NOTE: Inspect for shipping damage. Notify freight carrier or store where purchased immediately if damage is present. To avoid risk of personal injury
and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a licensed professional immediately. Current copies
of the product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER
HAZARDS. OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL
INJURY AS WELL AS PROPERTY DAMAGE.
USE ONLY WITH POTABLE WATER SYSTEMS.
Do not operate in a setting with freezing
temperatures or where the temperature can exceed 100°F and do not
exceed the maximum working pressure specified for this Product.
READ
INSTALLATION & OPERATION INSTRUCTIONS.
FAILURE TO FOLLOW THE INSTRUCTIONS AND WARNINGS MAY
RESULT IN SERIOUS OR FATAL INJURY AND/OR PROPERTY
DAMAGE, AND WILL VOID THE PRODUCT WARRANTY.
PRODUCT MUST BE INSTALLED BY A LICENSED PROFESSIONAL.
FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND
REGULATIONS. IN THE ABSENCE OF SUCH CODES, FOLLOW THE
CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND
NATIONAL ELECTRIC CODE, AS APPLICABLE.
This Product, like most Products under pressure,
may over time corrode, weaken and burst or
explode, causing serious or fatal injury, leaking or flooding and/or
property damage. To minimize risk, a licensed professional must install
and periodically inspect and service the Product. A drip pan connected to
an adequate drain must be installed if leaking or flooding could cause
property damage. Do not locate in an area where leaking could cause
property damage to the area adjacent to the appliance or to lower floors
of the structure.
RUPTURE OR EXPLOSION HAZARD. Do not
expose Product to freezing temperatures or
temperatures in excess of 100°F. Do not adjust the pre-charge or
re-pressure this Product except during installation or regular inspection.
Replace the Product and do not adjust the precharge if corroded,
WATER PRESSURE BOOSTER SYSTEM
INSTALLATION & OPERATION INSTRUCTIONS
CAREFULLY
THE
PRODUCT
AMTROL PRESSURISER
WITH GUARDIAN CP
Models RP-10HP, RP-15HP and RP-25HP
damaged or with diminished integrity. Adjustments to pre-charge must be
done at ambient temperature only. Failure to properly size the Product or
follow these instructions may result in excessive strain on the system and
may lead to Product failure, serious or fatal personal injury, leakage and/
or property damage.
working pressure designated in the Product Manual, whichever is less.
At least once every 3 years or if discharge is present, a licensed
THIS
professional should inspect the temperature and pressure relief valve
and replace if corrosion is evident or the valve does not function.
FAILURE TO INSPECT THIS VALVE AS DIRECTED COULD RESULT
IN UNSAFE TEMPERATURE OR PRESSURE BUILD-UP WHICH CAN
RESULT IN PRODUCT FAILURE, SERIOUS INJURY OR DEATH
AND/OR
SEVERE
PRODUCT WARRANTY.
You should test for corrosive elements, acidity, total solids and other
relevant contaminants, including chlorine and treat your water appropriately
to insure satisfactory performance and prevent premature failure.
cause cancer and birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov.
CONTROL
A relief valve must be installed to prevent pressure
in excess of local code requirement or maximum
PROPERTY
DAMAGE
Chlorine & Aggressive Water: The water quality
can significantly influence the life of this Product.
This product can expose you to chemicals including
lead, which is known to the State of California to
®
AND
VOID
THE

Advertisement

loading
Need help?

Need help?

Do you have a question about the RP-10HP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Amtrol RP-10HP

  • Page 1 Current copies of the product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing. THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS.
  • Page 2 The AMTROL Pressuriser should only be ® will cause damage to the motor. The pump models RP-10HP, RP-15HP connected to a municipal, cold water supply, and in and RP25-HP are pre-wired for 115 vac; however, they can be rewired to systems with a minimum pressure of 10 psig at all times, measured under be used with 230 vac.
  • Page 3 Start-Up Maintenance BEFORE CONTINUING, ENSURE THAT ALL Your AMTROL Pressuriser unit, including the pump, must be WIRING IS COMPLETED AND THE UNIT IS periodically inspected by a licensed professional for signs of GROUNDED. CHECK FOR OPEN DRAIN VALVES OR OTHER SOURCES OF FLOODING BEFORE STARTING UNIT.
  • Page 4 MARK OF THE ORIGINATOR 1400 Division Road, West Warwick, RI USA 02893 T: 800.426.8765 www.amtrol.com © 2019 Worthington Industries Inc. Part #: 9040B140 (01/19) One or more features of this product are covered by U.S. patents, visit www.amtrol.com/patents for more information.

This manual is also suitable for:

Rp-25hpRp-15hp