, Xn, Yn, On Parameter of directive is input symboli- TYP, POC_IN, POC_OUT #unit...
  • Page 80 Tecomat TC600 Image of outputs Image of outputs contains the CONT control word, pre-selection of the admeasured value for the ascending direction, and pre-selection of the ad- measured value for the descending direction. State of bits CONT.6 and CONT.7 is accepted immediately after their writing to the scratchpad, state of other bits in CONT as well as of the pre-selections is accepted in the cy- cle loop, or upon termination of the P44 interrupt process, respectively.
  • Page 81: Measurement Of The Signal Period And Phase Shift

    Technical equipment of TC600 PLC Zero IRC pulse Pre-selection for the descending direction Pre-selection for the descending direction Admeasured value Fig.10.9 Time diagram of admeasuring using incremental encoder 10.5.11 Measurement of the Signal Period and Phase Shift Function declaration The function declaration is performed by the directive with general #unit structure according to item 10.5.2.
  • Page 82 Tecomat TC600 Graphic illustration of time of the period and phase shift signal period time at BM input DI0 phase shift of signals at BM inputs DI1 and DI0 Measurement mode Control of the measurement mode is done by a program using the image control of the binary output DO0 of BM (by image Yn.0).
  • Page 83 Technical equipment of TC600 PLC Period cons2 Frequency ;frequency = 1 / period Phase shift Measurement of the phase shift is used for signals with the same fre- measurement quency. The time difference between descending edges of two different sig- nals connected to inputs DI1 and DI0 of BM is measured.
  • Page 84: Physical Addresses Of Inputs And Outputs

    Tecomat TC600 10.5.12 Physical Addresses of Inputs and Outputs Structure of the Physical address of binary and analog inputs and outputs has the fol- physical address lowing structure: address upper byte address lower byte A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 A0...
  • Page 85: Instruction Set

    Technical equipment of TC600 PLC 10.7 Instruction Set The set of instructions and system services of PLC's of the TC600 series is compatible with other Tecomat PLC's. The central unit of the D series contains the extended instruction set which, besides instructions of the re- duced and standard instruction set, contains instructions designed form the most efficient PLC's.
  • Page 86: Diagnostics And Removal Of Faults

    Set of Tecomat PLC, TXV 001 05.02 11. Diagnostics and Removal of Faults The PLC diagnostic The Tecomat PLC diagnostic system is a part of the standard sw and hw system equipment of the PLC's. It is active starting from turning on of the PLC power supply and operates independently of the user.
  • Page 87: User Program Errors

    Technical equipment of TC600 PLC The following abbreviations and terms are used in the overview of error codes: - address of instruction in which the error occurred (program counter) - activation of inputs and outputs: $40 = activation of inputs $80 = activation of outputs $C0 = activation of inputs and outputs - upper byte of the physical address of inputs and outputs at which...
  • Page 88 Tecomat TC600 80 09 00 00 the program has been compiled for another series of central units The compiler was set for another series of central units. It is necessary to select the correct series of central units in the...
  • Page 89: Errors In The Peripheral System

    Technical equipment of TC600 PLC 80 19 PC PC error of BP instructions nesting The BP instruction cannot be used in processes P50 to P57 (calling of the debugging process P5n in another P5m pro- cess). 80 1A PC PC process for servicing of the BP is not programmed The debugging process P5n called by the BP instruction is not programmed.
  • Page 90: Other Errors

    Tecomat TC600 A part of memory in the central unit reserved for initializa- tion data of the given type of inputs or outputs has been overfilled. 81 00 36 AJ 36 AJ number of the initialization table is greater than the maxi-...
  • Page 91: Errors Of Serial Communication

    Technical equipment of TC600 PLC 11.4.1 Errors of Serial Communication This group of errors is written only to the local stack without the possibil- ity of evaluation by the user program. Errors of the serial 10 05 wrong start delimiter communication 11 05 SD parity error...
  • Page 92: User Program Errors

    Tecomat TC600 08 00 00 00 exceeding of the first limit of guarding the cycle time The cycle time has been longer than the set warning value. 09 00 00 00 wrong system time of the RTC circuit The current time must be written from the superior system.
  • Page 93 Technical equipment of TC600 PLC No CH1 must be used for the PLC programming, correct the situa- tion. Yes Continue at item 6. 5. Do you use channel CH1 for connection? No Continue at item 10. Yes  6. Do you use the standard-fitted CH1 RS-232 interface for communica- tion? No Continue at item 9.
  • Page 94 Tecomat TC600 Checking of the cable Is the cable inserted in the correct COM socket at the PC? No Correct the situation. Yes  Are proper cables used? No Correct the situation, check connection of cables of your own pro- duction.
  • Page 95: Removal Of Faults

    PLC's of the TC600 series are complex electronic devices fitted with parts for printed mounting and parts sensitive to the electrostatic charge. Therefore the producer recommends to perform post-guarantee repairs only by exchanging the whole units.
  • Page 96: Checking Of Voltage Of Binary Transistor Outputs

    Tecomat TC600 Allowed voltage tolerance for closing of fast inputs (DI0 to DI3 of mod- ules TC603 to TC607) is17,5 V~ to 30 V~ or 18,5 V- to 30 V-. Allowed volt- age tolerance for opening of the input is0 V~ to 13,5 V~ or 0 V- to 14 V-.
  • Page 97 By switching parity off security of transmitted data is decreased (for details see Serial communication of TECOMAT program- mable logic controllers and TECOREG regulators, version 7 and higher, order number TXV 001 06.02 handbook).

Table of Contents