A50E-2 Line Relay Unit Installation Sheet
Description
The A50E-2 Line Relay Unit is an addressable device used to
provide one Form C change over dry relay contact to control
external appliances (door closers, fans, dampers, etc.) or
equipment shutdown. The system firmware ensures that the
relay is in the proper ON/OFF state. Upon command from the
control panel, the relay energizes. TB2-6 and TB2-7 provide a
normally-closed relay connection; TB2-7 and TB2-8 provide a
normally-open relay connection. One device address is
required.
Up to 127 devices can be assigned to the loop. All devices
incorporate a binary DIP switch enabling them to be given a
unique address. A red LED indicator illuminates when the unit
has activated.
Installation
Notes
This module complies with the requirements of EN 54-18.
If the module is used in conditions or circumstances that
do not comply with those tested for and allowed in
EN 54-18, operation may be impaired, and the supplier will
not be liable for any injury suffered or damage caused as
a result. You must contact our technical support
department for advice if the device is to be used in
conditions that differ from those prescribed in EN 54-18.
This module will not operate without electrical power. As
fires frequently cause power interruption, we suggest you
discuss further safeguards with your local fire protection
specialist.
© 2013 UTC Fire & Security. All rights reserved.
www.acornfiresecurity.com
WARNING:
present at terminals even when the power is shut off. Take
proper precautions to avoid injury or death.
Note:
as an assembled unit; it contains no user-serviceable parts and
should not be disassembled
To install the device:
1.
2.
Notes:
Mounting
The A50E-2 can be mounted using any of three methods:
The unit can be mounted in a European 100mm square box.
The terminal blocks will accept 14, 16, or 18 AWG wire (0.75,
1.0, 1.5, mm²). Sizes 16 and 18 AWG are preferred.
1 / 2
www.acornfiresecurity.com
Electrocution hazard. Dangerous voltages may be
The A50E-2 Line Relay Unit is shipped from the factory
Verify that all field wiring is free of opens, shorts, and
ground faults.
Make all wiring connections as shown in Figure 1.
If a 2 in. (51 mm) 1-gang box is used, conduit can enter
the electrical box through only one knockout hole.
If a 2-1/2 in. (64 mm) 1-gang box is used, conduit can
enter the electrical box through one or both
knockout holes.
A DIN rail method for mounting multiple/single units
Adaptor plates for accessory box mounting
Single box mounting
P/N 501-1761ZE-1-05 (EN) • REV 05 • ISS 07JUN13

Advertisement

loading

Summary of Contents for Ziton A50E-2

  • Page 1 Mounting Description The A50E-2 can be mounted using any of three methods: The A50E-2 Line Relay Unit is an addressable device used to provide one Form C change over dry relay contact to control • A DIN rail method for mounting multiple/single units external appliances (door closers, fans, dampers, etc.) or...